Laserfiche WebLink
i MAF,- 9-9� 1,911 4::6 FM ti::roh :DC. F % ti0. 425 40-7-3..: <br />InC. • Medical Gases • Medical Gas Line Verifications • Analgesia Equipment <br />565 <br />+++ MEDICAL GAB LINE VERIFICATION +++ <br />3 MARCH 1999 <br />CONTRACTOR: MCKINSTRY CONSTRUCTION COMPANY <br />DATE / TIME OF TESTING: 22 FEBRUARY 1999 1 4:00 P.M. <br />FACILITY: EVERETT CLINIC SURGERY CENTER <br />AREA: ENDOSCOPY TREATMENT ROOMS 1159A & 163A <br />VACUUM OUTLETS ADDED IN ROOMS. <br />i. VACUUM IS IN COMPLIANCE WITH NFPA 99 (1996ed.). <br />A. MEDICAL VACUUM MEETS OR EXCEEDS MINIMUM FLOWS <br />AND VACUUM LEVELS. <br />II. MEDICAL VACUUM: <br />1. STATIC VACUUM LEVEL: 22"H9. <br />2. DYNAMIC FREE FLAW: > 3.0 SCFM. <br />3. DELTA FLAW - PASS. <br />III. OUTLET BRAND: "MEDAES" - QUICK CONNECT <br />IV. • ZONE VALVE: "MEDAES" WITH DOWN LINE GAUGE. <br />(EXISTING) <br />V. ALARM BRAND: "MEDAES" NOT TESTED - EXISTING <br />VI. BRAZIER: MIKE BIRD - I XXX-XX-2368 <br />VII. WITNESS: DAN CLARK - MAINTENANCE MANGER <br />VIII. COMMENTS: <br />A. NFPA 99 /4-1.4 - AN EXISTING SYSTEM THAT I8 NOT <br />IN STRICT COMPLIANCE WITH THE PROVISIONS OF THIS <br />STANDARD SHALL BE PERMITTED TO BE CONTINUED IN USE AS <br />LONG AS THE AUTHORITY RAVING JDRISDICTION HAS <br />DETERMINED THAT SUCH USE DOES NOT CONSTITUTE A DISTINCT <br />HAZARD TO LIFE. <br />ECS2-22.99 P9 1 of 2 (D D <br />r]� 2706 164th Street S.W., Lynnwood. 98037 ��l <br />l�`'Jll ff7711//�aLhhu��� (42S) 741.8807 1.800.736.7047 Fax:x:(425) 74 i•2500 ...AR 1 010 <br />CITY OF EVERETT <br />Permit Services <br />