<br /> . V� l�a L AI V�LIJ � � � INAL lJ � l�' (V/�V) �h� IJL� F N ��HEDULE
<br /> PRIMARY PRIMARY PRIMARY ELECTRIC COIL
<br /> AIRFLOW AIRFLOW AIR MAX. INLET UNIT UNIT DRIVE ESP SOUND MOTOR WEIGHT
<br /> UNIT UNIT LEVEL SERVED BY FAN VALVE VALVE PRESSURE NC SIZE FAN V/PH MANUFACTURER MODEL NOTES LOCATION FAN
<br /> HP NO SERVICE FAN TYPE TYPE CFM IN WG SONES RPM BHP LBS BASIS OF DESIGN NOTES
<br /> NO. LOCATION CFM MAXIMU�1 MINIMUM �ROP LEVE (IN) KW S7AGE � � �� ��, � PM HP VOLT PH
<br /> CFM CFM (INCH WG)
<br /> VAV-03-03 1-A.75/2.70 LEVEL-1 ACU-03 640 600 240 0.5 30 8 1/3 �.0 1 277/1 PRICE FDCA2 1,2,3, 4 � EF-71 RF-8.25/2.0 WASTE ACCUMULATION AREA UPBLAST ROOF BELT 880 1.5 14 1725 0.56 1725 3/4 208/3 115 GREENHECK/CUE-131-A 2, 3, ,6, 10, 13, 14
<br /> � VAV-03-04 1-B.5/2.30 LEVEL-1 ACU-03 1160 700 280 0.5 30 8 1/3 1.8 1 277/1 PRICE FDCA2 1,2,3, 4 �
<br /> VAV-03-05 1-B.75/2.30 LEVEL-1 ACU-03 1160 700 2�0 0.5 30 8 1/3 1.8 9 277/1 PRICE FDCA2 1,2,3, 4
<br /> OF-01 1-8.5/3.5 SPAR TRIM & DRIL.L PIT OSCILLATING WALL MOUNT DIRECT 7525 - 13 - - - 1/4 120/1 36 GLOBAL 607050 4, 12
<br /> VAV-03-06 � �1-B.25/2.70 LEVEL-1 CU- 3 1400 850 340 0.5 30 10 314 2.2 1 277/1 PRICE FDCA2 2,3, 4
<br /> ^ � OF-02 1-B.5/3.75 SPAR TRIM & DRILL PIT OSCILLATING WALL MOUNT DIRECT 7525 - 13 - - - 1!4 120/1 36 GLOBAL 607050 4, 12
<br /> VAV-03-07 1-B.25/2.70 LEVEL-1 ACU-03 800 250 100 0.5 30 10 3/4 1.2 1 277/1 PRICE FDCA2 1,2,3, 4 OF-03 1-Cl3.5 SPAR TRIM & DRILL PIT OSCILLATING WALL MOUNT DIRECT 7525 - 13 - - - 1/4 120/1 36 GLOBAL 607050 4, 12
<br /> � VAV-03-08 1-B/2.30 LEVEL-1 ACU-03 1600 1600 640 0.5 30 12 3/4 4.5 2 480/3 PRICE FDCA2 1,2,3, 4 OF-04 1-C/3.75 SPAR TRIM & DRILL PIT OSCfLLATING WALL MOUNT DIRECT 7525 - 13 - - - 1/4 120/1 36 GLOBAL 607050 4, 12 �
<br /> VAV-03-09 1-Bl2.30 LEVEL-1 ACU-03 1600 1600 640 0.5 30 12 3/4 4.5 2 480/3 f'RICE FDCA2 1,2,3, 4
<br /> � �.J--.� w-
<br /> VAV-06-01 1-D.5/2.30 LEVEL-1 ACU-06 1200 9200 490 0.5 30 12 3/4 1.9 1 277/1 PRICE FDCA2 1,2,3,4 � OF-05 1-G.5/3.5 PANEL TRIM & DRILL PIT OSCILLATING WALL MOUNT DIRECT 7525 - 13 - - - 1/4 120/1 36 GLOBAL 607050 4, 12
<br /> VAV-06-02 1-D.25/2.30 LEVEL-1 ACU-06 1200 1200 490 0.5 30 12 3/4 1.9 1 277/1 PRICE FDCA2 1,2,3, 4 OF-06 1-H/3.5 PANEL TRIM & DRILL PIT OSCILLAI'ING WALL MOUNT DIRECT 7525 - 13 - - - 1/4 120/1 36 GLOBAL 607050 4, 12
<br /> , ,
<br /> VAV-06-03 1-D.15/2.30 LEVEL-1 CU- 6 1200 1200 90 0.5 30 12 3/4 1,9 1 277f/1. PRICE FDCA2 2,3, 4 NOTES:
<br /> VAV-06-05 1-D.5/2.30 LEVEL-1 ACU-06 70 50 20 0.5 30 6 1/3 0.5 1 277/1 PRICE FDCA2 1,2,3, 4 1. VFD PR(7VIDED BY DIVISION 26.
