�i O MECHANICAL NOTES: <br /> O 1. DUCT MATERIAL IS 26 GA. GALV. AND FLEX DUCT. DUCTWORK SHALL BE SUPPORTED PER 2015 IMC <br /> WAC CHAPTER 6. SECTION 603 <br /> 2. MATERIAL IN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25, SMOKE DEVELOPMENT • <br /> OF 50 PER 2015 IMC WAC CHAPTER 6, SECTION 602 <br /> 3. LOW PRESSURE DUCT SYSTEMS SHALL HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS ANp <br /> CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND SEALED WITH <br /> WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC SYSTEMS OR APPROVED TAPES <br /> INSTALLED IN ACCORDANCE WITH 2O15 IMC WAC CHAPTER 6 SECTION 603.9. <br /> CD-1 CD-1 <br /> 10" 10" 4. WHEN ISOLATION SLEEVES ARE USED AT LINE CONNECTIONS TO PLENUMS, THEN THEY SHALL COMPLY <br /> WITH IMC CHAPTER 6 <br /> WALL MOUNT <br /> 72� 7o\ ,O RETURN 5. 10" DIFFUSERS WITH NO MANUAL DAMPERS. USE FLOW CONTROLS AT WYES, TYPICAL AS NOTED ON PLAN <br /> � � 12 6. MINIMUM OUTSIDE AIR VENTILATION PER 2015 IMC WAC CHAPTER 4, TABLE 403,3.1.1. <br /> 1 O ,� 2 7. OUTSIDE AIR DAMPERS SHALL COMPLY WITH 2O15 WSEC, SECTION C403.2.4.3. <br /> HP-1 <br /> 1�/�O 8 2I0 0 0 BtuKhGREUUIRERECONOMI O RLS PER�WSECA403.3.AEXOTPL COOLING CAPACITY OF GREATER THAN <br /> O _ �`Z' o T TCURBF � � Q z CE T AS PERMITTED BY C403.3 EXCEPTION 1 <br /> g - - - - - - - - - - - - <br /> SUPPLY PLENUM <br /> #Pws�3� MECHANICAL NOTES: (cont.) <br /> OCCUPIED SET POINT MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUILDING SHALL BE IN ACCORDANCE WITH <br /> TO BE CONTROLLED BY THE REQUIREMENTS OF THE 2015 IMC WAC CHAPTER 6. <br /> nLIGHT OCCUPANCY <br /> SENSORS ROUND FLEX DUCT SHALL BE U.L. LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR DUCTS AND AIR <br /> CONNECTORS. MEASURED W ACCORDANCE TO ASTM C 518 OR ASTM C 177 AT 75DEG F MEAN <br /> TEMPERATURE. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURES INSTALLATION INSTRUCTIONS . <br /> CD-1 CD-1 <br /> . 10" 10" MECHANICAL DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR INSIDE DIMENSION. <br /> DUCT INSULATION SHALL COMPLY WITH 2O15 IMC WAC CHAPTER 6, SEC. 604. <br /> EL.ECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. <br /> THERMOSTAT SCHEDU�ING TO BE PERFORMED ON SITE BY OTHERS. <br /> ALL HVAC EQUIPMENT LEAVES FACTORY WIRED FOR 240 VOLT OPERATION <br /> OTHE ACCEPTAB�E OPERATING RANGE FOR THE 240V & 208V TAPS ARE: <br /> � TAP RANGE <br /> 240 253-216 <br /> MECHAN ICAL PLAN 208 22a-�8� <br /> 1/4" = 1'-0" SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS CONNECTED FOR <br /> THE APPLIED SITE VOLTAGE. <br /> MINIMUM VENTILATION RATES PER IMC SECTION 403 AIR FILTERS IN HVAC UNfTS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY QTHERS ON 51TE. <br /> Rp <br /> room# name Az(sf) sf/1000 Occ. Dens Pz(calc) Pz(used) (cfm/person) Ra (cfm/sf) Vbz(cfm) REGISTER AIR FLOW TEST AND BALANCE OF HVAC SYSTEM TO BE PROVIDED AND PERFORMED BY OTHERS ON SITE. <br /> 1 Cfassroom 817 0.817 35 29 29 10 0.12 388 <br /> 388cfm HVAC SITE CONTRACTOR IS RESPONSIBLE FOR BALANCING THE SYSTEM. (2015 IMC WAC 403.3.3.1.5) <br /> Az=room area (sfj • <br /> Occ. Dens=occupant density(from Tabie 403.3) <br /> Pz(calc) =zone population or occupant quantity(calculated) <br /> Pz(used) =zone population or occupant quantity(user can override the calculation-increase only) <br /> Rp=people outdoorairflow rate in breathing zone (cfm/person) <br /> Ra=area outdoor airflow rate in breathing zone (cfm/sf) <br /> Vbz=Breathing zone outdoor airflow rate per eq. 4-1( Rp*Pz+Ra*Az) <br /> PACKAGE *SPVU* HIGH EFFICIENCY WALL MOUNT HEAT PUMP - SCHEDULE <br /> DOAS/ERV/E�ECTRICAL 1� DOAS/ERV/ELECTRICAL � COOLWG CAPACITY(�3 HEATING CAPACITY 04 DOAS UNIT HEAT