GE.0110DESIGN FIELD REPORT <br /> 1.--of-3- <br /> . <br /> Project Name: I Everett River Front-Simpson Report: 102 <br /> GeoDesign#: i Polygon-127-03 _ Date: 3/14/2018 <br /> Reports with Unresolved Nonconformance Issues: Permit: <br /> PW 1505-005 <br /> Nick Abdelnour(Polygon) l Randy Allen(City of Everett) Weather: Clear, 50's <br /> Ron Bowen(Polygon) ! Eddy Stevens(Polygon) Arrival/Departure: 1515/1545 <br /> Distribution: —_...... — .—... — , — .... __ <br /> Doug Ross(Polygon) I Kirk Keck(City of Everett) <br /> i Paul McKee(City of Everett) I Dave Foster(City of Everett) Prepared By Ben Weinberg EIT <br /> Attachments: m Site Plan(s) ® ._Density Test Summary ( Signature: 4• <br /> �❑ Installation Records 0 Other i Reviewed By: <br /> PURPOSE of VISIT: GeoDesign representative, Ben Weinberg, was on-site part time at the request of Craig with DDS to <br /> observe foundation subgrade for Lots 155 and 156. <br /> SUMMARY OF OBSERVATIONS: <br /> Lot 155: <br /> Today, GeoDesign noted that DDS had completed excavation of the footing and crawl space area for Lot 155. The exposed <br /> footing subgrade soil generally consisted of a gray-brown to brown silty SAND with gravel that could be probed generally <br /> less than 2 inches using a 1/2 inch diameter soil probe. Relative compaction of the footing subgrade soils was tested using <br /> a Troxler Moisture-Density gauge; in-place density tests indicated that material had been compacted to greater than 95%of <br /> its maximum dry density as determined by a Modified Proctor analysis. <br /> It is the opinion of GeoDesign that exposed foundation subgrade observed today is currently suitable for support of the <br /> intended structure. GeoDesign recommends that any surficially loose and saturated material that may be generated be <br /> removed from the base of foundation areas prior to the placement of concrete. <br /> Lot 156: <br /> Today, GeoDesign noted that DDS had completed excavation of the footing and crawl space area for Lot 156. The exposed <br /> footing subgrade soil generally consisted of a gray-brown to brown silty SAND with gravel that could be probed generally <br /> less than 2 inches using a 1/2 inch diameter soil probe. Relative compaction of the footing subgrade soils was tested using <br /> a Troxler Moisture-Density gauge; in-place density tests indicated that material had been compacted to greater than 95%of <br /> its maximum dry density as determined by a Modified Proctor analysis. <br /> It is the opinion of GeoDesign that exposed foundation subgrade observed today is currently suitable for support of the <br /> intended structure. GeoDesign recommends that any surficially loose and saturated material that may be generated be <br /> removed from the base of foundation areas prior to the placement of concrete. <br /> A summary of observations and density tests taken can be found in the attached Figure 1 and Nuclear Density Gauge Data. <br /> The contractor was notified of our observations prior to our departure from the site today. <br /> This report presents opinions formed as a result of our observation of activities relating to geotechnical engineering or environmental services.We rely on the contractor to comply with the plans and <br /> specifications throughout the duration of the project irrespective of the presence of our representative.Our work does not indude supervision or direction of the contractor,the contractor's employees <br /> or agents. Our firm is not responsible for site safety.This field report is a DRAFT representation of our field observations,testing,and preliminary recommendations.The report can only be considered -. <br /> final upon review of the GeoDesign project manager,as indicated by initials in the"Reviewed By"section. <br /> 10700 Meridian Avenue North,Suite 402 I Seattle,WA 98133 I 206.838.9900 <br /> /P <br /> 2502 Jefferson Avenue I Tacoma,WA 98402 I 253.203.0095 <br />
The URL can be used to link to this page
Your browser does not support the video tag.