Laserfiche WebLink
. � , <br /> 20.PREMISE IDENTIFICATION AND ALL REQUIRED FIRE DEPARTMENT ACCESS ROADS <br /> AND FIRE HYDRANTS SHALL BE IN SERVICE PRIOR TO COMMENCEMENT OF <br /> CONSTRUCTION. <br /> 21.Fire Flow - Fire flow requicements for this structure aze 1,750 gpm. <br /> 22. Portable Fire Protection - A portable fire extinguisher with a minimum U.L. rating of 2-A:10-B:C <br /> shall be provided within 75 feet of travel on all floors of each building during construc6on and prior to <br /> occupancy. <br /> 23.Fire Alarm System - An approved automatic fire detection system shall be provided as required by City <br /> Ordinance No. 1902-92, Chapter 16.76, of the Everett Municipal Code. Plans for such system shaU <br /> be submitted to the Fire Marshal for review and approval prior to installadon. Submittal shall include <br /> cut sheets of all equipment intended for use. Appropriate trip tests, witnessed by a Fire Department <br /> inspector, shall be performed, along with a certificate of completion, prior to final acceptance of the <br /> system. Fire alarm systems shall be installed according to NFPA Standard 72. Fire alazm systems <br /> shall be installed under permit of the City of Everett Building Department. Electrical inspections and <br /> approval aze required prior to calling for acceptance tests. Call (425) 257-8810 for permit <br /> information. <br /> 24.Trash Collection - Dumpsters over 1.5 cubic yards capaciry shall be located a minimum of 5 feet from <br /> • the building [UFC 1103.2.2, 1994 Edition]. <br /> � <br />