Laserfiche WebLink
� c� <br /> Steve Mfller __ <br /> From: Steve Miller <br /> Sent: Monday,August 10,2009 17:52 AM <br /> To: 'feliciano.mangulabnan(c�bnharch.com' <br /> �; 'bnh(�bnharch.com' <br /> Subject: 2112 Rucker <br /> Felix, <br /> Preliminary plan review suggests attention to the following; <br /> 1. Smoke detectors should be indicated in accordance with IBC 907.2.10.1 <br /> 2. Fire-resistant construction is required at Flr./clgs. In accordance with IBC 711.Provide the assembly details and <br /> testing agency I.D. numbers for all rated assemblies. <br /> 3. Fire-resistant construction is requfred for the walls,beams,and columns supporting horizontal assemblies(13C <br /> 711.4). <br /> 4. All fans should be shown on the plans in accordance with the 2006 VIAQ. <br /> 5. Fans penetrating the ceiling of roted horizontal assemblies must comply with IBC 716.6.2. <br /> 6. Walls separatfng units must compiy with IBC 708.3. <br /> 7. Walls and floors between units are required to have a min.STC rating of 50 in accordance with IBC 1207. <br /> 8. Storage rooms are required to be protected in accordance with IBC 413. <br /> 9. Calculations,species,and grede will be required for all beams. <br /> 10. RCW 64.55 <br /> Thank You,Steve <br /> 1 <br />