_ _ _ _ _ _ __ <br /> � <br /> � � <br /> , � ME��IA�lICAL �QUIPMENT SCHEDULE �-� <br /> EQUIPMENT ON PANEL EQUIPMENT VOLTAGE PHASE HP KW FL.A MOCP BRANCH CIRCUIT DISCONNECT NOTES � <br /> ' TAG DWG ITEM RACEWAY PHASE N G SIZE FUSE �'� <br /> , �,, <br /> AHU-OA4 E4.2 OEH-3A-1,3,5 ROOFTOP AIR HANDLING UNIT 480 3 - - 46.3 50 1-114° 3#4 - 1#8 - 100 NOTE 1 3 � <br /> .,� <br /> � <br /> � �� � � <br /> AC-07 E4.'f OEP-3A-13,15 SPLIT SYSTEM AIR CONDITIONWG 208 1 - - 0.33 - 3/4° �: 2#12 - 1#12 30 I�lOTE 1 2,3 <br /> Z��3� i-�Cv4�E�Ft�.C{� ,4Vt <br /> ' CU-07 E4.2 OEP-3A-13,15 . SPLIT �YSTEM AIR CC�NDITIONING 208 1 - - 12 20 314" 2#12 - 1#12 30 NOTE 1 3 �`�=`���r� '''''�` ���'r�� <br /> � P��OiJr: ��1� �1?.��17 � <br /> CU-08 E4.2 OEH-3A-7,9,11 SP�IT SYSTEM AIR CONDITIONWG 480 3 > - - 55 80 1-1/2" 3#2 - 1#6 100 NOTE 1 3 F�;�; �r�� ;;t�_g��g <br /> EF-14 �4.2 OP3A-1 EXHAUST FAN 120 1 1/4 - 5.8 - 3/4" 1#12 1#12 1#12 - - 4 � ^ R � ) � <br /> EF-15 E4.2 OP3A-3 EXHAUST FAN 120 1 1/4 - �,8 - 3/4" 1#12 1#12 1#12 - - 4 <br /> Hargis Engineers, Inc. <br /> 1201 Third Avenue, Suite 640 <br /> FTU-13 E4.1 OEH-3A-2 FAN TERMINAL JNIT 277 1 1/5 - 5.8 - 3/4" ` 1#12 1#12 1#12 30 NOTE 1 3 Seattle,WA98101 <br /> FTU-14 E4.1 OEH-3A-6 FAN TERMINAL UNIT 277 1 1/3 - 5.8 - 3/4° 1#12 1#12 1#12 30 NOTE 1 3 t� 206.448.3376 <br /> - f� 206.448.4450 <br /> ; FTU-15 E4.1 OEH-3A-6 FAN TERMINAL UNIT 277 1 1/20 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 w� hargis.biz <br /> _ FTU-16 E4.1 OEH-3A-6 FAN TERMINAL UNIT 277 1 1/8 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 <br /> FTU-17 E4.1 OEH-3A-6 FAN TERMINAL UNIT 277 1 1/6 - 5.8 - 3/4° 1#12 1#12 1#12 30 NOTE 1 3 <br /> FTU-18 E4.1 OEH-3A-4 FAN TERMINAL UNIT 277 1 1/8 - 3.1 - 3/4° 1#12 1#12 1#12 30 NOTE 1 3 �" ``+��� <br /> �`� „� � <br /> FTU-19 E4.1 OEH-3A-4 FAN TERMINAL UNIT ' 277 1 1i8 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 ��� ' � `- <br /> �� , 1. � � '.. <br /> FTU-20 E4.1 OEH-3A-4 FAN TERMINAL UNIT 277 1 1/20 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 ��' ��� � <br /> �---�_-�-- �, ,�.,� <br /> A�R � <br /> FTU-21 E4.1 OEH-3A-4 FAN TERMINAL UNIT 277 1 1/15 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 �. <br /> I FTU-22 E4.1 OEH-3A-4 FAN TERMINAL UNIT 277 1 1/20 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 <br /> FTU-23 E4.1 OEH-3A-4 FAN TERMINAL UNIT 277 1 1/20 - 3.1 - 3/4° 1#12 1#12 1#12 30 NOTE 1 3 <br /> . J <br /> FTU-24 E4.1 