<br /> GRIL�ES , REGISTERS A�1D D FFUSERS GRI ��ES , REGISTERS A�1D D FFUSERS GENERA� NOTES �
<br /> 1. WITH SQUARE TO ROUND ADAPTOR ,
<br /> SP. MAX. SP. MAX. SEE PLANS FOR ROUND SIZE.
<br /> FACE INLET THROW MAX FACE INLET THROW MAX
<br /> MARK SERVICE MFR MODEL SIZE SIZE IN. �- NC CFM NOTES MARK SERVICE MFR MODEL SIZE SIZE IN. �- NC CFM NOTES
<br /> WG LEVEL WG LEVEL 2. FOR INVERTED TEE CEILING MOUNTING
<br /> � CO-ORDINATE CEILING TYPE WITH
<br /> SD-263 SUPPLY AIR TITUS TDC-AA-3-4A 24/24 9/9 .10 6 24 310 NOTE 1,2 ER-217 EXHAUST AIR TITUS 13RS 24/12 24/12 .09 -- 30 1230 W/AG-35 DAMPER ARCH. CONTR. .
<br /> SD-264 SUPPLY AIR TITUS TDC-AA-3-2S 24/24 9/9 .10 6 22 300 NOTE 1,2,4 ER-218 EXHAUST AIR TITUS 13RS 32/12 32/12 .09 -- 30 1610 W/AG-35 DAMPER 3. FOR DRY WALL CEILING.
<br /> SD-265 SUPPLY AIR TITUS TDC-AA-3-2S 24/2412/12 .05 5 14 388 NOTE 1,2,4
<br /> 4. 2-WAY THROW.
<br /> SD-266 SUPPLY AIR TITUS TDC-AA-3-2S 24/24 6/6 .03 11 0 70 NOTE 1,2,4 RR-210 RETURN AIR TITUS 23MRS 24/24 22/22 .07 -- 19 800 NOTE 2 5. 3-WAY THROW.
<br /> SD-267 SUPPLY AIR TITUS TDC-AA-3-3A 24/24 6/6 .05 8 7 90 NOTE 1,2,5 RR-211 RETURN AIR TITUS 23MRS 24/12 22/10 .04 -- �6 SEE NOTE 2 6. 1 WAY THROW.
<br /> PLANS
<br /> SD-268 SUPPLY AIR TITUS TDC-AA-3-4A 24/24 9/9 .05 4 10 210 NOTE 1,2 RR-221 RETURN AIR TITUS 23MRS 24/12 22/10 -- NOTE 2 7. TRANSITION TO DIFFUSER INLET
<br /> �
<br /> SIZE AT DIFFUSER.
<br /> SD-269 SUPPLY AIR TITUS TDC-3-2S 24/24 6/6 .05 13 7 100 NOTE 1,2,4 RR-222 RETURN AIR TITUS 50F 24/12 -- .05 -- 19 1000 NOTE 9 8. FACTORY PLENUM '
<br /> SD-270 SUPPLY AIR TITUS TDC-3-3A 24/24 6/6 .02 3 0 30 NOTE 1,3,5 RR-223 RETURN AIR TITUS 50F 24/24 -- .04 -- 16 2200 NOTE 9 9. EGGCRATE CORE ONLY FOR LAY-IN
<br /> SD-271 SUPPLY AIR TITUS TDC-3-2S 24/24 6/6 .09 16 20 140 NOTE 1,2,4 RR-224 RETURN AIR TITUS 23RL 24/16 22/14 -- SEE T-BAR CEILING (1/2"x1/2"x1/2").
<br /> PLANS 10. UPDATED AIR FLOW PARAMETERS.
<br /> SD-272 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .09 7 24 300 NOTE 1,2 RR-225 RETURN AIR TITUS 23RL 24/12 22/10 -- SEE
<br /> PLANS 11 . HEAT/VENT TO BALANCE AIR TO CFMS
<br /> SD-273 SUPPLY AIR TITUS TDC-3-3C 24/24 9/9 .05 7 11 225 NOTE 1,2,5 SD-316 SUPPLY AIR TITUS TMRA 27"� 12"� 07 11 35 754 SHOWN.
