Laserfiche WebLink
t <br /> S ' <br /> • <br /> . Lateral Force Bracing(figures 2 and 3) <br /> o ;e Bracing a Ceilings constructed of lath and plaster or gypsum board,screw or nail at- <br /> tached to suspended members that support a ceiling on one level extending <br /> • from wall to wall shall be exempt from the lateral force bracing requirements. <br /> has \ia5^or less Source CISCA zones 3-4 <br /> a Lateral force bracing is the use of vertical struts(compression posts)and M <br /> V . <br /> splay wires(see figure 2). "' <br /> 7 2 gage <br /> \_� �� splayed • u <br /> ��. fir '. brace Lateral force bracing is required for ceilings ove 1,000 s.uare feet�nd not <br /> 45^or less )45^°rlas• wires required for ceilings less than 1,000 square feet proVr•e. ey are surroundec <br /> by four walls and braced to structure"Source ASCE 7-02 section 9.6.2.6.2.2 item c <br /> a Lateral Force Bracing shall be 12 feet on center(maximum)and begin no <br /> Cross tee ' Main beam farther than 6 feet from walls.Source CISCA Seismic zohes 3-4 <br /> -• a Splay wires are to be four 12 gage wires attached to the main beam.Wires <br /> are arrayed 90°from each other and at an angle not exceeding 45°from the <br /> • <br /> plane of the ceiling.Source CISCA Seismic zones 3-4 <br /> • Splay wires-are to be within 2 inches of the connection of the vertical strut to <br /> suspended ceiling.Source CISCA Seismic zones 3-4 <br /> Rigid bracing may be used in lieu of splay wires.source ASCE section 9.6.2.6.2.2 <br /> figure 3 <br /> Maximum Recommended Lengths for a Ceilings with plenums less than 12 inches to structure are not require to��, <br /> Vertical Struts • have lateral force bracing.source Portland Building Department <br /> Vertical struts must be positively attached to the suspension systems and t <br /> EMT CONDUIT structure above.Source CISCA 3-4 <br /> uto6'0" <br /> a The vertical strut may be EMT conduit,metal studs or a proprietary Comptes <br /> /z" EMT conduit psion post(see figure 3). <br /> 3/4"EMT conduit . up to 8'6" _ -- __ <br /> 4 t=MT conduit up to 10 0 Wail Moidinas(figure 4) ®. <br /> •! •2 F ¢ - ' <br /> r.'� l �- ihr �J _ _ -• ^ 1.(�./NII.'L'lnif i:";`'�(perimeter(`I�1C141Yp;�L"{�Ir;CI'�•1:?YP.fYI IIY.EPf:'I 1'.!1�'L'.iVP�)„hnri7nnin <br /> : flange 2 inches wide,unless•alternate <br /> methods are approved prior to instal- . <br /> 15/e"metal stud(25 gage) up to 6'2" latioh by the local building department and the designer of record. One end <br /> tol0'6" <br /> of the ceiling grid shall be attached to the wall molding,the other end shall <br /> 2'/z'metal stud(25 gage) up • have a 3/4 inch clearance from the wall and free to slide.Source ASCE 702 section <br /> Source Portland Building Department 9.6.2.6.2.2 item b rivets or approved <br /> • • The grid shall be attached at two adjacent walls(pop <br /> Note:Plenum areas greater than 11'0"will require <br /> method).Source CISCA Seismic zones 3-4 <br /> engineering calculations. a , There shall be a minimum 3/4 inch clearance from the end of the grid system <br /> at un-attached walls.Source ASCE 702 section 9.6.2.6.2.2 item b <br /> • <br /> • <br /> • <br /> Spreader Bars (figure 4) <br /> ° • <br /> Spreader(spacer)bars or other means approved by.local building depart- <br /> • <br /> , ment shall be used to prevent the ends of the main beams at perimeter walls <br /> fig <br /> Wall Moll• <br /> ding • <br /> Requirements are 4 � � from spreading open during a seismic event.Perimeter wires shall not be-in <br /> Wlieu of spreader bars.Source CISCA Seismic zones 3-4 r�) 4-r, "Nu. <br /> • <br /> a Wire tying is an acceptable alternative to spreader bars. /fs <br /> maximum e' 202 mm7 a Spreader bars are not required if a 90 degree intersecting cross or main is <br /> WALL /// within 8 inches of the perimeter wall. <br /> • <br /> I I Spreader bar or — <br /> • <br /> `° other suitable 5a and 5b) <br /> D sYstemrequiredto anger (Suspension) Wires (figures <br /> • <br /> S �� �i keep Penmiter ' <br /> ///\ components from <br /> ,,� spreading apart <br /> / / unattached h mm) ... <br /> . a Hanger and perimeter wires must lie,plumb within 1 in 6 unless(figure 5a) <br /> X. at unattached Walls <br /> minimum ~4 <br /> 2"(50 mm) O`°� counter sloping wires are provided(figure 5b),Source ASTM c 636 section 21.4 <br /> ` <br /> _ ...cisHanger.wires shall be 12 gage and spaced 4 feet on center or 10 gage ( <br /> spaced 5 feet on center:source ASTM C 636 <br /> • Any connection device at the supporting construction shall be capable of ca <br /> rying not less than 100 pounds.source CISCA zones 3-4 f <br />