G. Exhaust Duct System (506.3.4): DESIGN MINIMUM 500 FEET PER MINUTE <br /> 1. Applicant shall provide the specified air velocity in exhaust duct. <br /> 2. Duct Size /3 in. X 13 in., duct area = in. X in. _ 1//7 ft2 <br /> 144 <br /> Type of Proposed <br /> Hood Air Velocity(FPM) CFM/Duct Area (ft2) Air Velocity <br /> 1. Type I Req. 500 to recom. 2500 /62°u / /, / 7 _ /53 FPM <br /> Type II Req. min 500 CFM / = FPM <br /> 2. Static Pressure Loss <br /> Duct L LS in. + grease filters/extractor e 5 in. + other in. =Total s 75 In. of H2O <br /> 3. Fan and motor shall be of sufficient capacity to provide the required air movement. Fan motor shall <br /> not be installed within ducts or under hood. <br /> Fan make and model 7�,,✓41't A`4,1-- DV 6S /:' HP 3� e <br /> Static pressure _i75 in. at ZZu G CFM. <br /> Note: If using a listed duct wrap, provide manufacturer's installation instructions and listing documents. <br /> H. Exhaust Outlet Location (506.3.13): <br /> Minimum <br /> Exhaust Outlet Location Required Proposed <br /> Type I 40 in. � fi'` <br /> Exhaust outlet shall terminate above roof Type II 30 in. <br /> Type I 10 ft. CU <br /> Distance from same or adjacent building Type II 30 in. <br /> Type I `� / <br /> Distance above adjoining grade Type II 10 ft. 6 <br /> Type I <br /> Distance from property line Type II 10 ft. lb <br /> Type I 10 ft. e <br /> Distance from windows and doors Type II 3 ft <br /> Type I ✓e. P <br /> Distance from mechanical air intake Type Il 10 ft. <br /> OS)ter_ <br />