5(or)e g 5 co* 1 e n I ko x AC <br /> 5006088-CTG-C-0716 <br /> PHYSICAL AND ELECTRICAL DATA <br /> MODEL TW4B1821S TW4B2421S TW4B3021S TW4B36215 TW4B4221S TW4B4821S TW4B6021S <br /> Unit Supply Voltage 208-230V,14),60Hz <br /> Normal Voltage Range 1 187 to 252 <br /> Minimum Circuit Ampacity 11.8 13.6 17.6 20.5 22.1 25.7 31.7 <br /> _ <br /> Max.Overcurrent Device Amps 2 20 20 30 35 35 45 50 <br /> Min.Overcurrent Device Amps 3 15 15 20 25 25 30 35 <br /> Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll <br /> Compressor Rated Load 9.0 10.2 13.4 15.4 16.6 19.5 24.3 <br /> Amps Locked Rotor 56.3 61.6 72.5 83.9 109.0 130.0 144.2 <br /> Crankcase Heater No No No No No No No <br /> Factory External Discharge Muffler No No No No No No No <br /> HS Kit Required with TXV 4 No No No No No No No <br /> Fan Diameter Inches 18 22 22 22 w 24 24 26 <br /> Rated HP 1/12 1/8 1/8 1/4 1/4 1/4 1/4 <br /> Fan Motor Rated Load Amps 0.64 0.80 0.80 1.3 1.3 1.3 1.3 <br /> Nominal RPM 1000 1075 1075 850 850 850 850 <br /> Nominal CFM 1900 2875 2950 3275 3500 3500 4300 <br /> Face Area Sq.Ft. 12.37 13.83 13.83 17.37 18.74 18.74 23.40 <br /> Coil Rows Deep 1 1 1 1 1 1 1 <br /> Fins/Inch 23 23 23 23 23 23 23 <br /> Liquid Line Set OD(Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 <br /> Vapor Line Set OD(Field Installed)5 3/4 3/4 3/4 3/4 7/8 7/8 1-1/8t <br /> Unit Charge(Lbs.-Oz.)6 3-6 3-12 3-15 4-10 4-15 4-15 5-12 <br /> Charge Per Foot,Oz. 0.62 0.62 0.62 0.62 0.67 0.67 0.75 <br /> Operating Weight Lbs. 130 135 140 155 T 200 200 205 <br /> 1. Rated in accordance with AHRI Standard 110-2012,utilization range A. <br /> 2. Dual element fuses or HACR circuit breaker.Maximum allowable overcurrent protection. <br /> 3. Dual element fuses or HACR circuit breaker.Minimum recommended overcurrent protection. <br /> 4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model. <br /> 5. For applications with non-standard vapor line sizes,see the"Applications&Accessories"section of this Technical Guide. <br /> 6. The Unit Charge Is correct for the outdoor unit,smallest matched indoor unit,and 15 feet of refrigerant tubing.For tubing lengths other than 15 feet,add or subtract <br /> the amount of refrigerant,using the difference in actual Ilneset length(not equivalent length)multiplied by the per foot value. <br /> --.tf,..._., c DIMENSIONS <br /> � <br /> `tif"` `"" *" "� '"""j4 ► Unit Dimensions Refrigerant Connection <br /> (Inches) Service Valve Size <br /> _ �:- .,.----- I-'- Model <br /> �, - .: A B C Liquid Vapor <br /> +�.* ,---.7,011,X1 <br /> +„`-w -•'" � TW4B1821S 33-114 W 24 24 <br /> =+ .e ,tzi TW4B2421S 30 29-114 29-1/4 <br /> --Z$t ZTI TW4B3021S 30 29-1/4 29-1/4 314 <br /> A ,...-......01,:V.•'+ TW4B3621S 36-1/4 29-1/4 29-1/4 3/8 <br /> E ;, - -" `'�,• _ TW4B4221S 33-1/4 35-1/4 31-3/4 <br /> 4•7: z..' '^ - TW4B4821S 33-1/4 35-1/4 31-3/4 , 7/8 <br /> ,�„ ..;,� ry TW4B6021S 36-1/4 38 34-1/4 7/8 <br /> ry .,....0.., y ......... `? $Adapter fitting must be field Installed for the required 1-1/B"line set. <br /> "''e+ •!.', !+r ,. Nr All dimensions are In inches and are subject to change without notice. <br /> ':•z:b. -B Overall height Is from bottom of base pan to top of fan guard. <br /> w A0119401 Overall length and width include screw heads. <br /> Johnson Controls Unitary Products 3 <br />