STRIPS ' <br /> ENERGY RECOVERY ELECT. INFORM. CT. INFOR . <br /> DOAS LOW VENTILATION MODE FULL VENTILATION MODE <br /> COMP TOTAL ECON. COOL SENS. COOL SENS. HTG HTG OUTDOOR E�EC. ELEC. OPER. <br /> BARD TYPE CFM BLR. 100% ERV ECM ECM OUTSIDE ENT ENT CAP. CAP. CAP. CAP. OUTSIDE CAP. CAP. SUMMER DB/WB HRS HRL WINTER INDOOR WHR HEAT HEAT WGT. ADDITIONAL <br /> TAG QTY MODEL # TONS SCROLL NOM. TYPE. FREEFLOW OSA V-PH ERV BLOWER V-PH ERV BLOWER DB DB WB EER IP�V BTUH BTUH BTUH BTUH DB COP BTUH BTUH EFFICIENT DEG'S BTUN BTUH EFFICIENT DB MOP V-PH MCA MOP CKT V-PH MCA BTUH CKT KW BTUH LBS, REMARKS <br /> � PART/FULL VENTIL MOTOR MOTOR PART LOAD PART lOAD FUU.LOAD �FULL LOAD . PART/LOAD FULL/LOAD <br /> HP-1 1 C36HA-A10ZP4XXR 3 2-STAGE 750 ECM NO 388 230/1 AMPS-1.3 AMPS-.87 230�� AMPS-2.2 AMPS-1J4 95 8d 67 11.0 14.5 23.4K T8.5K 35K 26.3K 47 3.3 22.7K 31K 65% 95/70 6,318 1,711 80% 1,711 23,328 230 1 27 40 A 240 1 52 60 B 10 34,130 678 1, 2, 3, 4, 5, 6, 7, 8 <br /> 1100 450 WATTS-296 WATTS-95 WATTS-497 WATTS-192 � � <br /> ADDITIONAL REMARKS; c3sHi The sequence of operation for the Integrated DOAS system. <br /> 2 - PNC UQE BARD WALL CURB #TCURBF3642A-4. ERV Watts - Low 296 Watts Biower Full Load 192 Watts 1. Upon a call from the occupancy sensor the(DOAS) ERV and the indoor(ECM)motor will <br /> 3 - THERMOSTAT, BARD # 8403-060, 7-DAY PROGRAMMABLE. ERV Am s - Low 1.3 Am s Blower Full Load 1.74 Am s start in low vent mode and ventilate the space continuously as occupied. <br /> A - WALL CO2 SENSOR. #8403-067 ERV CFM - Low 300 CFM Blower Part Load 95 Watts Note: 1 on the HVAC Schedule. <br /> 5 - OCCUPANCY SENSOR, (SUPPLIED BY BLAZER) ERV Watts - Med 415 Watts Blower Part Load 0.87 Am s 2, U on a call from the CO2 sensor the DOAS ERV and the indoor ECM motor will <br /> 6 - GPS (FIELD INSTALLED CONTROL KIT). ERV Am s - Med 1.8 Am s p � � � � <br /> 7 - 2" Fi�TER. ERV CFM - Med 375 CFM Com ressor Full 2588 Watts change to full vent mode and ventilate the space until the CO2 sensor is satisfied and then <br /> a - ERv (�oAs) ENERGY RECOVERY. ERV Watts - Hi 497 Watts Com ressor Full 11.46 Am s revert back to the low vent mode during the occupied time. <br /> 9 - UNIT COLOR IS *BUCKEYE GRAY* ERV Am s - Hi 2.2 Am s Com ressor Part 1734 watts Note: 2 on the HVAC Schedule. �. <br /> 10 - PRE INSTALLED OUTDOOR THERM05TAT, SET AT 40DEG'S. ERV CFM - Hi 450 CFM Com ressor Pqrt 7.99 Am s 3. The Heating and Cooling section will only work if there is a Heating or Cooling call from <br /> *. outdoor Fan 38o Watts the thermostat. This action works entirely independent of the DOAS ventilation portion. <br /> M.C. TO REFER TO INSTA�LATION INSTRUCTIONS FOR START UP AND EQUIPMENT SET. <br /> ** M.C. TO CHECK SITE VOLTAGE AND SET CORREGT TAP ON TRANSFORMER. Outdoor Fan 1.67 Am s Note: 3&4 on the HVAC Schedule. <br /> ** M.C. TO SET AND PROGRAM THERMOSTAT PER CUSTOMERS REQUIREMENTS. 4. ThIS aCt1011 WIII ke8p f2p@2titlg ItS@If aS f2qUl1'ed by fhG'OCCUpa11Cy S@I1SOf, CO2 sensor <br /> and Room Thermostat. <br /> 8-18-17 REVISE HEAT PUMP SCHEDULE,ADD SEQUENCE OF OP. RMS COPYRIGHT 2017, BLAZER INDUSTRIES, INC. � MODULAR Approved for Const: Job No: 19031 <br /> 9-6-17 ADD SUPPLY PLENUM NUMBER (#PWS131) LDG THIS MATERIAL IS THE EXCLUSIVE PROPERTY C/assroom for.� <br /> OF BLAZER INDUSTRIES, INC.AND SHALL ■■ File Copy: <br /> NOT BE REPRODUCED, USED,OR DISCLOSED �� 2$ x 32 KC DA - Everett S�D■ <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE wouSrRiEs,wC. Drawn By: LDG � <br /> DATE REVISION BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. � �•blazerind.com wA. GOLD Pacific Mobile 17 BLMP-04 A9 WA <br /> �� P.O.BOX 489 ■ Aumsville,OR 97325-0489 ISsue Dat2: 9-6-�7 <br />