ELEVATOR NOTES
<br /> 1. ASME SECTIONS 101 & 102. PIPES, DUCTS, CONDUITS, AND EQUIPMENT NOT USED FOR THE OPERATION
<br /> OF THE ELEVATORS ARE PROHIBITED IN MACHINE ROOM AND HOISTWAYS.
<br /> ���-a�� 2. SBC 3020.4. MAINTAIN ALL REQUIRED WORKING CLEARANCES IN MACHINE ROOM.
<br /> 8,_4„
<br /> ! 3. ASME RULE 100.2c. WATERPROOF AS NECESSARY TO PREVENT ENTRY OF GROUND WATER. SUMP PUMPS
<br /> 3 MAY BE INSTALLED FOR FLOOD CONTROL BUT NOT APPROVED TO MAINTAIN DRY PIT.
<br /> A6.0 4. ASME RULE A17.1 / SECTION 2.2.4, AS AMENDED UNDER SBC 3023. PROVIDE PIT ACCESS. � ����
<br /> � �
<br /> 5. ASME RULE 101.5b. PROVIDE MACHINE ROOM VENTILATION. �� �
<br /> � .,; ; =-�- - -- -.i 6. SBC 3016.5. PROVIDE HOISTWAY VENTILATION FOR ELEVATOR #3. � �
<br /> -- � � . ; :,�� � , .: . �. ..��- � .: _
<br /> c
<br /> i �
<br /> �, ; --�� � 7. SBC 3016.3. COMPLY WITH SEISMIC REQUIREMENTS. .�'�,� . ��`�
<br /> ----- ,, f ��'r� ,5,� �
<br /> , _ , �`�`r:���rt'�'L`l��»�
<br /> ��.,��, - � 8. ASME RULE 101.4, PROVIDE MINIMUM 7'-0" CLEAR HEADROOM IN MACHINE ROOM.
<br /> �
<br /> ; �
<br /> � � 9. WAC 296-96-02300 THRU 02365, AND ICC/ANSI A117.1-SECTION 407. ACCOMMODATE PEOPLE WITH �
<br /> � � DISABILITIES_
<br /> � �N �
<br /> � ELEVATOR ELEVATOR _
<br /> � � 04 u 05 , ; 10. ASME SECTION 300. PROVIDE PROPER TOP CAR RUN-BYS, CLEARANCES AND REFUGE SPACE.
<br /> � ;
<br /> � �' I 11. ASME RULES 100.1 b & 110.14. GROUT ALL MASONRY JAMBS AND HEADERS TO RETAIN FIRE RATING OF
<br /> , �
<br /> HOISTWAY. IN OTHER THAN MASONRY, PROVIDE LABELED ENTRANCE ASSEMBLIES INSTALLED AS TESTED.
<br /> 12. SBC 3020. GROUT BEHIND ALL HOISTWAY PENETRATIONS FOR PIPES, FIXTURES, ETC.
<br /> O :;�
<br /> 13. SBC 3016.5. ELEVATOR HOISTWAY SHALL NOT BE VENTED OR PRESSURIZED THROUGH MACHINE ROOM.
<br /> ,,
<br /> ,';
<br /> r% 14. SBC 3022.2 VENTILATION AND PRESSURIZATION EQUIPMENT, DUCTS, ETC. CANNOT BE LOCATED IN
<br /> 3 ELEVATOR MACHINE ROOMS, HOISTWAYS, OR SPACES. �
<br /> As.o ; •��
<br /> ., 15. ASME 100.1c, 204.1h. GLASS USED IN OR ON ELEVATOR HOISTWAYS AND CARS MUST BE LAMINATED AND �
<br /> � �"�:' -�% ;� ''- M�ET REQUIREMENTS OF ASME Z97.1.
<br /> 16. SBC 106.5.2. PROVIDE CALCULATIONS AND DRAWINGS TO DCLU FOR APPROVAL OF THE STRESSES AND �
<br /> COMMERCIAL ELEVATORS - PARKING LEVEL 1 SHALL BE NOTED IN THEAPPLICABLE RULES OF ASME 105. .�e
<br /> ��4"_ �a'-a' 17. ASME SECTION 109. PROVIDE CALCULATIONS TO DCLU FOR APPROVAL OF THE ABILITY OF THE PIT FLOOR �
<br /> AND STRUCTURE TO WITHSTAND THE ELEVATOR BUFFER ENGAGEMENT REACTIONS. U
<br /> L
<br /> 18. ASME 211.1(a)(2}. PROVIDE MEANS OF TWO-WAY CONVERSATION BETWEEN EACH ELEVATOR AND A
<br /> READILY ACCESSIBLE POINT (BUILDING ENTRANCE LOBBY) OUTSIDE HOISTWAY.
