WCPM Splits February 07,2017 <br /> and use permanently sealed ball bearings. Motors can operate at plus or minus 10 percent of rated voltage on all speed <br /> settings. <br /> 2" Pleated Throw-Away Merv8 Filter <br /> The units are equipped with 2"flat pleated media filters with a rated average dust spot efficiency of no less than 35 to 40 <br /> percent when tested in accordance with ASHRAE 52.1 atmospheric dust spot method and a Merv8 rating based on <br /> ASHRAE Standard 52.2. <br /> Angle Filter Box <br /> The angle filter box is constructed of heavy gauge galvanized steel with an angle filter frame for use with 2"filters.When <br /> used with vertical units, mounting legs are provided. <br /> Polymer Drain Pan <br /> The drain pan is noncorrosive and double-sloped to allow condensate drainage. The drainpan construction is polymer. <br /> Coils mount above the drain pan, not in the drain pan - thus allowing the drain pan to be fully inspected and cleaned. <br /> The drain pan can also be removed for cleaning. The drain pan connections are unthreaded 3/4"schedule 40 PVC for <br /> solvent bonding. The main drain connection is at the lowest point of the drain pan. An auxiliary drain connection is <br /> provided on the same side as the main connection. <br /> Customer Supplied Terminal Interface(CSTI) <br /> The customer supplied terminal interface(CSTI) is a pre-wired control offering of selected control components. This <br /> option intended to be used with a field-supplied, low-voltage thermostat or controller and field supplied temperature <br /> sensors. The control box contains a relay board which includes a line voltage to 24-volt transformer. Selected <br /> components are wired to a low-voltage terminal block and are run-tested, so the only a power connection and <br /> thermostat/controller connection are needed to commission the unit. <br /> Condensate Overflow Sensor <br /> This option provides an output that indicates when the drain pan is in danger of overflowing with condensate. This <br /> condition is indicated when the float switch rises to 50% of its travel and the normally closed output opens. The float <br /> switch is factory-wired to a terminal block for connection to a field supplied controller.When wired to the CSTI, the <br /> switch does not de-energize the unit when open position occurs.This is a dry contact only and sequence of operation of <br /> unit when this condition is reached is the responsibility of the field provided controller or thermostat. <br /> FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Pa re <br /> Installed by Others <br />