1. CEILING SYSTEMS SHALL COMPLY WITH ASTM C 635 &636. SEE ASCE 7-10 SECTION � <br /> 13.5.6 AND CISCA PROVIDE FURTHER DETAILED INSTRUCTIONS. � <br /> 2. PROVIDE 12 GA. (MIN) HANGER WIRES @ 4'-0"O.C. ALONG MAIN RUNNERS � <br /> 3. PROVIDE 12 GA. HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS <br /> WITHIN 8" FROM THE SUPPORT AT THE PERIMETER OF THE CEILING AREA. WIRES SHALL <br /> NOT HANG MORE THAN 1 IN 6 OUT OF PLUMB. 2X4 TEGULAR EDGE CEII.ING TILE � <br /> �� <br /> .� <br /> 4. WIRES SHALL NOT ATTACH TO OR BEND AROUND INTERFERING MATERIALS OR -- -- - - -- <br /> EQUIPMENT. PROVIDE TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT MEMBERS AT <br /> OBSTRUCTIONS TO MAIN HANGER SPACING. PROVIDE ADDITIONAL HANGERS, STRUTS OR j <br /> BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS OR DISCONTINUOUS AREAS. � - - - - - - - <br /> �-- _---- -__--� <br /> . 5. CEILING GRID MEMBERS MAY BE ATTACHED TO NOT MORE THAN TWO ADJACENT WALLS i ; <br /> WITH 2"MIN. CLOSURE ANGLES. CEILING GRID MEMBERS SHOULD BE AT LEAST 3/4" FREE i <br /> OF OTHER WALLS. ' <br /> E1 E1 T e <br /> 6. AT THE PERIMETER OF THE CEILING AREA,WHERE MAIN OR CROSS RUNNERS ARE NOT <br /> CONNECTED TO THE ADJACENT WALL, PROVIDE INTERCONNECTIONS BETWEEN THE Driftmier <br /> RUNNERS AT THE FREE END TO PREVENT IATERAL SPREADING.WHERE THE - 9'-0" - 9'-0" � _ � <br /> PERPENDICULAR DISTANCE FROM THE WALL TO THE FIRST PARALLEL RUNNER IS 12"OR , x 4 x 9'-0" 9 � 9'-0" <br /> LESS,THIS INTERLOCK IS NOT REQUIRED. 2' 4 ACT 2'x4' CT • <br /> 2'x 'ACT 2'x 'ACT Archite cts Ps <br /> 7. PROVIDE SETS OF FOUR 12 GA. SPLAYED BRACING WIRES ORIENTED 90 DEGREES FROM � <br /> EACH OTHER AT 12 FEET BY 12 FEET ON CENTER. PROVIDE BRACING WIRES AT LOCATIONS <br /> NOT MORE THAN 1/2 THE SPACING FROM EACH PERIMETER. THE SLOPE OF THESE WIRES 7983 Leary Way NE <br /> SHALL NOT EXCEED 45 DEGREES FROM THE PLANE OF THE CEILING AND SHOULD BE TAUT � � <br /> WITHOUT CAUSING THE CEILING TO LIFT. 9,_ , Redmond, WA 98052 <br /> 8. FASTEN HANGER WIRES WITH NOT LESS THAN 3 TIGHT TURNS. FASTEN BRACING WIRES 2'x 4' CT (425) 881�7SOC <br /> 4 TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 1 1/2". HANGER OR mail@driftmier.C011'1 <br /> BRACING WIRE ANCHORS TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER <br /> THAT THE DIRECTION OF THE WIRE ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION � <br /> OF THE FORCES ACTING ON THE WIRE. <br /> 9. FLUSH OR RECESSED CEILING LIGHT FIXTURES OR AIR TERMINALS OR SERVICES <br /> WEIGHING LESS