<br /> � SD-274 SUPPLY AIR TITUS TDC-3-2S 24/24 9/9 .07 19 18 270 NOTE 1,2,4 SD-317 SUPPLY AIR TITUS TDCA-3-4A 24 24 8"� .04 6 16 220 12. TWO REQ'D FOR BOTH SIDES OF WALL.
<br /> SD-275 SUPPLY AIR TITUS TDC-3-4A 24/24 6/6 .12 5 27 160 NOTE 1,2 SD-318 SUPPLY AIR TITUS TMSA 24/24 g"� .07 9 17 250 24/24 MODULE 13. VAV DIFFUSER SET UP BELOW �
<br /> VFS COOLING ONLY DIFFUSER SETUP AND BALANCE
<br /> SD-276 SUPPLY AIR TITUS TDC-3-4A 24/24 6/6 .11 6 20 150 NOTE 1,2 SD-319 SUPPLY AIR TITUS TMSA 24/24 �p"� .05 10 15 300 24/24 MODULE a) SET THE TEMPERATURE ON THE PRIMARY TEMPERATURE CONTROL SO THAT
<br /> THE SUPPLY AIR TTEMPERATURE IS 65 DEGREES OR LESS. THE ROOM TEMPERATURE
<br /> SD-277 SUPPLY AIR TITUS TDC-3-4A 24/24 6/6 .07 7 14 120 NOTE 1,2 SD-320 SUPPLY AIR TITUS US300FL 24/10 24/10 .06 12 20 625 SHOULD BELESS THAN 75 DEGREES F. THE TEMPERATURE IS NOT IMPORTANT UNTIL
<br /> SD-278 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .10 9 23 300 NOTE 1,2 STEP 10 (ADJUSTING THE MINIMUM SET POINT). IF A MINIMUM AIR VOLUME IS NOT
<br /> REAUIRED, THE ROOM TEMPERATURE IS NOT IMPORTANT FOR THE PURPOSE OF
<br /> SD-279 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .10 9 24 315 NOTE 1,2 TG-321 TRANSFER AIR TITUS 33RL 24/24 24/24 .05 NA NA 1625 NOTE 12 BALANCING.
<br /> B) OPEN AND REMOVE THE APPEARANCE PANEL COVER.
<br /> SD-280 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .05 9 10 190 NOTE 1,2 THERMAL C) OPEN THE ADJUSTMENT ACCESS COVER Bl' ROTATING IT TO EXPOSE THE
<br /> � SD-322 SUPPLY AIR PRODUCTS VFS-24C 24 24 8"� .05 5 21 200 NOTE 13 ADJUSTMENT SET SCREW.
<br /> SD-281 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .05 14 11 250 NOTE 1,2 SD-323 SUPPLY AIR TITUS TMS 24/24 12" .06 9 21 550 D) REMOVE THE MINIMUM SET POINT ADJUSTMENT SET SCREW. KEEP SCREW �
<br /> FOR REINSERTION AT LATER STEP.
<br /> SD-282 SUPPLY AIR TITUS TDC-3-4A 24/24 12/12 .05 13 13 350 NOTE 1,2 SD-324 SUPPLY AIR TITUS MCD 24/24 g" .032 7 19 210 NOTE 1 E) INSERT THE BALANCING PIN INTO THE MINIMUM ST POINT ADJUSTMENT HOLE.
<br /> DAMPER IS NOW IN FULL OPEN POSITION. ROTATE THE ADJUSTMENT ACCESS COVER
<br /> SD-283 SUPPLY AIR TITUS TDC-3-4A 24/24 6/6 .10 9 19 150 NOTE 1,2 SD-325 SUPPLY AIR TITUS p " 42 8 18 320 NOTE 1 TO THE CLOSED POSITION. OVER THE BALANCING PIN. tHE COVER WILL HOLD THE
<br /> BALANCING PIN IN PLACE.
