Building Permit Plans Checklist, pg. 1 ENV-CHK
<br /> 2015 WSEC Compliance Forms for Commercial Buildings including R2,R3,&R4 over 3 stories and all R1 Revised Jun 2016
<br /> Project Title: Enhanced Servicess Facility(ESF)+Retail Date 10/04/2017
<br /> The following information is necessary to check a building permit application for compliance with the building envelope requirements in the Washington State Energy
<br /> Code,Commercial Provisions.
<br /> Applicability Code Location in Building
<br /> (yes,no,na) Section Component Compliance information required in permit documents Documents Department Notes
<br /> SCOPE
<br /> Low energy spaces are identified on plans;include project information,and
<br /> na C402.1.1 Low energy spaces calculations if applicable,that demonstrate spaces are eligible for envelope
<br /> provisions exemption
<br /> na C402.1.1.1 Semi-heated spaces Semi-heated spaces are identified on plans,include calculations that
<br /> demonstrate spaces are eligible for wall insulation exemption
<br /> Provide building area,average wall and roof U-factor,and installed
<br /> na C402.1.2 Equipment Buildings equipment information that demonstrates equipment building is eligible for
<br /> envelope provision exemption
<br /> Walk-in and Cooler and freezer spaces are identified on plans;C410 envelope
<br /> na C410.2 warehouse cooler compliance forms provided(pending)
<br /> and freezer spaces
<br /> na C101.4.1 Mixed occupancy Spaces with different occupancy requirements are identified on plans
<br /> Existing unconditioned spaces changing to semi-heated or conditioned
<br /> na C503.2 Change of space space,and existing semi-heated spaces changing to conditioned space,are
<br /> conditioning identified on plans.Include calculations that demonstrate baseline and final
<br /> level of conditioning.
<br /> Existing F,S and U-occupancy spaces undergoing a change in occupancy
<br /> are indicated on plans;include calculations that demonstrate upgrade
<br /> complies with the current WSEC.
<br /> Change of Pre-2002 Group R spaces undergoing a change to a commercial
<br /> na C505.1 occupancy are indicated on plans;include calculations that demonstrate
<br /> occupancy
<br /> upgrade complies with the current WSEC.
<br /> Non-Group R occupancy spaces undergoing a change to Group R are
<br /> indicated on plans;include calculations that demonstrate upgrade complies
<br /> with the current WSEC.
<br /> ENVELOPE PROVISIONS
<br /> Indicate envelope insulation compliance path and provide applicable forms; Delta 2
<br /> yes C103.2 Compliance ENV-PRESCRIPTIVE or ENV-UA/ENV-SHGC for component performance Correction
<br /> C103.6.3 documentation Response
<br /> If complying via total buidling performance,provide a list of all proposed
<br /> envelope component types,areas and U-values Package
<br /> C303.1.1 Insulation Indicate identification mark shall be applied to all insulation materials and
<br /> yes insulation installed such that the mark is readily observable during A601,A603,A605,
<br /> C303.1.2 identification inspection A611,A613
<br /> yes C303.1.3 Fenestration product Fenestration products shall be labeled with rated U-factor,SHGC,VT,and
<br /> C402.4.3 rating leakage rating A705
<br /> Indicate installation methods,thicknesses,densities and clearances to
<br /> yes C303.1.1 General insulation achieve the intended R-value of all insulation materials;
<br /> C402.2.1 installation Where two or more layers of rigid insulation will be used,indicate that edge A601,A603,A605,
<br /> joints between layers are staggered A611,A613
<br /> Indicate R-value(s)of cavity/continuous insulation on roof sections;
<br /> Indicate framing materials on roof sections;
<br /> Indicate method of framing for ceilings below vented attics and vaulted
<br /> ceilings perA102.2(std,adv);
<br /> yes C103.2 Roof assembly Provide area weighted average U-factor calculation for insulation whose
<br /> C402.2.2 insulation thickness varies by 1 inch or less;
<br /> Indicate effective U-factors of tapered insulation entirely above deck per
<br /> A102.2.6;include roof configuration and slope,maximum R-value at peak A401,A403,A421,
<br /> and minimum R-value at low point for all roof surfaces A423,A601,A603,
<br /> Indicate R-values for thermal spacers and each insulation layer,and liner A605,A611,
<br /> system(LS)method for metal building roofs NOTES
<br /> na C402.2.2 Skylight curb Indicate curb insulation R-value on roof section if not included in skylight
<br /> insulation NFRC rating
<br /> Indicate R-value(s)of cavity/continuous insulation on wall sections;
<br /> Indicate framing materials on wall sections;
<br /> Indicate method of framing for wood const per A103.2(std,int,adv);
<br /> C103.2 Indicate material density category,wall weight and heat capacity for
<br /> C402.2.3 Above/below grade
<br /> yes C402.2.4 wall insulation qualifying mass walls;
<br /> C303.2.1 For qualifying ASTM C90 masonry walls,indicate loose-fill core insulation
<br /> material and percentage of cores filled including grouted cores,bond
<br /> beams,vertical fills,headers and any other grouted cores; A601,A603,
<br /> Indicate method of protection of exposed exterior basement/crawlspace wall A605,A611,
<br /> insulation NOTES