<br /> 1 T�"
<br /> a'-4" 19. ASME 211.1(b). THIS STRUCTURE IS CONSIDERED AS UNATTENDED AND ONE OF TWO ADDITIONAL �
<br /> EMERGENCY SIGNALING DEVICES SHALL BE PROVIDED (PHONE TO ANSWERING SERVICE).
<br /> 3 �, T'
<br /> As.o 20. ASME 211.1. PROVIDE AN EMERGENCY POWER SUPPLY FOR THE DEVICES REQUIRED BY 211.1{a)(2) AND � o
<br /> 211.1(b). THE SUPPLY SHALL BE CAPABLE OF OPERATING THE AUDIBLE DEVICE FOR AT LEAST ONE HOUR ; � o
<br /> AND THE MEANS OF TWO-WAY CONVERSATION FOR AT LEAST FOUR HOURS. `� � ■ �
<br /> � �+ �' �
<br /> 21. SBC 3016.9. INSTALL APPROVED KEY RETAINER BOX, KEYED TO THE CITY STANDARD. KEY-ACE ONE INCH z > ° � > �-
<br /> '�r`c+r �g�'t.�,...,. 4 s<'�4. `•5.��''>m�i �`� �g � m` �' : � �.�,.2 5�,��+ a /1 1 A / / / !� � � C[ Q
<br /> �<��'' � -�sr�,.� ��.��.:..� ������. ��.������.�:�.���, n, .��.n�x���-.�.��.� � r.F�e.� �;: r�,,,.,�.;�; C�r �iNDER Cr►M LG'C� �E�r �39�v4. � � N � �
<br /> 4 � � �
<br /> - � � � � �
<br /> �-�-_n-�` __ ' � � ai N � � ��/
<br /> 22. SBC 3016.10. KEYS REQUIRED FOR THE OPERATION OF ELEVATOR, FIRE EMERGENCY SERVICE, THE o o aroi � o o �
<br /> '', ; MACHINE ROOM, AND THE MECHANICAL HOISTWAY ACCESS SHALL BE TAGGED AND KEPT IN THE KEY BOX. = r� cn N N
<br /> -- -�y-- 23. COMPLY WITH ALL APPLICABLE CODES.
<br /> - i
<br /> � �
<br /> ,
<br /> � 'N ELEVATOR ELEVATOR 24. PROVIDE SHAFT PRESSURIZATION AT ELEVATORS #1 & 2. PER SBC SECTION 909.22.1 EXCEPTION:
<br /> � - "PRESSURIZE TO NOT LESS THAN 0.10 INCH OF WATER COLUMN. SEE CHAPTER 30 FOR ADDITONAL CRITERIA.
<br /> � 04 05
<br /> NO ELEVATOR LOBBIES REQUIRED, PER SBC 707.14.1, EXCEPTION 5.
<br /> 25. PROVIDE STANDBY POWER AT ELEVATOR#1, AS REQUIRED FOR ACCESSIBLE MEANS OF EGRESS. SBC
<br /> 1007.2.1
<br /> 26. ELEVATOR #1 TO ACCOMMODATE AN AMBULANCE STRETCHER. SBC 3016.12.
<br /> 3 27. GENERAL: ELEVATORS SHALL COMPLY WITH ICC/ANSI A117.1-2003 SECTION 407 AND ASME A17.1 LISTED IN
<br /> SECTION 105.2.5. ELEVATORS SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME A17.1. ELEVATOR
<br /> as.a OPERATION SHALL BE AUTOMATIC.
<br /> 28. CALL CONTROLS: WHERE ELEVATOR CALL BUTTONS OR KEYPADS ARE PROVIDED, THEY SHALL COMPLY
<br /> WITH ICC/ANSI A117.1-2003 SECTION 407.2.1 AND 309.4.
<br /> 29. HALL SIGNALS: HALL SIGNALS, INCLUDING IN CAR SIGNALS, SHALL COMPLY WITH ICC/ANSI A117.1-2003
<br /> COMMERCIAL ELEVATO F�S - GROUN D FLOOR PLAN SECTION 407.2.2.
<br /> 1i4��= ��-o^ 30. HOISTWAY SIGNS: SIGNS AT ELEVATOR HOISTWAYS SHALL COMPLY WITH ICC/ANSI A117.1-2003 SECTION
<br /> 407.2.3.
