Laserfiche WebLink
• <br /> INSTALLED BY <br /> UL 300 COMPLIANT R & T HOOD SERVICES INC_ <br /> SYSTEM MFG.RG,/KIDDE 6100 12TH S. SEATTLE WA. 98108 <br /> CAPABLE FLOW 18 ACTUAL FLOW 9 PHONE(206) 726-0940 FAX (206) 767-2607 <br /> MECHANICAL 24"x 12"DUCT <br /> r:1 <br /> 1/2"PIPE AUTOMATIC <br /> A...........:GAS SHUTOFF 0 —y---450*FUSIBLE LINKS <br /> .,�r14 ADP <br /> ADP — 711- 12" HOOD <br /> O. X <br /> 6 GALLON FIRE <br /> SUPPRESSION R R GRW R PHO HUNG <br /> SYSTEM 120"-42" I 351r 56" 20"142" 9605 EVERGREEN WAY STE E <br /> MANUAL PULL i EVERETT,WA 98204 <br /> BY EXIT 48" y_� Z+� 47�# R R <br /> aP <br /> ABOVE FLOOR ~X111._ 4_+ "M. +Z# T T <br /> 20"142" 20142" <br /> 36"X 24" 24"X 24" / 'r` <br /> GAS GAS WOK GAS 18"X 18" 18"X 18" <br /> RANGERANGE GAS STOCK GAS STOCK <br /> IIII <br /> POT RANGE POT RANGE <br /> NOTE: ■ All pipe is black schedule 40 ■ K-CLASS Back up portable fire • Plenum nozzle must be located .x Fire system must inter-tied <br /> isSystem operating and maintenance extinguisher(54"Max above floor level) within 6"of end of plenum to the main building alarm board <br /> instruction posted by manual pull located along path of egress and deviding the length into if present. <br /> within 30'travel distance sections equal to or less than 10' ""Upon acuation all electrics under <br /> • Cylinder has mechanical control head the hood and make-up air must shut <br /> down. <br /> 7 <br />