POWER CONDUIT AND RACEWAY ONE-LINE DIAGRAM LIGHTING DRAWING CONVENTIONS
<br /> FOR RECEPTACLES IN THIS SECTION, WP DENOTES ALL CONDUCTORS INCLUDING NEUTRAL AND ALL DEVICES THIS SECTION TO BE 3 POLE UNO, SEE LUMINAIRE SCHEDULE FOR FURTHER INFORMATION. SMALL LETTER
<br /> WEATHERPROOF WHILE-IN-USE BOX AND GR GROUND SHALL BE SIZED TO MATCH OR EXCEED RATINGS AS INDICATED. SUBSCRIPT ON SWITCH AND LUMINAIRE INDICATES CONTROL GROUP. A TITLE DETAIL/SECTION TITLE UNDERLINE,
<br /> RECEPTACLE. FOR ALL OTHER DEVICES, WP OVERCURRENT PROTECTION DEVICE PER NEC, 2#12, MULTIPLE SUBSCRIPTS INDICATE MULTIPLE CONTROL GROUPS MANAGED E2.1 SCALE: 1/4"=1'-0" E2.1 = SHEET WHERE REFERENCED
<br /> DENOTES NEMA 3R ENCLOSURE UNO. 1#12G MINIMUM UNO. ALL CONDUITS SHALL BE •da..J TRANSFORMER, SECONDARY BY ONE SWITCH.
<br /> CONVENIENCE RECEPTACLE - SIZED TO MATCH OR EXCEED QUANTITIES AND VOLTAGE. PHASE AND RATING
<br /> ' DUPLEX UNO, MOUNTING HEIGHT SIZES OF CONDUCTORS PER NEC, 3/4" MINIMUM , INDICATED AS APPLICABLE A AA = DETAIL/SECTION NUMBER
<br /> 93 TO BE 18" AFF UNO UNO. _J_ GROUND EXISTING ® ® E5.1 = SHEET WHERE SHOWN
<br /> 3 = CIRCUIT NUMBER HOME RUN, DESTINATION =
<br /> CONVENIENCE RECEPTACLE - P1_t 3 SHOWN, CIRCUIT NUMBERS OQI�00+ POINT SOURCE LUMINAIRES /\
<br /> FOURPLEX PRECEDED BY PANEL NAME, - FUSE
<br /> SEE PANEL SCHEDULE, ARROW x 400 �� NORTH ARROW
<br /> DOES NOT ALWAYS POINT TO --0 CIRCUIT BREAKER
<br /> 0 v
<br /> QJ JUNCTION BOX PANEL 400 '—�—� 0 '
<br /> I I
<br /> SPECIAL PURPOSE RECEPTACLE, ABOVE GROUND CONDUIT AND 0400— SWITCH I 10I I I II LINEAR LUMINAIRES 3O NOTE
<br /> —
<br /> DESIGNATION AND AMPERAGE AS CONDUCTORS, CONCEALED 1
<br /> ®." INDICATED, OR SHOWN IN UNO. EXPOSED CONDUITS v J REVENUE GRADE METER AND 11 I I Q1 REVISION REFERENCE
<br /> A SCHEDULE, SEE SPECIFICATIONS SHALL BE GRS PAINTED TO ENCLOSURE
<br /> CONNECTION POINT TO MATCH THE STRUCTURE,
<br /> CURRENT TRANSFORMER IIN
<br /> EMBEDDED CONDUITS SHALL
<br /> EQUIPMENT SPECIFIED FURNISHED LUMINAIRES ON EMERGENCY
<br /> ® AND INSTALLED BY OTHER BE SCHEDULE 40 PVC UNO. 0 • CIRCUIT
<br /> TRADES. RACEWAY, CONDUCTOR UNDERGROUND CONCEALED O p TRANSFER SWITCH GENERAL NOTES
<br /> AND CONNECTION BY ELECTRICAL _ - CONDUIT AND CONDUCTORS, d
<br /> CONTRACTOR. SCHEDULE 40 PVC UNO. EMERGENCY EGRESS 1. MEET ALL REQUIREMENTS OF THE NEC AND AHJ FOR
<br /> 0MOTOR CONNECTION r LUMINAIRE INSTALLATION AND CONSTRUCTION.
<br /> IZENONFUSED30A NI ESS DISCONNECT SWITCH. D CONDUIT DOWN2. VERIFY LOCATION OF ALL MECHANICAL AND HEATING
<br /> ❑� SIZE UNLESS INDICATED FEEDERETAG - SUE HEEDER EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO
<br /> OTHERWISE, 3 POLE UNO —0 CONDUIT UP XX SCHEDULE FOR FURTHER ROUGH-IN. COORDINATE EXACT CIRCUIT BREAKER, FUSE
<br /> FUSED DISCONNECT SWITCH. INFORMATION AND WIRE SIZE WITH MECHANICAL PRIOR TO ROUGH-IN.
