Laserfiche WebLink
' WCPM Splits February 07,2017 <br /> Mechanical Specifications-Split System Air Conditioning Units(Small) <br /> Item: Al,A2 Qty: 2 Tag(s): HP-1, HP-2 <br /> General -4TWR5 <br /> The 4TWR5 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor <br /> ambient temperatures as high as 115 F. Cooling capacities are matched with a wide selection of air handlers and <br /> furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. <br /> Casing -4TWR5 <br /> Unit casing is constructed of heavy gauge,G90 galvanized steel and painted with a weather-resistant powder painton all <br /> louvers, panels, prepaint on all other panels. Corrosion and weather-proof CMBP-G30 DuraTuff base. <br /> Refrigerant Controls-4TWR5 <br /> Refrigeration system controls include condenser fan and compressor contac-tor. High and low pressure controls are <br /> inherent to the compressor.A factory installed liquid line drier is standard. <br /> Compressor-4TWR5 <br /> The Climatuff compressor features internal over temperature and pressure protection and total dipped hermetic motor. <br /> Other features include: centrifugal oil pump and low vibration and noise. <br /> Condenser Coil -4TWR5 <br /> The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by <br /> louvered panels. <br /> Low Ambient Cooling -4TWR5 <br /> As manufactured,this unit has a cool-ing capability to 55 F. The addition of an evaporator defrost control with TXV <br /> permits low ambient cooling to 20 F. <br /> FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal ,Psige 3-eff e— <br /> Installed by Others <br />