Laserfiche WebLink
�pril 7, 1976 <br />Samuel G. lforrison, A.I.A. & Associates <br />P.O. Box 599 <br />biercer Island, Washington 98040 <br />Ref�rence: Soci3�-Security Office Building <br />-'IC D.Ei. Inves�ors <br />2940 �iorton <br />V-N Construction <br />� Fire Zone 2 <br />\ <br />�__ Occupant Load 115 . <br />Plan Check No. 76-157 <br />Gentlemen: <br />�, . <br />crcv oF <br />everett <br />QTY NALL � 250•e)�0 <br />[V[NRT. WA6HINGTON <br />• aexm <br />INi�CCTION pLPAPTMEIIT <br />The Plans for the above referenced project have been reviewed <br />ar.d the following corrections are required to comoly with the <br />Uniform Building Code, Uniform Plwnbing Code, and Uniform <br />Mechanical Code. <br />1. All construction is subject to field inspections and <br />correct:ons. <br />2. There shall be no occuoancy of the building prior to <br />final inspection and a certificate of occupancy being <br />issued by the Building Official. <br />3. No concrete or grout shall be placed without inspection <br />and approval. <br />4. Final partition layouts and details shall be submitted <br />piior to installation to justify compliance with <br />occupancy, fire resistive and er.it requirements. <br />5. Heating and air conditi.oning plans do aot indicate how <br />ventilation in accordance with Section 1105 is provided. <br />6. Stairways shall comply with Sections 3305 an3 1714. <br />7. Roof overflow scuppers shall be of. a sufficient size to <br />eaual three times that of the 6" roof drain. Section 3207(c). <br />8. Soecial inspecti�n by an approved inspection agency is <br />required for pre-fabricated brick wall Sections. <br />Section 304(c). <br />." _ ".'_ _ -..._ .. . ,_ ._'_� -_.. .� —.- _-. . ..-�.._-- . `I "r <br />