Laserfiche WebLink
BUILDING CONTROL SYSTEM POINT SUMMARY � <br />� SYSTEM NAME: QTY: <br /> SYSTEM NAME; QTY: PLENUM LEVEL 2 <br /> GENERAL 1 DESCRIPTION: A��O� ANALOG DIGITAL DIGITAL NETWORK ALARMS REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS <br /> DESCRIPTION: aNa�oc ANALOG DIGITAL DIGITAL NETWORK ALARMS REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS TYPICAL OF EACH <br /> TYPICAL OF EACH DIFFERENTIAL PRESSURE 3 3 LOCATED ACROSS PRE FILTERS AND ALSO <br /> OUTSIDE AIR TEMP 1 SENSOR ACROSS FINAL FILTERS <br /> DIFFERENTIAL PRESSURE 1 LOCATED ACROSS FINAL FILTERS <br /> OUTSIDE AIR HUMIDITY 1 SWITCH <br /> SYS7EM NAME: QTY: SYSTEM NAME; QTY: <br />� SPRAY BOOTH AND AUTOMATIpN GARAGE 1 AUTOMATION GARAGE MAKE•UP AIR HANDLING UNIT 1 <br /> DESCRIPTION: ANALOG ANALOG DIGITAL DIGITAL NETWORK ALARMS REMARKS DESCRIPTION: ANALOG ANALOG DIGITAL DIGITAL NETWORK ALARMS REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS INPUTS OUTPUTS INPU7S OUTPUTS <br /> TYPICAL OF EACH TYPICAL OF EACH <br /> TEMPERATURE SENSOR 4 HIGH,MID&LOW LEVEL IN SPRAY BOOTH, MID SUPPLY FAN START/STOP 1 <br /> LEVEL IN AUTOMATION GARAGE <br /> HUMIDITY SENSOR 1 LOCATED MID LEVEL SUPPLY FAN PROOF � 1 <br /> DIFFERENTIAL PRESSURE 2 2 BOOTH 70 FACTORY, BOOTH TO AUTOMATION 5UPPLY FAN VSD 1 1 1 SPEED,PLUS ADD'L INFO VIA GATEWAY <br /> SENSOR STORAGE SUPPLY AIRFLOW 1 <br /> BOOTM USER INTERFACE 1 MQNITORING UNIT <br /> PANEL SUPPLY AIR TEMPERP,TURE 1 • <br /> FIRE ALARM PANEL � OUTSIDE AIR TEMPERATURE 1 <br />� SPRAY AIR VALVE CONTROL 1 <br /> FREEZE STAT 1 1 HARDWIRED SHUTDOWN <br /> SPRAY AIR PRESSURE 1 HEATING COIL CONTROL 1 <br /> BREATHING AIR PRESSURE 1 VALVE <br /> FILTER PRESSURE 1 1 <br /> DIFFERENTIAL <br /> SYSTEM NAME: QTY: OUTSIDE AIR DAMPER 1 <br /> PROCESS AIR HANDLING UNIT(SPRAY) � <br /> DESCRIPTION: aNa�oc ANAL06 DIGITAL DIGITAL NETWORK ALAftMS REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS SYSTEM NAME; QTY: <br /> TYPICAL OF EACH AUTOMATION GARAGE GENERAL EXHAUS7 FAN 1 � <br />� SUPPLY FAN START/STOP 4 DESCRIPTION: aNa�oc ANALOG DIGI7AL DIGITAL NETWORK ALARMS REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS <br /> SUPPLY FAN PROOF 4 4 <br /> TYPICAL OF EACH <br /> SUPPLY FAN VSD 4 4 4 SPEED, PLUS ADD'L INFO VIA GATEWAY EXHAUST FAN START/STOP 1 <br /> SUPPLY AIRFLOW 4 EXHAUST FAN PROOF 1 <br /> MONITORING UNIT 1 <br /> SUPPLY AIR TEMPERATURE 1 EXHAUST FAN VSD 1 1 1 SPEED, PLUS ADD'L INFO VIA GATEWAY <br /> OUTSIDE AIR TEMPERATURE 1 EXHAUST AIRFLOW 1 <br /> HEATWG COIL CONTROL 2 MONITORWG UNIT <br /> VALVE EXHAUST AIR DAMPER 1 <br /> FILTER PRESSURE 1 1 • <br /> DIFFERENTIAL <br />� OUTSIDE AIR DAMPER 1 SYS7EM NAME: QTY: <br /> SERIES FAN POWERED VAV TERMINAL UNIT 1 <br /> FREEZE STAT 1 1 HARDW�RED SHUTDOWN ANALOG ANALOG DIGITAL DIGITAL NETWORK ALARMS <br /> DESCRiPTION: iNPurs ourPUTs INPUTS ourPurs REMARKS <br /> SYSTEM NAME: QTY: <br /> TYPICAL OF EACH <br /> PREP BOOTH AiVD AUTOMATION GARAGE � SPACE TEMPERATURE 1 1 <br /> DESCRIPTION: aNa�oc ANALOG DIGITAL DIGITAL NETWORK ALARMS REMARKS <br /> INPUTS ouraurs INPUTS ourPurs SPACE TEMPERATURE 1 <br /> TYPICAL OF EACH ADJUST <br /> TEMPERATUF2E SENSOR 2 MID LEVEL IN PREP BOOTH,MID LEVEL IN SPACE OCCUPANCY 1 <br /> AUTOMATION GARAGE OVERRIDE <br /> DiFFERENTIAL PRESSURE 2 BOOTH TO FACTORY,BOOTH TO AUTOMATION FAN START/STOP 1 ' <br /> SENSOR STORAGE FAN PROOF 1 1 <br />� BOOTH USERINTERFACE 1 <br /> PANEL CON7ROL DAMPER POSITION 1 <br /> FIRE ALARM PANEI� 1 AIRFLOW SENSOR 1 <br /> SPRAY AIR VALVE GONTROL 1 UNIT DISCHARGE 1 1 <br /> SPRAY AIR PRESSURE 1 TEMPERP,TURE <br /> BREATHING AIR PRESSURE 1 ELECTRIC HEATWG CONTROL 1 <br /> VACUUM SYSTEM CONTROL �- 1 <br /> VACUUM SYSTEM PRESSURE 1 SYSTEM NAME: QTY: <br /> CEN7RAL INDUSTRIAL WAS7E SUMP PUMPS 2 � <br /> DESCRIPTION: aNa�o� ANALOG DI�ITAL �IGITAL NETWORK ALARMS I�EMARKS <br />� SYSTEM NAME: QTY: iNPUTs OU7PUTS INPUTS OUTPUTS <br /> PROCESS AIR HANDLING UNIT(PREP) � TYPICAL 0�EACH <br /> ANALOG ANALOG DIGITAL DIGITAL NETWORK ALARMS PUMP START/STOP 3 <br /> DESCRIPTION: REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS <br /> TYPICAL OF EACH PUMP PROOF 3 3 <br /> SUPPLY FAN START/STOP 6 FLOAT SWITCH 4 1 LOW LEVEL SWITCH(PUMP OFF),3 PUMP <br /> SUPPLY FAN PROOF 6 6 ENABLE SWITCHES,ALARM AT HIGHEST PUMP <br /> ENABLE SWITCH <br /> SUPPLY FAN VSD 6 6 6 SPEED,PLUS ADD'L INFO VIA GATEWAY <br /> SUPPLY AIRFLOW 6 SYSTEM NAME: QTY: <br /> MONITORING UNIT . <br /> SUPPLY AIR TEMPERATURE 1 SUBMERSIBLE INDUSTRIAL WASTE SUMP PUMPS 4 <br />� DESCRIPTION: ANa�oc ANALOG DIGITAL DIGITAL NETWORK ALARMS REMARKS <br /> OU7SIDE AIR TEMPERATURE � INPUTS ouTPUTs INPUTS OUTPUTS <br /> BURNER CONTROL � TYPICAL OF EACH <br /> PUMP START/5TOP 1 <br /> FILTER PRESSURE 1 1 <br /> D(FFERENTIAL PUMP PROOF 1 1 <br /> OUTSIDE AIR DAMPER 1 FLOAT SWITCH 1 1 HIGH LEVEL ALARM <br /> FREEZE STAT 1 1 HARDWIRED SHUTDOWN <br /> SYSTEM NAME: QTY: PROCESS WATER HEATING 1 <br /> PROCESS EXHAUST FAN 2 DESCRIPTION: ANALOG ANALO� DIGI7AL DIGITAL NETWORK ALARMS REMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS • <br /> DESCRIPTION: ANALOG ANALOG DIGITAL DIGITAL NETWORK ALARMS �EMARKS <br /> INPUTS OUTPUTS INPUTS OUTPUTS TYPICAL OF EACH <br />� 7YPICAL OF EACH WATER HEATERS 1 1 <br /> EXHAUST FAN START/STOP 4 WATER HEATER CONTROL 2 <br /> EXHAUST FAN PROOF 4 4 VALVE <br /> EXHAUST FAN VSD 4 4 4 SPEED,PLUS ADD'L INFO VIA GATEWAY WATER HEATER 2 <br /> CIRCULATION PUMP <br /> EXHAUST AIRFLOW 4 <br /> MONITORING UNIT <br /> EXHAUST AIR TEMPERATURE 1 <br /> ,4 <br /> DiFFERENTIAL PRESSURE 2 ' �.= . '� <br /> DIFFERENCE ACROSS FAN <br /> EXHAUST AIR DAMPER 2 � � � <br /> i <br /> '�00 SW 16th 5treet Suite 307 FSi consulting engineers <br /> R�nton, Washin�ton 98057 Solutions & Service <br /> � <br /> ACCEPTABILITY DRAWN DATE SUBTtTLE CURRENT REVISION SYMBOL DATE <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE o <br /> 0 IssueForConstruction FSi BSC 03/08/16 � W. Cq THISDESIGNAND/OR �HE�KEo 09'06"6 CONTROLS p01NTS LIST W2548317 <br /> 3 09/06/16 a <br /> Q-�' ��i, '�' SPECIFICATION IS APPROVED RED 09/06/16 sHEET � <br /> � ��` �'r ENGINEER TITLE I� <br /> 1 Revision-Release 47 FSi BSC 07/12116 � � y � APPROVED BY DEPT. DATE gg� 09/06/16 Boeing 777X CWC BUI LDING /� � o <br /> 2 Revision-Release 48 FSi BSC 07126/16 CHECKED � I f� � <br /> 3 Revision-Release 51 FSi BSC 09I06/16 APo��s'���Na�R��G\��� REDRovE� �U I L D I N G 40'�V JOB NO.� COMP NO. � • <br /> 40-58-M1ia Q <br /> i os�os��s APPROVED MECHANICALMASTER EVERETT, WA °WGNO. 40-58-M1ia <br />