OM NOT SCALE DRAWINGS.CONTRACTOR MUST TERYAL
<br /> L
<br /> DIMENSIONS AND ADVISE CONSULTANTS OF ANY ERRORS
<br /> O
<br /> RGENERAL ELECTRICAL NOTES LEGEND OMISSIONS.NO VARIATIONS
<br /> ORMODIFICATIONS TO WORK
<br /> SHOWN SHALL BE IMPLEMENTED WITHOUT PRI WRITTEN
<br /> APPROVAL ALL PREVIOUS ISSUES OF THIS DRAWING ARE
<br /> SYMBOL I DESCRIPTION SUPERSEDED THE LATEST REVERT.ALL DRAWINGS AND
<br /> GENERAL GROUNDING SPECIFlCATIONS REMAIN THE PROPERTY OF MORRISON
<br /> n HERSHFIELD CORPORATION.NEITHER MORRISON HERSHFIELD
<br /> CIRCUIT BREAKER NOR THE ARCHITECT WILL BE PROVIDING CONSTRUCTION
<br /> 1. EXAMINE THE SITE CONDITIONS VERY CAREFULLY AND THE SCOPE OF PROPOSED WORK TOGETHER WITH THE 1. ALL LIGHTNING PROTECTION AND SAFETY GROUNDING OF THE ELECTRICAL EQUIPMENT SHALL BE CARRIED OUT REVIEW OF THIS PROJECT.
<br /> WORK OF ALL OTHER TRADES AND INCLUDE IN THE BID PRICE ALL COSTS FOR WORK SUCH AS EQUIPMENT IN ACCORDANCE WITH THE CURRENT NFPA AND VERIZON WIRELESS STANDARDS. ❑.I NON-FUSIBLE DISCONNECT SWITCH
<br /> AND WIRING MADE NECESSARY TO ACCOMMODATE THE ELECTRICAL SYSTEMS SHOWN AND SYSTEMS OF OTHER a FUSIBLE DISCONNECT SWITCH
<br /> TRADES. 2. GROUND LUGS ARE SPECIFIED UNDER SECTION 3 "CONDUCTORS AND CONNECTORS".
<br /> 8259
<br /> SURFACE MOUNTED PANEL BOARD
<br /> 2. SUBMITTAL OF BID INDICATES CONTRACTOR IS COGNIZANT OF ALL JOB SITE CONDITIONS AND WORK TO BE 3. ALL GROUND LUG AND COMPRESSION CONNECTIONS SHALL BE COATED WITH ANTI-OXIDANT AGENT, SUCH AS REGISTERED
<br /> PERFORMED UNDER THIS CONTRACT. NO-OX, NOALOX, PENETROX OR KOPRSHIELD. TR TRANSFORMER •-CHITECT
<br /> 3. PERFORM DETAILED VERIFICATION OF WORK PRIOR TO ORDERING THE ELECTRICAL EQUIPMENT AND 4. GROUND ALL EXPOSED METALLIC OBJECTS ON BUILDING EXTERIOR INCLUDING BUILDING TIE DOWN BRACKETS. ❑© KILOWATT HOUR METER
<br /> COMMENCING CONSTRUCTION. ISSUE A WRITTEN NOTICE TO THE CONSULTANT OF ANY DISCREPANCIES. DENOTES CABLE OR CONDUIT
<br /> 5. PROVIDE LOCK WASHERS FOR ALL MECHANICAL CONNECTIONS FOR GROUND CONDUCTORS. USE STAINLESS -0 TURNING UP IN PLAN VIEW
<br /> 4.. OBTAIN ALL PERMITS, PAY ASSOCIATED FEES AND SCHEDULE INSPECTION. _ STEEL HARDWARE THROUGHOUT. r RE'< .E''R. ' '
<br /> C DENOTES CABLE OR CONDUIT �T
<br /> 5. PROVIDE ALL LABOR, MATERIAL, EQUIPMENT, INSURANCE, AND SERVICES TO COMPLETE THIS PROJECT IN 6. DO NOT INSTALL GROUND RING OUTSIDE OF PROPERTY LINE. TURNING DOWN IN PLAN VIEW �,'`+ ;-:•,'.( ' r t'19 8N
<br /> ACCORDANCE WITH THE CONTRACT DOCUMENTS AND PRESENT IT AS FULLY OPERATIONAL TO THE
<br /> SATISFACTION OF THE OWNER. 7. REMOVE ALL PAINT AND CLEAN ALL DIRT FROM SURFACES REQUIRING GROUND CONNECTIONS, REPAINT TO JB JUNCTION BOX .1:54 7- a
<br /> MATCH AFTER CONNECTION IS MADE TO MAINTAIN CORROSION RESISTANCE.