<br /> 31. ELEVATOR DOOR REQUIREMENTS: HOISTWAY AND ELEVATOR CAR DOORS SHALL COMPLY WITH ICC/ANSI
<br /> A117.9-2003 SECTION 407.3. '
<br /> 32. ELEVATOR CAR REQUIREMENTS: ELEVATOR CARS SHALL COMPLY WITH SECTION 407.4.
<br /> 33. FLOOR DESIGNATION: FLOOR DESIGNATION SHALL BE PROVIDED IN TACTILE CHARACTERS COMPLYING
<br /> WITH ICC/ANSI A117.1-2003 SECTION 703.3 LOCATED ON BOTH JAMBS OF ELEVATOR HOISTWAY ENTRANCES.
<br /> TACTILE CHARACTERS SHALL BE 2 INCHES MINIMUM HEIGHT. A TACTILE STAR SHALL BE PROVIDED ON BOTH
<br /> /r ' JAMBS AT THE MAIN ENTRY LEVEL.
<br /> �
<br /> i +
<br /> 34. CAR DESIGNATION: DESTINATION ORIENTED ELEVATORS SHALL PROVIDE CAR IDENTIFICATION IN TACTILE
<br /> _ CHARACTERS COMPLYING WITH ICC/ANSI A117.1-2003 SECTION 703.3 LOCATED ON BOTH JAMBS OF THE ��,�3 ���,,,�
<br /> _ � .... .- ...� :: : . ..• . . . ., . . • . HOISTWAY IMMEDIATELY BELOW THE FLOOR DESIGNATION. TACTILE CHARACTERS SHALL BE 2 INCHES ���gl��Q
<br /> � GROUND FLOOR ' ' � �" �
<br /> ` ��` `� `Vt' MINIMUM HEIGHT. ��.H���T
<br /> EL. 117'-0" .1. -� �'
<br /> ���
<br /> ,.�.�Y �H i e'1�t�f
<br /> ; .::
<br /> 3Tl�TE Qf w�YNB�'IOM�
<br /> ;.�':• HO1ST BEAM,
<br /> - SEE STRUCTURAL
<br /> ;;,;.
<br /> :'j;�_� Revisions
<br /> - I
<br /> .;'.=, PERMIT SUBMfTAL
<br /> �*�.,4 Q
<br /> � 5/20/2013
<br /> = 0
<br /> �' r-r
<br /> � i i _ PERMIT RE-SUBMITAL
<br /> r- �-'� ;..'� CV
<br /> i i ":;'• �-� 0 9/11/2013
<br /> _-� �_�-___ C� � oo°
<br /> �=__-_--- - -- . e ._
<br /> � I I i �•�'i. M
<br /> I � � I
<br /> i i i i V�' CV
<br /> i � � I ';;+' N
<br /> � I I = i ELEVATOR o0o a o°
<br /> � i i i CAB
<br /> i i � o o ao
<br /> 000 !
<br /> � � � t
<br /> i � � t
<br /> � � � i
<br /> i GROUND FLOOR ; i i � `�,�' CALL BUTTON AND SIGNAL HEIGHT FLOOR DESIGNATION DESTINATION-ORIENTED CAR IDENTIFICATION
<br /> EL. 99'-0„ :,;.::.:•...::� , � � , ��
<br /> � � i .y•:.
<br /> � � � i
<br /> i i ';_,.
<br /> � -� �- --�------! .
<br /> L -----� (---------J !
<br /> I I , .f
<br /> �I I I
<br /> " ' ' r�� ELEVATOR SIGNAGE
<br /> � i i :.,��
<br /> � � � ��=�
<br /> n �_�� PAGODA VfLLAGE
<br /> :....;
<br /> .�::..
<br /> � i i .,., NOT TO SCALE
<br /> ...
<br /> w � � ��- EVERETT
<br /> > i i '•'��•' ; --i I---j 'r'�-�.a� ..._ , , ,_ ; ; , ; i i ._ _--,
<br /> � � � �i -! �_ _ � i � �� � � i �- i , ___,-� ; '
<br /> ,•;.
<br /> �i
<br /> F- I '., ' ' 1 � ;- i I I _ i _� i - i i
<br /> _ I I ,. . . � I � - i i � ' �
<br /> p ,,• T _._{ I i i i i �_'_ �-i'I 4 I
<br /> ' � � T H E S I G N A G E S H A L L B E 1 2 x 1 2 GRAND & WALL STREET
<br /> . ::. _ ____
<br /> � � ..
<br /> � � � - ..: � - ; , --_� � i i F
<br /> , -----, ; ,••----- -- f
<br /> N _.