<br /> 2. CONTROLL�D FROM BUILDING MANAGEMENT 5YSTEM PROVIDED UNDER DIVISION 23.
<br /> VAV-06-06 1-D.5/2.30 LEVEL-1 ACU-06 1300 1300 520 0.5 30 12 3/4 1.9 1 277/1 PRICE FDCA2 1,2,3, 4 5 3. DIVISION 23 SHALL FURNISH AN[7 MOUNT S7ARTER/H-O-A DISCONNECT. DIVISION 26 SHALL WIRE
<br /> STARTER/DISCONNECT.
<br /> � VAV-06-Q7 1-D.5/2.30 LEVEL-1 ACU-06 1200 1200 490 0.5 30 12 3/4 1.9 1 27711 PRICE FDCA2 1,2,3, 4 S 4. PROVIDE OSHA GUARD.
<br /> 5. PROVIDE PREMIUM EFFIGENCY MOTOR.
<br /> VAV-06-09 1-D.5/2.30 LEVEL-1 ACU-06 70 50 20 0.5 30 6 1/3 0.5 1 277/1 PRICE FDCA2 1,2,3, 4 6, PROVIDE BACKDRAFT DAMPER.
<br /> 7. PROVIDE SIDE MOUNTED MOTOR. -
<br /> t VAV-06-08 1-D.5/2.30 �.EVEL-1 ACU-06 170 160 65 0,5 30 6 1/3 0.5 1 277/1 PRICE FDCA2 1,2,3, 4 8. PROVIDE VIBRATION ISOLATORS.
<br /> 9. PROVIDE FILTER BOX.
<br /> VAV-06-10 1-D.5/2.30 LEVEL-1 ACU-06 170 160 65 0.5 30 6 1/3 0.5 1 277/1 PR(CE FDCA2 1,2,3, 4 '10. PROVIDE ALUMINUM WHEEL.
<br /> -�`� 11. PROVIDE PIEZOMETER AIRFLOW MONITORING RING AND INLET TAP FOR SUPPLY FAN. EXTEND SENSOR TUBES TO
<br /> � EXTERIOR OF UNIT CASING. TERM�NA7E WITH BRASS BARBS. •
<br /> 12. PROVIDE EL�CTRICAL CORD AND PLUG.
<br /> 13. PROVIDE EXPLOSION PROOF MOTOR.
<br /> 14. PROVIDE BELT TENSIONER.
<br /> VAV-12-01 1-F,75/2.3Q LEVEL-1 ACU-12 1200 1200 500 0.5 30 12 3/4 2.0 1 277/1 PRICE FDCA2 1,2,3, 4
<br /> VAV-12-02 1-G/2.30 LEVEL-1 ACU-12 1200 1200 500 0.5 30 12 3/4 2.0 1 277/1 PRICE FDCA2 1,2,3, 4
<br /> VAV-12-03 1-G/2.30 LEVEL-1 ACU-12 1600 300 120 0.5 30 6 1/3 2.5 1 277/1 PRICE FDCA2 1,2,3, 4
<br />� .
<br /> VAV-15-01 1-H.75/2.30 LEVEL-1 ACU-15 2860 1720 690 0.5 30 12 3/4 4.5 2 480/3 PRICE FDCA2 1,2,3, 4
<br /> VAV-15-02 1-J/2.30 LEVEL-1 ACU-15 2860 1720 690 0.5 30 12 3/4 4.5 2 480/3 PRICE FDCA2 1,2,3, 4
<br /> VAV-15-03 1-J.25/2.30 LEVEL-1 ACU-15 1600 990 400 0.5 30 10 3/4 2.5 1 277/1 PRICE FDCA2 1,2,3, 4
<br /> _ �.�..-. _ �
<br /> 5 VAV-15-05 1-H.50/2.30 LEVEL -1 ACU-15 1920 1150 460 0.5 � 30 12 3/4 2.0 1 277/1 PRICE FDCA2 1,2,3, 4
<br /> VAV-15-06 1-H.25/2.30 LEVEL-1 ACU-15 840 840 340 0.5 30 10 3/4 1.8 1 277/1 PRICE FDC 1,2,3, 4
<br /> ��
<br />� •
<br /> VAV-18-43 M1-K/2.4 M1 LEVEL ACU-18 840 840 225 0.5 30 10 1/2 2.7 1 277/1 PRICE FDC 1,2,3, 4 �,
<br /> NOTES:
<br /> 1. PROVIDE WITH ECM MOTOR,
<br /> 2. PROVIDE WITH FACE MOUNTED ELECTRICAL CONTF20LS ENCLOSURE.
