Laserfiche WebLink
GENERAL NOTES <br /> 1. ALL EQUIPMENT IS EXISTING, TO <br /> CONTINUED FROM PART 1 REMAIN AS-IS UNLESS NOTED <br /> OTHERWISE OR DENOTED BY BOLD <br /> / LINE WORK. <br /> c(}-(3,000A/3P 1 100A/3P MAIN SWITCHBOARD 75KVA 225A/3P <br /> 4 I \I 100A MLO 15KVA 50A/3P �.� <br /> ' / I <br /> 150A/3P ] [ <br /> TPS2 PS2 <br /> 4X T2X 2X 225A MLO <br /> 0•• 00 <br /> 00 <br /> 100A/3P 350 KW 225A/3P <br /> 100A ATS }f 2 GENERATOR DOWNSIZE 600A CIRCUIT <br /> 3,000A ATS #1 BREAKER OR UPGRADE L4 LOAD SUMMARY <br /> q o- o O GENERATOR (WORK TO 225A MLO <br /> b 600A/3P ___ BE PERFORMED UNDER 400A PANEL SW4-1 (480V 30) MAX 33.2 KVA 39.9 A <br /> SEPARATE CONTRACT) 0 30-DAY DEMAND JAN-FEB 2016 <br /> 225A/3P 3,000A SERVICE (480V 30) MAX 371.0 KVA 446.2 A <br /> 75KVA 225A/3P PS4 12-MONTH DEMAND JAN 2016 <br /> 3,000A <br /> MAIN ,---_ <br /> DISTRIB. <br /> 100A/3P <br /> 3P IIIo o DEMOLISHED LIGHTING -4.0 KVA -4.8 A <br /> PANEL TRD RD 50A/3P © NEW LIGHTING 1.7 KVA 2.1 A <br /> b ELEV #1 <br /> 400A MLO NEW BAY 5 & BAY 14 LIFTS 39.5 KVA 47.5 A <br /> ,----. NEW BODY SHOP PORTABLE LIFTS 34.9 KVA 42.0 A <br /> ---o o OFFICE PORTION <br /> 400A/3P o 0 <br /> OP4 60A/3P d E©#2 TOTAL LOAD ADDED TO SW4-1 74.4 KVA 89.5 A <br /> 112.5KVA 400A/3P EXISTING SW4-1 LOAD + 125% <br /> ,-- -, - 225A MLO PER NEC 220.87 41.5 KVA 49.9 A <br /> -0 0 ] [----- <br /> 175A 3P 0 TOTAL LOAD PANEL SW4-1 115.9 KVA 139.4 A <br /> TOP2 OP2 225A/3P <br /> 600A MLO 112.5KVA 400A/3P AC TOTAL LOAD ADDED TO SERVICE 72.2 KVA 86.8 A <br /> �� EXISTING SERVICE LOAD + 125% <br /> -0 0 463.8 KVA 557.8 A <br /> 600A/3PPER NEC 220.87 <br /> SPARE <br /> SE4 TSE2 SE2 400A/3P TOTAL SERVICE LOAD 535.9 KVA 644.6 A <br /> 301NA 100A/3P COMPONENT REBUILD <br /> 50A/3P ] II225A/o SPARE <br /> TCR CR PANELBOARD SW4-3 225 A BUS SECTIONS: 1 SURFACE MOUNTED <br /> 400A MLO 112.5KVA 400A/3P �--. 480/ 277V 3 PHASE 4 WIRE 225 A MCB LUGS: SINGLE NEMA: 1 <br /> o -.. 0 0 - SPARE LOCATION: ELEC ROOM 197A 35,000 AIC FEED: NUMBER OF POLES: 42 <br /> 125A/3P CKT TYPE SERVES C.B. KVA CONNECTED PHASE LOAD KVA C.B. SERVES TYPE CKT <br /> 400A/3P \ 1 MO LIFT BAY 5 30/3 18.96 12.1 17.46 60/3 BODY SHOP UFT RECEPT MO 2 <br /> SW4-1 TSW2 SW2 <br /> 400A MLO <br /> SHOP AND BODY SHOP _0 o SPACE 5 ___ 12.1 12 1 --- 4 <br /> 125A/3P6 <br /> a PROVIDE 225A/3P 7 MO UFT BAY 14 30/3 18.96 12.1 17.46 60/3 BODY SHOP LIFT RECEPT MO 8 <br /> 400A/3P 35K AIC BREAKER IN TRANSMISSION 9 --- 12.1 --- 10 <br /> SW4-2 EXISTING PANEL -0 o DYNOMETER 11 --- 12.1 --- 12 <br /> 225A MLO 400A/3P RM #157 13 SPACE 0.0 SPACE 14 <br /> \ NEW UFT 15 SPACE 0.0 SPACE 16 <br /> PANEL 17 SPACE 0.0 SPACE 18 <br /> -� o- SPACE <br /> .. 19 SPACE 0.0 SPACE 20 <br /> ` SW4-3 225A/3P <br /> 400A MLO 30KVA 100A/3P 21 SPACE 0.0 SPACE 22 <br /> 23 SPACE 0.0 SPACE 24 <br /> o -0 o SPACE 25 SPACE 0.0 SPACE 26 <br /> 400A/3P ( I 225A/3P 27 SPACE 0.0 SPACE 28 <br /> BW4 TBW2 BW2 BUS WASH AND 29 SPACE 0.0 SPACE 30 <br /> 225A/3P 451NA 150A/3P FUEL ISLAND 31 SPACE 0.0 SPACE 32 <br /> o0 SPACE 33 SPACE 0.0 SPACE 34 <br /> 1.- 125A/3P <br /> 35 SPACE 0.0 SPACE 36 <br /> F4 TF2 F2 37 SPACE 0.0 SPACE 38 <br /> -0 0 SPACE 39 SPACE 0.0 SPACE 40 <br /> il CONTINUED ON PART 2 125A/3P 41 SPACE 0.0 SPACE 42 <br /> a 24.3 24.3 24.3 CALCULATED LOAD 77.6 KVA ', <br />. 3 <br /> � o o MAXIMUM AMPS PER PHASE 93.3 AMPS 4 <br /> M <br /> c, <br /> of i NO. DATE BY REVISION DRAWN: CMS PROJECT NO.: W. #32 <br /> N. 8, 0$.S COMMUNITY TRANSIT MERRILL CREEK w <br /> l<PffELCON ASSOCIATES, INC 4 DESIGN: SDB SCALE: NONE Cl) <br /> OJ <br /> ENGINEERS-CONSULTANTS o` ►1N OPS BLDG HOIST BAY CONVERSION CHECKED: DKS DATE: JAN 3, 2017 I_ <br /> 0 16300 CHRISTENSEN ROAD,SUITE 330 /i. 7100 HARDESON ROAD,EVERETT,WA <br /> DRAWING NO. 2 <br /> 0 o SEATTLE,WASHINGTON 98188 <br /> ii I6016thAenue,8ui[e1300 TEL(206)243-5022 '4"4.,oHb62� A. ELECTRICAL ONE-LINE DIAGRAM E3.1ce <br /> y m (206)3 Washington98101yyyyyyg�pn•()pm ' 1 _ _ / <br /> o/ (208)382-0600 Fax(206)382-0600 .32- <br /> 1!3/11 SHEET NO. 7.8-0F 0. <br />