<br /> SIZE INDICATED, (60 = SWITCH 3 CONDUIT STUBBED AND 3. VERIFY LOCATION OF ALL LUMINAIRES AND DEVICES WITH
<br /> 60/40 ATING, 40 = FUSE RATING) 3 CAPPED AS SHOWN ARCHITECTURAL AND/OR LANDSCAPE PLANS AND ELEVATIONS
<br /> POLE UNO —Z CONDUIT CONTINUED
<br /> PRIOR TO ROUGH-IN.
<br /> ;-...---1 PANEL �57..-- - EXPOSED FLEX CONDUIT 4. ALL EXTERIOR DEVICES TO BE CIRCUITED WITH #10 WIRE
<br /> MINIMUM UNLESS NOTED OTHERWISE.
<br /> O TRANSFORMER • CONDUIT SEAL FITTING 5. ALL WIRING SHALL BE COPPER UNLESS NOTED OTHERWISE.
<br /> El HANDHOLE, SIZE AS NOTED 6. VERIFY LOCATIONS OF OTHER UTILITIES PRIOR TO
<br /> G GENERATOR COMMENCING WORK, PROVIDE REQUIRED CLEARANCES FROM
<br /> OTHER UTILITIES, BUILDINGS, AND FREESTANDING
<br /> STRUCTURES, DURING INSTALLATION OF CONDUITS, CABLES,
<br /> ETC.
<br /> 7. USE ELECTRICAL PLANS FOR DETERMINING LUMINAIRE AND
<br /> DEVICE COUNTS. QUANTITIES SHOWN WITHIN CALCULATION
<br /> AND CONTROL SCHEDULES SHALL NOT BE USED FOR BID
<br /> COUNTS.
<br /> 8. NOT ALL COMPONENTS OF THE ELECTRICAL SYSTEMS ARE
<br /> ABBREVIATIONS SHOWN (FOR CLARITY). PROVIDE MATERIALS AND LABOR
<br /> NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.
<br /> A AMMETER, AMPERE CPT CONTROL POWER TRANSFORMER GA GAUGE N NEUTRAL, NEW SW SWITCH 9. THE AIC OF THE PANELS SHOWN ARE TENTATIVE AND GIVEN
<br /> AC ABOVE COUNTER CR CONTROL RELAY GALV GALVANIZED NC NORMALLY CLOSED SWBD SWITCHBOARD FOR BIDDING PURPOSES ONLY. CONTRACTOR SHALL
<br /> AF AMPERE FRAME CT CURRENT TRANSFORMER GFT GROUND FAULT INTERRUPTER NEUT NEUTRAL SWGR SWITCHGEAR CALCULATE THE PANEL AIC BASED UPON FINAL CONDUIT
<br /> AFF ABOVE FINISHED FLOOR CTRL CONTROL GRC,GRS GALVANIZED RIGID STEEL NO NORMALLY OPEN, NUMBER SYM SYMMETRICAL ROUTING AND TRANSFORMERS AND FUSES SUBMITTED.
<br /> AFG ABOVE FINISHED GRADE CU COPPER HH HANDHOLE NIC NOT IN CONTRACT T THERMOSTAT
<br /> AHJ AUTHORITY HAVING JURISDICTION DDC DEDICATED DIALER CIRCUIT HP HORSEPOWER NP NAMEPLATE TB TERMINAL BLOCK, TRANSFORMER BANK 10. THE OPERATION OF THE FACILITY WILL TAKE PRECEDENCE
<br /> AIC AMPERE INTERRUPTING CAPACITY DEM DEMAND HPS HIGH PRESSURE SODIUM 0 PHASE, DIAMETER TEL TELEPHONE OVER THE WORK OF THE CONTRACTOR. IT IS THE
<br /> AL ALUMINUM DEMO DEMOLITION HVAC HEATING, VENTILATION, AIR CONDITIONING P PANEL, POLE TPU TACOMA PUBLIC UTILITIES RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE
<br /> ANN ANNUNCIATOR DIM DIMENSION HWH HOT WATER HEATER PB PUSH-BUTTON TTB TELEPHONE TERMINAL BOARD CONSTRUCTION WITH OWNER'S PERSONNEL TO MINIMIZE
<br /> ASYM ASYMMETRICAL DISC DISCONNECT IC INTERRUPTING CAPACITY PF POWER FACTOR TYP TYPICAL DISRUPTION TO THE FACILITY.