<br /> 6. CARRY OUT WORK IN ACCORDANCE WITH ALL GOVERNING STATE, COUNTY AND LOCAL CODES AND O.S.H.A. PB PULL BOX TO NEC/TELCO STANDARDS
<br /> 7. PRIOR TO BEGINNING WORK COORDINATE ALL POWER AND TELCO WORK WITH THE LOCAL UTILITY COMPANY 8. ALL EXTERIOR GROUNDING CONDUCTORS INCLUDING EXTERIOR GROUND RING SHALL BE #2 AWG SOLID BARE
<br /> TINNED COPPER UNLESS NOTED OTHERWISE. MAKE ALL GROUND CONNECTIONS AS SHORT AND DIRECT AS OH OVERHEAD UTILITIES
<br /> AS IT MAY APPLY TO THIS SITE. ALL WORK TO COMPLY WITH THE RULES AND REGULATIONS OF THE POSSIBLE, AVOID SHARP BENDS. THE RADIUS OF ANY BEND SHALL NOT BE LESS THAN 8"AND THE ANGLE ROBERT JERRY LARA
<br /> UTILITIES INVOLVED. OF ANY BEND SHALL NOT EXCEED 90'. GROUNDING CONDUCTORS SHALL BE ROUTED DOWNWARD TOWARD.THE UGT UNDERGROUND TELCO
<br /> BURIED GROUND RING. LICENSED ARCHITECT
<br /> 8. FABRICATION AND INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEM SHALL BE DONE IN A FIRST CLASS - UGP UNDERGROUND POWER STATE OF WASHINGTON
<br /> WORKMANSHIP PER NECA STANDARD 1-2000 BY QUALIFIED PERSONNEL EXPERIENCED IN SUCH WORK AND 9. BOND ALL EXTERIOR CONDUITS, PIPES AND CYLINDRICAL METALLIC OBJECTS WITH A PENN-UNION GT SERIES 8259
<br /> SHALL SCHEDULE THE WORK IN AN ORDERLY MANNER SO AS NOT TO IMPEDE PROGRESS OF THE PROJECT. CLAMP, BLACKBURN GUV SERIES CLAMP OR A BURNDY GAR 3900BU SERIES CLAMP ONLY, NO SUBSTITUTES -UCP/UGT- UNDERGROUND POWER/TELCO
<br /> 9. DURING PROGRESS OF THE WORK, MAINTAIN AN ACCURATE RECORD OF THE INSTALLATION OF THE ACCEPTED.
<br /> ELECTRICAL SYSTEMS, LOCATING EACH CIRCUIT PRECISELY AND DIMENSIONING EQUIPMENT, CONDUIT AND T TELCO CONSTRUCTION
<br /> 10
<br /> CABLE LOCATIONS. UPON COMPLETION OF THE INSTALLATION, TRANSFER ALL RECORD DATA TO BLACK LINE . ALL GROUND CONNECTIONS SHALL BE APPROVED FOR THE METALS BEING CONNECTED.