<br /> 3. REFER TO SPECIFICATIONS FOR CONTROL REQUIREMENTS.
<br /> 4. PROVIDE TRANSFORMER TO 24V CON7ROL POWER.
<br />� .
<br /> �
<br /> VA �� L �1 R V LlJ M �T� I� i �IAL 1� IT (VAV) H U L
<br /> PRIMARY PRIMARY PF2IMARY HOT WATER HEATING COIL DATA
<br />� UNIT UNIT AIRFLOW AIRFLOW AIR MAX. INLET •
<br /> LEVEL SERVED BY FAN VALVE VALVE PRESSURE NC SIZE FAN V/PH MANUFACTURER MODEL NOTES
<br /> NO. LOCATION CFM HP EAT LAT EWT LWT PD
<br /> MAXIMUM MINIMUM DROP LEVEL (IN) MBH ROWS
<br /> CFM CFM (INCH WG) (�F) (°F) (°F) (°F) /GPM FT H20
<br /> VAV-18-42 M1-K.75/2.30 M1 LEVEL ACU-18 1230 1230 310 0.6 34 12 3/4 65 85 135 100 26.7 2/ 1.5 0.83 277/1 PRICE FDC 1,2,3,4
<br /> NOTES:
<br /> 1. PROVIDE WITH ECM MOTOR.
<br /> 2. PROVIDE WITH FACE MOUNTED ELECTRICAL CONTROLS ENCLOSURE. �
<br /> 3, F2EFER TO SPECIFICATIONS FOR CONTROL REQUIREMENTS.
<br /> 4. PROVIDE TRANSFORMER TO 24V CONTROL POWER.
<br />� .
<br /> Core & Shell
<br /> . . 'P�NG C�N
<br /> 1° ���' 0` Wnsy/ �F\� •
<br /> � � - �
<br /> Ja�e� in C�nl , r. � �
<br /> 09� 4 6- �(=8 ': T)
<br /> -o � ��
<br /> 900 SW 16th Street Suite 307 ���'Fss �ca� 6�e G��`�
<br /> Ren�on, Washington 98057 ��NA I c�
<br /> �
<br /> ¢
<br /> W A g ACCEPTABILITY DRAWN DATE SUBTITLF CURRENT REVISION SYMBOL DATE <,'�'>,
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE aF y R�,N 01126l16 �
<br /> 0 Issue For Construction RAN JLC 10120115 5 Revision-Release 35(TI) RAN JLC 01126/16 T`� /��r THIS DESIGN AND/OR CHECKED SCH ED U LES W2548317 � 01/26/16 �
<br /> y � SPECIFICATION ISAPPROVED �LC 01126/16 SHEET �
<br /> 1 Revision-Release 30(P2T-IFC UG Utilites)(S2T-90%FINAL UG Utilities) RAN J�C 11/03115 � BRPHARCHITECTS ENGINEER TITLE � •
<br /> ENGINEERSINC. APPROVED BY DEPT. DATE f7AN 01/26/16 Boeing 777X CWC BUILDING �
<br /> 2 Revision-Release 32 RAN JLC 12I01/15 N0.3137 CHECKED . ��� N
<br /> N
<br />� 3 Revision-Release 33 (S2T-IFC FINAL UG Utilities) RAN JLC 12l22115 � B U I L D I�� 40'�J V � �
<br /> �P�� 9T � �o APPROVED - JOB NO. COMP NO. [�O-SH-M�U �
<br /> 4 Revision-Release 34 RAN JLC 01/15/16 /� F OF AUSH� ��P APPROVED
<br /> MECHANICAL MASTER EVERETT,WA owc No. 40-58-M2u
<br /> i
<br />
|