THAN 56 POUNDS MAY BE SUPPORTED DIRECTLY ON THE RUNNERS OF A <br /> HEAVY DUTY GRID SYSTEM BUT, IN ADDITION,THEY MUST HAVE A MINIMUM OF TWO 12 GA. <br /> SLACK SAFETY WIRES ATTACHED TO THE FIXTURE AT DIAGONAL CORNERS AND ANCHORED <br /> TO THE STRUCTURE ABOVE. <br /> 1 1 1 1 1 1 1 1 1 <br /> 10. ALL FLUSH OR RECESSED CEILING LIGHT FIXTURES OR AIR TERMINALS OR SERVICES <br /> WEIGHING MORE THAN 56 POUNDS SHALL BE INDEPENDENTLY SUPPORTED BY NOT LESS <br /> THAN 4 TAUT 12 GA. WIRES EACH ATTACHED TO THE FIXTURE AND TO THE STRUCTURE <br /> ABOVE REGARDLESS OF THE TYPE OF CEILING GRID SYSTEM USED. THE WIRES AND THEIR M <br /> ATTACHMENTS MUST BE CAPABLE OF SUPPORTING 4 TIMES THE WEIGHT OF THE UNIT. <br /> � � � � <br /> � � � Z � <br /> CEILING NOTES NAq 17 <br /> W �' <br /> � a <br /> 1 1 1 1 1 1 1 1 1 � � � <br /> ,o. o.. _i W � <br /> - - - - rX2 ACT ,-' - - ' a � <br /> ANCHOR TO STRUCTURE ABOVE , � � > W <br /> � � � � � � <br /> � _ � O <br /> i � _ i � <br /> i � �� � � � � <br /> ATTACH COMPRESStON STRUT TO � � � � <br /> . � i � � � <br /> MAIN RUNNER WITH 2 SCREWS-#8 � � �� \` � � <br /> SELF TAPPING SCREWS � � � � � � <br /> , , , , W <br /> 1 1 �� i 1 1 1 � i 1 1 � ., <br /> � \ � ,i �1 � i � � � <br /> T-BAR OR GWB. CEILING SYSTEM � , i � � � � <br /> � i � �� �� � � <br /> � � _ � <br /> . <br /> � . � � � �� <br /> � � - - , � ; - � � � J � p <br /> � � � J <br /> , , Z a <br /> NOTES: \ / � O�/ <br /> . � � <br /> 1.ATTACH STRUT TO MAIN RUNNERS AND TO STRUCTURE. \ - ' � li. <br /> 2. COMPRESSION STRUT SHALL NOT REPLACE HANGER WIRE. � 1 1 L1 ` 1 1 1 1 1 � � � <br /> SCALE � O <br /> COMPRESSION STRUT N,A 18 �... � <br /> M <br /> 5/8"GWB. � <br /> CLOSURE ANGLE-PAINT <br /> 3� „ TO MATCH CEILING FINISH <br /> 9'OD FABRIC DECORATION 11'OD FABRIC DECORATION 9'OD FABRIC DECORATION 2X4 TEGULAR EDGE W! <br /> SECOND LOOK CEILING TILE <br /> 2" � a <br /> O � <br /> O <br /> � W �"629 R ST <br /> ACOUSTICAL <br /> CE�LING TILE Z � ` � � E <br /> _ w <br /> � � <br /> Q Q R' ards Dritimier <br /> H � <br /> OF WASHINGTON <br /> SCALE � <br /> SCALE � 9 PROPOSED RCP 14„= ,._o�. <br /> CEILING TO WALL DETAIL N,A <br /> REVISION SCHEDU�E <br /> COMPRESSION STRUTS NO. TYPE REVISION DATE <br /> 2x4 LAY-IN A.C.T. SEE DETAIL 4 HANGER WIRES L1 2x2 RECESSED FLORESCENT WITH PARABOLIC LENS 1. CEILING FINiSH AND MOUNTING HEIGHTS ARE DESIGNATED AS FOLLOWS: HEIGHT <br /> TYPICAL 7,0 (SEE CEILING NOTES) LIGHTING CALCULATIONS FINISH <br /> � 12 GA. BRACING WIRE W/ PROVIDED: 2. CEILING HEIGHTS ARE TO FACE