Laserfiche WebLink
Below are the responses for letter sent to Mr. Madison dated 4/4/17 regarding <br /> questions/comments by Jim Venturo, Assistant Fore Marshall. <br /> On the drawing sheets the corrections are clouded and labeled as Delta 6. Also included in this <br /> packet are the responses of the various consultants on this project. <br /> Thank you. <br /> Comment#2. Reply: A Knox Box, box#3270, is to be ordered at www.everettfire.org. Refer to <br /> sheets A201 and A303, and Spec 108013. <br /> Comment#3. Reply: Refer to Civil Plan Set under a separate submission. Order cap #3043 (2) at <br /> www.everettfire.org. <br /> Comment#9. Reply: <br /> Ground Floor: Portable fire extinguishers with a minimum U. L. rating of 3A-40B:C shall be <br /> provided within 75 ft. of travel on the ground floor during construction and prior to occupancy. <br /> First Floor: Portable fire extinguisher with a minimum U. L. rating of 2A-10B:C shall be provided <br /> within 75 ft. of travel on the first floor during construction and prior to occupancy. Refer to <br /> sheet A005 and Spec 104410. <br /> Comment#16: Reply: Note has been added to the SPEC set to address this request: Ground <br /> Floor in the drawing set shall have signage FLOOR 1, and first floor(residential floor) will have <br /> signage FLOOR 2. Refer to Spec 101400. <br /> If there are any questions or concerns with the responses to any of the corrections please let us <br /> know. <br /> Regards, <br /> Marc Jenefsky <br /> Principal Architect <br /> Bazan Architects <br /> 2000 116th Avenue NE <br /> Bellevue, WA 98004 <br /> Project No. 3014594 and 6324483 Page 2 of 2 Bazan Architects <br />