OEH-3A-4 FAN TERIVIINAL UNIT 277 1 1/20 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 �C <br /> FTU-25 E4.1 OEH-3A-2 FAN TERMINAL UNIT 277 1 1/4 - 5.8 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 1--+ <br /> FTU-26 E4.1 OEH-3A-2 FAN TERMINAL UNIT 277 1 1/3 - 5.8 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 z m w <br /> � � <br /> FTU-27 E4.1 OEH-3A-2 FAN TERMINAL UNIT 277 1 1/3 - 5.8 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 � � E; <br /> FTU-28 E4.1 OEH-3A-2 FAN TERMINAL UNIT 277 1 1/15 - 3.1 - 3/4" 1#12 1#12 1#12 30 NOTE 1 3 j z � <br /> � w <br /> oC u aw. <br /> EWG1 E4.1 CONNECT TO EXISTING DRINKING FOUNTAIN 120 1 - - ' - 3/4" 1#12 1#12 1#12 - - 3 - <br /> � <br /> IH-1 E4.1 OP3A-36 INSTA-HOT 120 1 - - 6.25 - 3/4" 1#12 1#12 1#12 - - 3,4 � � <br /> _ - ua '� `� <br /> a � � <br /> , NOTES � d- i.�rs <br /> 1. SIZE FUSES PER EQUIPMENT MANUFAC'�URER'S RECOMMENDATION. O <br /> 2. INDOOR UNIT POWERED FROM OUTDOOR UNIT z <br /> 3. MAKE EQUIPMENT CONNECTION <br /> 4. PROVIDE MOTOR RATED TOGGLE SWITCH. - <br /> �� ` � MECHANICAL EQUIPI'VI��IT SCHE�ULE � <br /> . � Ea.4 SCALE: NONE r � <br /> C� I- � . <br /> � � 4! 1 <br /> H W <br /> � � � � <br /> � � � <br /> _ Z Z � � W � <br /> _ a � � o c� � <br /> - � � � �� <br /> . - _ °� � � 4J 1 <br /> = 0 ,z <br /> , - 0 � � T �,.�I <br /> , � ' O � I"'� � <br /> � � H � W <br /> - WIREMOLD > <br /> - RACEWAY Q ~ r " <br /> = _ • � (� �"�'°� <br /> = W (,!� N <br /> - _ CL � o <br /> : O � � <br /> NOTES; � �I <br /> 1. PROVIDE (1) CABLE SPILLWAY DEVICE ABOVE EACH <br /> = - = ENCLOSURE AND ATTACH TO PER MANUFACTURER <br /> � = UNI-STRUT TRAPEZE SPECIFICATIONS. <br /> = = SUPPORT BRACKET <br /> � � = (TYP RS NECESSARY) 2. ALL TRAY SECTIONS SHALL BE BONDED TOGETHER <br /> , THREADED ROD = _ ° USING #6 AWG BONDING STRAPS OR EQUIVALENT. SHEET TITLE: <br /> TO STRUCTURE (TYP) � � MECHANICP►L EQUIPME(�T <br /> , - 3. SEE ELECTRICAL DRAWINGS FOR EXACT <br /> RECEPTACLE TYPES, LOCATIONS AND QUANTITIES. SCHEDULE <br /> CABLE TRAY � <br /> � • Q 9 <br /> o � . <br /> = o • <br /> _ , <br /> = DATE: 04/08/16 <br /> � • JOB NO. : 14008 <br /> • a P� <br /> ONE INCH AT FULL SCALE. <br /> . <br /> `' IF NOT, SCALE ACCORDINGLY <br /> MOUNTING BRACKETS AS � • Qo � 2 �ETAIL _ RA�K MOU�TED �� V IC�S �` <br /> �� SHEET: <br /> NECESSARY FOR O ' E0.4 SCALE: NONE <br /> WIREMOLD WSTALLATION <br /> ■ <br /> , - <br /> � SHEET 59 OF 95 <br /> i - � <br />