<br /> :.•; 1------ � i 1. - � ' �- -i i 1._...__.� �
<br /> `- 4_�; :.,: i � i=-i � i-�---:Y, �. _----�
<br /> EVERETT, WA
<br /> � � I r',�- � i �- -� � ' STAIR NO '� - ��� X�4�� THE STAIRWAY LOCATION
<br /> � � � i----, j ;. __
<br /> ��:..;. _
<br /> �:.:a '-�__ , --
<br /> � � ti� ' , -� ' � - SHALL BE PLACED AT THE
<br /> PARKING LEVEL 1 � � � �_� ' �', - I''-----� ' ROOF ACCESS „ N
<br /> � � . .
<br /> .' - I, , ; __,� � �� 5 X 3!4 TOP OF THE SIGN IN A 12"
<br /> � EL. 87'-0" , I I
<br /> ' �''�` '':-���� i , ' '��' '-�___-; � HIGH BLOCK LETTERING WITH
<br /> � � -� � :---I� Drawing Title
<br /> o � � ; - -: '�, ;.._.._._ �----- ��� X /4� A/4„ STROKE
<br /> ; , _ _,_
<br /> v - ' ELEVATOR PIT LADDER, I
<br /> i i SEE DETA[L9/A6.04 L_P2 TO ROOF r THE STAIRWAYS UPPER ELEVATORS
<br /> c .e �' - ''-- -T TERMINUS SHALL BE PLACED PLANS SECTIONS
<br /> . _
<br /> .. , . ..
<br /> _ .. . i: ... ,._ .
<br /> .;.
<br /> . . .
<br /> .
<br /> ��'�,.M .. �. ' d
<br /> � ,� ' y, t..� • �
<br /> -. : ;
<br /> - -� � _. '::},�.:. , :.� UNDER THE STAIR I.D. WITH 1"
<br /> .,... , �
<br /> � � � • AND N E
<br /> .:•.:: ' , � ' '
<br /> �
<br /> , :_
<br /> ..,. ' - � i I , � � ; X%4 LETTERING
<br /> . _ _._ .
<br /> .....� , < - •
<br /> : .. , -T�-� '
<br /> �. _ � � --
<br /> ...... i , � �
<br /> i•,.. � i__ i � I...
<br /> . , ,
<br /> .;•:, ,,:.;:, �
<br /> :• �
<br /> . . � ,_ f ,
<br /> �w..:. ' I � - -I i � � i ` ' THE FLOOR LEVEL NUMBER
<br /> . �_�^ � i I ;
<br /> ����� ' - ' ' ' --` SHALL BE PLACED IN THE
<br /> , � _ � � ;
<br /> :.-.
<br /> _� �
<br /> .:,; ` , _, ' ' '
<br /> -' ' �"�' ' - ' � ' - MIDDLE OF THE SIGN IN 5" X
<br /> PARKING LEVEL 2 �'� � : ; � , � I - SEE DETAI L 1 lA6.04 3 ��
<br /> ! + i
<br /> -� , „ - '�� ' ; � ' �-� � , --- ;-'- ' - ; ; /� LETTERING. BASEMENT
<br /> EL. 77-0 ,.�. .:... .. , _ _
<br /> ._.:
<br /> _.-�..: � i� ' MFB�,
<br /> : � � � ' LEVELS SHALL HAVE A
<br /> .� . . _. _
<br /> ,..r��::•: : , ' �__._
<br /> . --: ,
<br /> : . ; , �
<br /> .,. .. � '
<br /> � -�� �: �'� � � � PRECEDING THE FLOOR #
<br /> :d. I ' � � �
<br /> � � ' ..., j _
<br /> . . �
<br /> . . .. . �-._: �_...�...� I I.....� .' )� __..__�I
<br /> •� . • � �
<br /> � .. . I ' I_ _ i .
<br /> . . .� '._._.._, � �� . ��,. ' _._ I,
<br /> __. I _ I � I �' ..� ��
<br /> --:- - , .. , --�-- =-�-� ' ' - THE LOWER AND UPPER �
<br /> TERMINUS OF THE STAIR -
<br /> SHALL BE PLACED AT THE Date: 09/11/2013
<br /> BOTTOM OF THE SIGN IN 1" X Job No; -
<br /> %4" LETTERING.
<br /> - COMMERCIAL ELEVATORS - SECTION THESE SIGN SHALL BE
<br /> 3 - LOCATED 5'-0" ABOVE FLOOR Drawing No.
<br /> �ia��_ ��-o�� L.EVEL AT EACH FLOOR LEVEL
<br /> LANDING.
<br /> � ■o�
<br /> STAIRWELL SIGNAGE
<br /> IVOT TO SCALE
<br />
|