<br /> SD-284 SUPPLY AIR TITUS TDC-3-2S 24/24 6/6 .12 11 22 140 NOTE 1,2,4 SD-326 SUPPLY AIR TITUS 272FL 48/24 48/24 .020 61 24 4500 K REPEAT ABOVE STEPS FOR ALL DIFFUSERS.
<br /> SD-285 SUPPLY AIR TITUS TDC-3-3A 24/24 6/6 .10 14 20 150 NOTE 1,2,5,7 F) BALANCE AIR FLOW TO DIFFUSER.
<br /> G REMOVE THE BALANCING PIN
<br /> SD-286 SUPPLY AIR TITUS TDC-3-3A 24/24 9/9 .10 12 24 300 NOTE 1,2,5 H REINSTALL THE MINiMUM SET POINT SCREW. IF A MINIMUM AIR VOLUME IS
<br /> � SPECIFIED, GO TO NEXT STEP.
<br /> SD-287 SUPPLY AIR TRANE VDLD-2LA1 24�113�16 5 � .05 5 -- 50 NOTE 2,6 I) tHE DAMPER SHOULD BE IN THE FULLY CLOSED POSITION �EFORE THE MINIMUM �
<br /> SET POINT CAN BE SET. CHECK THE DAMPER POSITION BY VISUAL INSPECTION. IF THE
<br /> SD-288 SUPPLY AIR TITUS TDC-3-4A 24/24 15/15 .03 8 16 606 NOTE 1,2 DAMPER IS NOT FULLY CLOSED, ADJUST THE VAV COOLING ADJUSTMENT TO A HIGHER
<br /> TEMPERATURE TO CLOSE THE DAMPER. ADJUST THE MINIMUM SET POINT ADJUSTMENT
<br /> SD-289 Sl1PPLY AIR TITUS TDC-3-3A 24/24 9/9 .05 14 11 190 NOTE 1,2,5 SCREW TO OPEN THE DAMPER. BALANCE TO MINIMUM AIR FLOW.
<br /> SD-290 SUPPLY AIR TITUS TDC-3-4A 24/24 6/6 .12 11 22 165 NOTE 1,2 DIFFUSER). THE VAV COOLING TEMPERATURE SET POINT (SEE INTRUCTON LABEL. ON
<br /> REPEAT STEPS F THROUGH J FOR ALL DIFFUSERS IN THE CONTROL ZONE.
<br /> % ; ., ,
<br /> SD-300 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .05 14 12 227 NOTE 1,2 ;
<br /> i -
<br /> , ;- -
<br /> SD-301 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .07 11 18 266 NOTE 1,2 � �
<br /> �
<br /> � , � �
<br /> SD-302 SUPPLY AIR TITUS TDC-3-4A 24 24 9 9 .�. ,;= �� � �
<br /> ,� � � ,
<br /> / / .03 9 10 170 NOTE 1,2 �
<br /> - ,
<br /> � �' ' ����� ��
<br /> i
<br /> . � ��
<br /> , , f
<br /> SD-303 SUPPLY AIR TITUS TDC-3-4A 24/24 6/6 .05 8 15 125 NOTE 1,2 � ; � ; I' �t ,'�;:
<br /> - � i S � � r r.���
<br /> �' , 1 °�l
<br /> SD-304 SUPPLY AIR TITUS TDC-3-4A 24/24 9/9 .04 10 11 180 NOTE 1,2 � �"
<br /> SD-305 SUPPLY AIR TITUS TDC-3-4A 24/24 12/12 .05 12 13 380 NOTE 1,2
<br /> � SD-306 SUPPLY AIR TITUS TDC-3-3A 24/24 9/9 .05 11 12 195 NOTE 1,2,5 ���Y �� �����T� �
<br /> �EVI�UV�D �aR P���IT
<br /> SD-307 SUPPLY AIR TITUS TDC-3-4A 24/24 12/12 .06 13 14 400 NOTE 2
<br /> SD-308 SUPPLY AIR TITUS TDC-3-4A 24/24 18/18 .05 10 16 788 NOTE 2
<br /> Permit#: M1806-050