<br /> PRINTS OF THE ORIGINAL DRAWINGS AND SUBMIT THESE DRAWINGS AS RECORD DRAWINGS TO THE P POWER
<br /> CONSULTANT. 11. ALL EXTERNAL GROUND CONNECTIONS SHALL BE EXOTHERMICALLY WELDED. ALL EXOTHERMIC WELDS TO
<br /> EXTERIOR GROUND RING SHALL BE THE PARALLEL TYPE, EXCEPT FOR THE GROUND RODS WHICH ARE TEE (2 y-` DENOTES REFERENCE NOTE
<br /> EXOTHERMIC WELDS. REPAIR ALL GALVANIZED SURFACES THAT HAVE BEEN DAMAGED BY EXOTHERMIC WELDING. `-�
<br /> 10. COMPLETE JOB SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR AFTER THE DATE OF JOB USE SPRAY GALVANIZER SUCH AS HOLUB LECTROSOL #15-501. • EXOTHERMIC WELD CONNECTION
<br /> ACCEPTANCE BY OWNER. ANY WORK, MATERIAL, OR EQUIPMENT FOUND TO BE FAULTY DURING THAT PERIOD
<br /> SHALL BE CORRECTED AT ONCE UPON WRITTEN NOTIFICATION, AT THE EXPENSE OF THE CONTRACTOR. 12. CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER WHEN THE BURIED GROUND RING IS INSTALLED SO ■ MECHANICAL CONNECTION (eg LUG, C-TAP)
<br /> 11. GENERAL CONTRACTOR IS RESPONSIBLE FOR REQUESTING CONNECTION OF COMMERCIAL POWER FROM THE THE REPRESENTATIVE CAN INSPECT THE GROUND RING BEFORE IT IS BACKFILLED WITH SOIL. 0 09/14/17 ISSUED FOR PERMIT
<br /> POWER COMPANY. ELECTRICAL CONTRACTOR SHALL COORDINATE THIS WORK WITH THE GENERAL CONTRACTOR. 'II GROUND ROD
<br /> 13. FOR METAL FENCE POST GROUNDING, USE A HEAVY DUTY TYPE GROUNDING CLAMP OR EXOTHERMIC WELD B 08/09/17 ISSUED FOR REVIEW
<br /> 12. COORDINATE EXACT TELEPHONE REQUIREMENTS AND SERVICE ROUTING WITH LOCAL TELEPHONE COMPANY. CONNECTION TO POST. GROUND ALL FENCE POSTS WITHIN 6' OF EQUIPMENT. 4F-EDGROUND ROD WITH INSPECTION SLEEVES
<br /> ',. APPLY FOR TELEPHONE SERVICE IMMEDIATELY UPON AWARD OF CONTRACT. 14. WHERE MECHANICAL CONNECTORS (TWO-HOLE OR CLAMP) ARE USED, APPLY A LIBERAL PROTECTIVE COATING -E-1- GROUND BAR A 07/27/17 ISSUED FOR REVIEW
<br /> OF AN ANTI-OXIDE COMPOUND SUCH AS "NO OXIDE A" BY DEARBORN CHEMICAL COMPANY ON ALL
<br /> CONNECTORS. -g PIN AND SLEEVE RECEPTACLE No. Date Revision
<br /> BASIC MATERIALS AND METHODS
<br /> ---- GROUND CONDUCTOR Client:
<br /> 1. ALL ELECTRICAL WORK SHALL CONFORM TO THE EDITION OF THE NEC ACCEPTED BY THE LOCAL
<br /> JURISDICTION AND TO THE APPLICABLE LOCAL CODES AND REGULATIONS. OVERCURRENT & SHORT-CIRCUIT/GND FAULT PROTECTION (IF APPLICABLE)
<br /> 2. ALL MATERIALS AND EQUIPMENT SHALL BE NEW. MATERIALS AND EQUIPMENT SHALL BE THE STANDARD 1. CONTRACTOR SHALL RECORD LOAD READINGS WHEN SITE POWER ORIGINATES FROM A 30 SERVICE TO
<br /> PRODUCTS OF MANUFACTURER'S CURRENT DESIGN. ANY FIRST-CLASS PRODUCT MADE BY A REPUTABLE MONITOR & ASSURE A BALANCED LOAD AT THE PRIMARY SUPPLY. RECORDS SHALL BE PROVIDED TO THE ver izon
