Laserfiche WebLink
Essential Process Engineering <br /> PRESSURE RELIEF VALVE SUMMARY: <br /> Collection Vessel — Required Flow Rate: 194.11 CFM (See calculation on page Al2)_ <br /> 1 PRV installed—Maximum Flow Rate: 54.3 SCFM <br /> 4 PRV's of this type are required to be installed for the Collection Vessel. <br /> 217 CFM 4 Installed PRVs are adequate. <br /> Material Vessel —Required Flow Rate: 180.07 CFM (See calculation on page A13). <br /> 1 PRV installed—Maximum Flow Rate: 54.3 SCFM <br /> 4 PRV's of this type are required to be installed for the Collection Vessel. <br /> 217 CFM 4 Installed PRVs are adequate. <br /> **Multiple JW-LOK RV1 Type PRV's are needed <br /> 5/3/2016 Project: 1604141_BrianKnopf_Extractor Page 23 of 34 <br /> EPE Doc. 160414ER Confidential- Proprietary Document Butane USE ONLY <br />