<br /> AT AMPERE TRIP DN DOWN JB,J-BOX JUNCTION BOX PH PHASE UG UNDERGROUND 11. OUTAGES ARE TO BE MINIMIZED. PROVIDE NOTIFICATION TO
<br /> ATS AUTOMATIC TRANSFER SWITCH DS DISCONNECT SWITCH K KELVIN PIR PASSIVE INFRARED UH UNIT HEATER
<br /> AUX AUXILIARY DWG DRAWING KCM THOUSAND CIRCULAR MILS PIV POST INDICATOR VALVE UL UNDERWRITERS LABORATORIES OWNER'S PERSONNEL OF ANY IMMINENT POWER OUTAGES A
<br /> BLDG BUILDING DZ DAYLIGHT ZONE KV KILOVOLT PNL PANEL UNO UNLESS NOTED OTHERWISE MINIMUM OF 48 HOURS PRIOR TO OUTAGE. PROCEED WITH
<br /> BRKR BREAKER E EMPTY, EXISTING KVA KILOVOLT AMPERE(S) POMB POSITION ORIENTED MOGUL BASE UPS UNINTERRUPTIBLE POWER SUPPLY EACH OUTAGE ONLY AFTER APPROVAL FROM OWNER'S
<br /> C CONDUIT EF EXHAUST FAN KW KILOWATT(S) (SOCKET) V VOLTMETER, VOLT PERSONNEL IS GIVEN.
<br /> CAN CABLE TELEVISION ELEC ELECTRICAL LC LIGHTING CONTACTOR PS PRESSURE SWITCH VA VOLT AMPERE(S) 12. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL
<br /> CB CIRCUIT BREAKER ELEV ELEVATION, ELEVATOR LED LIGHT EMITTING DIODE PSE PUGET SOUND ENERGY VP VAPORPROOF DIMENSIONS AND CONDITIONS, WHICH MAY AFFECT THE
<br /> CCTV CLOSED CIRCUIT TELEVISION EMT ELECTRICAL METALLIC TUBING M MAGNETIC COIL R RELAY W WIRE, WATT WORK REQUIRED FOR THIS PROJECT PRIOR TO THE
<br /> - CKT CIRCUIT EXIST EXISTING MCB MAIN CIRCUIT BREAKER REC RECEPTACLE(S), RECESSED W/ WITH BEGINNING WORK.
<br /> t CENTER LINE F,FU FUSE MCC MOTOR CONTROL CENTER RM ROOM WAC WASHINGTON ADMINISTRATIVE CODE
<br /> CL CURRENT LIMITING FACP FIRE ALARM CONTROL PANEL MH MANHOLE, METAL HALIDE SCH SCHEDULE WHD WATTHOUR DEMAND METER
<br /> CLF CURRENT LIMITING FUSE FBOIC FURNISHED BY OTHERS INSTALLED BY MIN MINIMUM SCL SEATTLE CITY LIGHT W/0 WITHOUT
<br /> CLR CLEAR CONTRACTOR MISC MISCELLANEOUS SEC SEATTLE ENERGY CODE WP WEATHERPROOF
<br /> o CM CIRCULAR MILS FLUOR FLUORESCENT MLO MAIN LUGS ONLY SD SMOKE DETECTOR WSEC WASHINGTON STATE ENERGY CODE
<br /> 44 COMM COMMUNICATIONS FSA FIRE SYSTEM ANNUNCIATOR MOV METAL OXIDE VARISTOR SF SQUARE FEET XFMR TRANSFORMER
<br /> CONC CONCRETE FT FOOT MTD MOUNTED SHT SHEET 3P 3-POLE
<br /> CONST CONSTRUCTION FVNR FULL VOLTAGE NON-REVERSING MTG MOUNTING SPD SURGE PROTECTIVE DEVICE
<br /> CONT CONTINUED G,GND GROUND MTS MANUAL TRANSFER SWITCH SUPV SUPERVISOR
<br /> T
<br /> 3.
<br /> N O 041
<br /> iii
<br /> N O
<br /> y of i "KPHNO. DATE BY REVISION DRAWN: CMS PROJECT NO.: W.O. #32 I"'
<br /> EL-CON ASSOCIATES, INC 484N.°�x s� COMMUNITY TRANSIT MERRILL CREEK DESIGN: SDB SCALE:NONE tW
<br /> ~ Ng ENGINEERS-CONSULTANTS ‹N OPS BLDG HOIST BAY CONVERSIONCHECKED: DKS DATE: JAN 3, zon F-
<br /> cg 16300 CHRISTENSEN ROAD,SUITE 330 7100 HARDESON ROAD,EVERETT,WA
<br /> o SEATTLE,WASHINGTON 98188 DRAWING N0.
<br /> k e`,WAingon98301� TEL(206)243-5022 sjo� •� LEGEND AND ABBREVIATIONS EO.1ce
<br /> LU
<br /> 8 (206)382-0600 Fax(206)382-0500
<br /> a
<br /> I/3/F1 SHEET NO. OF Q