3. The plans should note that an NFPA-72 fire alarm will be provided. Everett ORD. 1902-92 <br /> Response: A note that an NFPA-72 fire alarm will be provided. Everett ORD. 1902-92 has <br /> been added &clouded on the title sheet (Re: T0.1). <br /> 4. The roof insulation installed under the roof sheathing creates an attic that must be ventilated. <br /> An unvented attic should be designed per Section 1203.3, the insulation revised to rigid <br /> insulation placed on top of the sheathing or attic ventilation should be provided and detailed. <br /> Section 1203.2 <br /> Response: Revised & clouded the roof insulation to rigid insulation placed on top of the <br /> sheathing.(Re:A4.0 &A4.1). <br /> 5. Storefront glazing adjacent to the entry doors should be shown as safety glazing. Section <br /> 2406.4.2 <br /> Response: A note has been added & clouded to the floor plan sheet (Re:A2.1) and the <br /> window schedule (Re:A4.1). <br /> 6. For interior slab-on-grade insulation, the insulation should be placed on the on the inside of <br /> the foundation wall and extend downward to the bottom of the slab. Once there, it may <br /> extend horizontally for the remainder of the 24': Section C402.2.6 <br /> Response: A interior slab-on-grade insulation has been added notated & clouded to the <br /> foundation plan sheet (Re:A3.0) and the building &wall sections (Re:A4.0&A4.1). <br /> 7. The air barrier should be detailed on the plans. Testing requirements should be noted. Section <br /> C402.5 <br /> Response: The air barrier details and testing requirements have been added and clouded on <br /> the building section,details & plan sheets (Re:A2.1, A4.0 &A4.1). <br /> If the are any questions or clarification needed for the above referenced corrections please contact <br /> James Thomas or Matt Schreifels at 425.259.0661 or by email at jthomas@arch-design or mattOarch- <br /> design.net <br /> Sincerely, <br /> James Thomas Matt Schreifels <br /> Architect Project Manager <br /> (L)� 1 <br /> • <br />