<br /> SD-309 SUPPLY AIR TITUS TDC-3-3C 24�24 15�15 .10 10 16 591 NOTE 2, 5 Site,�ddress: 3Q03 W CASINO RD 4(3-56
<br /> Owner: BOEING COMPANY
<br /> SD-310 SUPPLY AIR TITUS TDC 24�24 9�9 .04 10 11 175 NOTE 1,2,10,� � Tenant: BOEIIVG COMPANY
<br /> SD-311 SUPPLY AIR TITUS TDC 24/24 12/12 NOTE 1,2 App.Date: 6/15/ZO18
<br /> Praposed Use: MFG
<br /> Qescriptian: (NSTALLFLQORMOUNTA/CUNITONFAN
<br /> � SD-312 SUPPLY AIR TITUS TDC 24/24 12/12 NOTE 1,2,5
<br /> FILTER&SUPP�RTIN6 MECH
<br /> SD-313 SUPPLY AIR TITUS TBD-30 2 SLOT 6 NOTE 2,8 �� i
<br /> Reviewed ey: r��J" ` �ate�� I� 1�
<br /> SD-314 SUPPLY AIR TITUS ML-38 2 SLOT 6 NOTE 3,8
<br /> �"�OfFice Set lola Site et Fire/Planning Set
<br /> i
<br /> SD-315 SUPPLY AIR TITUS TDC 24/24 18/18 NOTE 1,2 �� ��
<br /> .� �� ��.��
<br /> ER-212 EXHAUST AIR TITUS 25RL 10/8 8/6 .10 -- 13 140 -- �� � �
<br /> ER-213 EXHAUST AIR TITUS 25RL 10/10 8/8 .07 -- 0 170 -- (�,.� R O U P
<br /> � ER-214 EXHAUST AIR TITUS 25RL 8/8 6/6 .04 -- 0 50 -- 600 Stewart St., Ste 1400
<br /> Seattie, Washington 98101 �
<br /> ER-215 EXHAUST AIR TITUS 23MRS 24/12 22/10 .06 -- 13 372 -- � FC SU BM ITTAL
<br /> Tel 206.267.1700
<br /> ER-216 EXHAUST AIR TITUS 25RL 12/10 10/8 .09 -- 17 250 -- Fax 206.267.1701
<br /> 01 .31 . 18
<br /> SAZAN # 500-1786
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE
<br /> ti E. L�� THIS DESIGN AND/OR CHECKED GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE W2572915 K o� .3� .18
<br /> K IRC - WBS 2.2.3.4.2 LSAM PRINTER INSTALLATION W2572915 SAZAN/GB 01.31.18 E NEW WORKSTATIONS 56673400 MH DH FB 06.27.06 �, oF wAs,�r �
<br /> �Q��' , �� O SPECIFICATION IS APPROVED SHEET
<br /> U � � � ER TITLE
<br /> F IRC REALIGNMENT 56824502 JM FB 03.26.07 � �' , `� �� �,1�'�' APPROVED BY DEPT. DATE IRC - WBS 2.2.3.4.2 LSAM PRINTER INSTALLATION
<br /> � BOE,�� � < ....�� �`���>..' ;,3..1� �.: �e. CHECKED 1 Y 1� 1 �
<br /> B ESRC NORTH PHASE 110976-10 JSM 05.24.02 G DATA CLOSEf AT COL E-6.1 575747-00 LMS DH FB 04.04.07 � 3,85� •
<br /> ����ISTEK��� APPROVED B U I L D I N G 40-056 JOB N0. COMP N0.
<br /> C ESRC OFFICE REQUIREMENTS 546338-00 JSM FB BOC 11.01.04 H HIGH DENSITY OFFICE 57692400 JM DH/FB 02.22.08 SlorraL�' W2572915
<br /> D EDRC TRAINING ROOMS 556746-00 LMS DH FB 10.14.05 J IRC - WBS 2.2.3.4.2 ADDITIVE MANUFACTURING W2572915 SAZAN/GB 10.26.16 01/30/2018 APPROVED MECHANICAL MASTER EVERETf, I�IA °wc No. 40-056-M2-14