OF FINISH FOR SUSPENDED SYSTEMS AND FACE OF <br /> MIN. 4 TIGHT TURNS IN 1 1/2" LIGHT FIXTURE L2 � 2x4 RECESSED FLORESCENT WITH DIFFUSERS STRUCTURAL FRAMING FOR DIRECT ATTACHED SYSTEMS. <br /> / BOTH ENDS OF WIRE (TYP.) TYPE QTY WATTS TOTAL WATTS <br /> , � / LI 34 60 2,040 3. LIGHT FIXTURES SHALL HAVE TIE WIRES PER CODE. <br /> � L2 17 84 1,428 L3 � 2x4 RECESSED FLORESCENT WITH PARABOLIC LENS 4. PROVIDE LIGHTS ON EMERGENCY CIRCUITS AS REQUIRED BY CODE OR LOCAL <br /> � � - L3 5 56 280 <br /> � _ / � TOTAL WATTS PROPOSED 3,748 AUTHORITY.VERIFY LOCATIONS WITH ARCHITECT. LIGHTS AT THE ENTRIES NEED TO BE <br /> _ � EXHAUST ON 24 HOURS. <br /> J _ _% -- � � - � � FAN 5. SUSPENDED GWB. &ACT CEILING: INSTALL PER NOTES&DETAILS 202 <br /> ' 45.0 M ALLOWED: <br /> � � f � � .- GYPSUM BOARD CEILING OR � SUPPLY A[R DIFFUSER <br /> - _ _ � � _ _ � ACOUSTICAL CEILING WHERE ROOM SF W/SF ALLOWED 6. PAINT ALL EXPOSED SOFFITS, GWB AND FASTENERS. NO NAILS OR FASTENERS WILL BE <br /> OCCURS LEFT EXPOSED TO VIEW. <br /> � _ BREAKROOM 192 .58 111 ISSUE DATE: 12/28/2017 <br /> / / � RETURN AIR GRILL <br /> _ _ � INVENTORY 201 .50 101 7. PROVIDE EXIT& EMERGENCY FIXTURES&NIGHT LIGHTS AS REQUIRED BY CODE/A.H.J. <br /> PANEL 57 .76 43 DRAWN BY: SA <br /> � / - 2X4 GRID SPACING HALLWAY 132 .53 70 <br /> _ ,- � HANGER WIRES ATTACHED TO TRAINING 371 1.00 371 � EXIT SIGN, CEILING MOUNTED WAL PACKS PIER CO EAY LIGHTING: USE LIGHT FIXTURES ON BATTERY BACK UP OR PROJECT MANAGER: MCW <br /> MAIN RUNNER FIXTURE&ANCHORED TO TOILET ROOM 130 .7$ 101 PROJECT NUMBER: 21734 <br /> � LIGHT FIXTURE STRUCTURE SALES FLOOR 2 717 1.27 3 451 0� STROBE ALARM <br /> NOTES: TOTAL 4,248 9. EXTEND ALL GWB AND NECESSARY BLOCKING FOR CEILINGS ABOVE EXISTING <br /> CROSS RUNNER � CEILINGS. SHEET NAME: <br /> 1. CEILING SYSTEM BRACING REQUIRES SPECIAL SPEAKER 10. PROVIDE SMOKE DETECTORS AS REQUIRED PER CODE/A.H.J. <br /> INSPECTION PER IBC 1705.3 AND 1707. 2 MAX. FROM REFLECTED <br /> BRACE WIRES TO �Q SECURITY CAMERA 11. GC 70 PROVIDE SWITCHING AND OCCUPANCY CONTROLS FOR ALL NEW LIGHTING �, <br /> 2. FOR LIGHTING TIES SEE DETAIL 6� CROSS RUNNER `/ CIRCUITS PER 2015 WSEC SECTION C405. CEILING PLAN <br /> 5 � <br /> 3. FOR CEILING NOTES SEE �� <br /> GYPSUM BOARD CEILING OR ACOUSTICAL SHEET NUMBER: <br /> 4. FOR PERIMETER MOLDING SEE DETAIL �� CEILING, WHERE OCCURS <br /> PENDED A.C.T. CEILING SCALE 20 LIGHT FIXTURE TIE DETAIL SCALE � 6 LIGHTING CALCULATI4NS SNAqE 12 CEILING PLAN LEGEND SNAqE 8 RCP NOTES SNAqE 4 �►2•2 <br /> S U S N/q N/A <br />