<br /> MANUFACTURER MAY BE USED PROVIDING IT CONFORMS TO THE CONTRACT REQUIREMENTS AND MEETS THE SITE/FACILITY OWNER. CONTRACTOR SHALL CONSULT MANUFACTURER'S PLANS, SHOP DRAWINGS AND SPECS
<br /> APPROVAL OF THE CONSULTANT AND THE OWNER. FOR INDOOR/OUTDOOR EQUIPMENT LOCATION & INSTALLATION. ELECTRIC SERVICE SHALL BE IN COMPLIANCE
<br /> WITH ALL RULES & REGULATIONS OF THE UTILITY CO. ELECT. CONTRACTOR SHALL PROVIDE EQUIPMENT WITH
<br /> 3. ARRANGE CONDUIT, WIRING, EQUIPMENT, AND OTHER WORK GENERALLY AS SHOWN, PROVIDING PROPER HIGHER SHORT-CIRCUIT FAULT CURRENT RATINGS (kA.I.C.) AS REQUIRED TO MATCH & EXCEED UTILITY CO. ABBREVIATIONS
<br /> CLEARANCES AND ACCESS. CAREFULLY EXAMINE ALL CONTRACT DRAWINGS AND FIT THE WORK IN EACH AVAILABLE SYMMETRICAL & ASYMMETRICAL FAULT CURRENT LEVELS. FUSES IN SERVICE SWITCHES SHALL BE
<br /> LOCATION WITHOUT SUBSTANTIAL ALTERATION. WHERE DEPARTURES ARE PROPOSED BECAUSE OF FIELD CLASS "RK1", CURRENT LIMITING TYPE, 200 kA.I.C., NON-TIME DELAY, DISCONNECT SWITCHES TO HAVE Implementation Team:
<br /> CONDITIONS OR OTHER CAUSES, PREPARE AND SUBMIT DETAILED DRAWINGS FOR ACCEPTANCE. REJECTION CLIPS, UNLESS INDICATED OTHERWISE. ELECTRICAL EQUIPMENTS & PROTECTIONS SHALL BE AFG ABOVE FINISHED GRADE
<br /> 4. THE CONTRACT DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ALL OFFSETS, BENDS, FITTINGS AND STANDARD kAIC RATED HIGHER THAN INCOMING EQUIPMENT.AND/OR UTILITY CO. kAIC RATE AND CONSIDERING
<br /> THEE CONTRA ARE NOT SEARESGEY ALLY DI PROVIDE ALA D AL ITEMS TS MAY BE FEQUIGSD ND FIT THE ELECTRIC MOTORS FAULT CONTRIBUTION. CONTRACTOR SHALL NOT BEGIN CONSTRUCTION UNTIL THIS AIC AMPERE INTERRUPTING CAPACITY '1 CROWN
<br /> MANDATORY REQUIREMENT IS MET. IF NEW LOAD IS ADDED CONTRACTOR SHALL VERIFY & CONFIRM BEFORE
<br /> WORK TO THE CONDITIONS. CONSTRUCTION THAT TOTAL UTILITY SERVICE LOAD SHALL KEEP EQUAL TO (125% MAX. DEMAND+ NEW LOAD)< BFG BELOW FINISHED GRADE CASTLE
<br /> 5. MAINTAIN ALL CLEARANCES AS REQUIRED BY NEC. 80% SERVICE ENTRANCE CONDUCTORS/MAIN OVER CURRENT PROTECTION AMPACITY, WHICHEVER RATING IS C CONDUIT %,....•
<br /> { LOWER. LIGHTING SHALL MEET NEC, IESNA AND/OR FM STANDARDS IF APPLICABLE. PHOTOMETRIC LEVELS
<br /> 6. SEAL AROUND CONDUITS AND AROUND CONDUCTORS WITHIN CONDUITS ENTERING THE PREFABRICATED SHALL COMPLY WITH LOCAL, STATE& FEDERAL RULES. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN CRGB CELL REFERENCE GROUND BAR 1505 WESTLAKE AVE N,SUITE 800
<br /> k ACCESSIBLE AREAS ONLY. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF SEATTLE,wAse1D9
<br /> SHELTER/CABINETS WHERE PENETRATION OCCURS WITH A SILICONE SEALANT TO PREVENT MOISTURE POWER AND TELE- PHONE UTILITY COMPANIES. CU COPPER
<br /> PENETRATION INTO BUILDING/SHELTER. C/W COMPLETE WITH A&E Team:
<br /> 7. SILICONE SEAL AROUND ALL BOLTS AND SCREWS USED TO SECURE EQUIPMENT TO EXTERIOR OF BUILDING. D.T.T. DRY TYPE TRANSFORMER1 R
<br /> 8. MAKE NECESSARY CONNECTIONS FOR BATTERY IN EMERGENCY LIGHT FIXTURE. CONNECT EXTERIOR LIGHT
<br /> FIXTURE (PROVIDED BY SHELTER MANUFACTURER) TO EXTERNAL JUNCTION BOX. EC EMPTY CONDUIT
<br /> O GROUND MORRISON HERSHFIELD
<br /> CONDUCTORS AND CONNECTORS GE GROUNDING ELECTRODE 600 STEWART ST,SUITE 200
<br /> SEATTLE,WA 98101
<br /> 1. UNLESS NOTED OTHERWISE, ALL CONDUCTORS SHALL BE COPPER, MINIMUM SIZE #12 AWG, WITH GEC GROUNDING ELECTRODE CONDUCTOR Tel:206
<br /> INSULATION CONFORMING TO NEMA WC5 OR CROSS-LINKED POLYTHYLENE INSULATION GRC GALVANIZED RIGID CONDUIT Iw✓•w.mortisonhershfield.com
<br /> CONFORMING TO NEMA WC7. (TYPES THHN OR THWN-2). INSULATION SHALL BE RATED FOR 90'C MTS MANUAL TRANSFER SWITCH Project Info:
<br /> CONDUCTORS SHALL BE COLOR CODED IN ACCORDANCE WITH NEC. 1
<br /> NEC NATIONAL ELECTRICAL CODE B 824022
<br /> 2. ALL CONDUCTORS USED FOR GROUNDING SHALL BE COPPER AND SHALL HAVE GREEN INSULATION EXCEPT v U#(J Y G
<br /> WHERE NOTED. 0/H OVERHEAD
<br /> FEELY
<br /> RNC RIGID NON-METALLIC CONDUIT (SCHEDULE 80 PVC)
<br /> 3. FOR COPPER CONDUCTORS #6 AWG AND SMALLER USE 3M SCOTCH-LOK OR T&B STA-KON COMPRESSION 8215 BROADWAY AVE
<br /> TYPE CONNECTORS WITH INTEGRAL OR SEPARATE INSULATION CAPS. FOR COPPER CONDUCTORS LARGER THAN SD SERVICE DISCONNECT SWITCH EVEREIT,WA 98203
<br /> #6 AWG USE SOLDERLESS, (DENT HEX SCREW OR BOLT TYPE PRESSURE CONNECTORS OR DOUBLE
<br /> COMPRESSION C-CLAMP CONNECTORS, UNLESS SPECIFIED OTHERWISE ON DRAWINGS. SE SERVICE ENTRANCE Drawing Title:
<br /> 4. UNLESS NOTED OTHERWISE ALL LUGS SHALL BE TIN PLATED COPPER, TWO-HOLE, LONG BARREL, SN SOLID NEUTRAL
<br /> COMPRESSION TYPE.
<br /> TGB TELCO GROUND BAR
<br /> 5. CONDUCTOR LENGTHS SHALL BE CONTINUOUS FROM TERMINATION TO TERMINATION WITHOUT SPLICES. TEGB TOWER EXIT GROUND BAR ELECTRICAL NOTES
<br /> SPLICES ARE NOT ACCEPTABLE. IF SPLICES ARE UNAVOIDABLE PRIOR APPROVAL FROM THE ENGINEER MUST
<br /> BE OBTAINED. TR TRANSFORMER
<br /> TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR AN D SYM B 0 LS
<br /> RACEWAYS AND BOXES TYP TYPICAL
<br /> WP WEATHERPROOF - NEMA 3R Project Number: Start Date:
<br /> 1. ALL CONDUIT SHALL BE UL LABELED.
<br /> U/G UNDERGROUND 7170282 07/27/17
<br /> 2. ALL EMPTY CONDUITS INSTALLED FOR FUTURE USE SHALL HAVE A PULL CORD. PPC POWER PROTECTION SHELTER Drafter: Designer.
<br /> 3. SHEET METAL BOXES SHALL CONFORM TO NEMA OSI; CAST-METAL BOXES SHALL CONFORM TO NEMA 81 AND JS LB
<br /> SHALL BE SIZED IN ACCORDANCE WITH NEC UNLESS NOTED OTHERWISE. Project Manager: Professional of Record:
<br /> RKL RL
<br /> Revision No: Sheet No:
<br /> 0 E- 1
<br /> ►s1 /i1'