Laserfiche WebLink
B. Locations: Each conductor at panelboard gutters, pull boxes, outlet boxes, and junction <br /> boxes each load connection. <br /> C. Legend: <br /> 1. Power and Lighting Circuits: Branch circuit or feeder number indicated on drawings. <br /> D. WIRE COLOR CODING. <br /> 1. Single Phase, 3-Wire System: 120/240-Volt. <br /> a. Phase A: Black. <br /> b. Phase B: Red. <br /> 2. Equipment ground wire- green. <br /> 3. Control wiring shall be black with identifying wire numbers at each termination. <br /> 4. Color-coded tape may be used in lieu of color-coded insulation for conductors#8 <br /> AWG and larger. However, when color coded tape is used, the conductor insulation <br /> shall be black only and shall be tape identified with color scheme shown above at <br /> splices, terminations and junction boxes. <br /> CONDUIT MARKERS <br /> A. Location: Furnish markers for each conduit longer than 6 feet(2 m). <br /> B. Spacing: 20 feet(6 m) on center. <br /> C. Color: <br /> 1. 208 Volt System: Blue. <br /> 2. Telecommunication System: Gray. <br /> UNDERGROUND WARNING TAPE <br /> Description: 4 inch (100 mm) wide plastic tape, detectable type colored red with suitable <br /> warning legend describing buried electrical lines. <br /> ENCLOSED CONTACTORS <br /> MANUFACTURERS <br /> A. Square D. <br /> 1. 8910DPA14VO2U1 Sq D Contactor <br /> 2. 8910DPA22VO2U1 Sq D Contactor <br /> 3. (2) 9910DPG2 Sq D Enclosure <br /> 4. XB4BG61 Sq D Select Switch <br /> B. Substitutions: Not permitted. <br /> LIGHTING CONTACTORS <br /> A. Description: NEMA ICS 2, magnetic lighting contactor. <br /> B. Configuration: Electrically held. <br /> C. Coil operating voltage: 120 volts, 60 Hertz. <br /> D. Poles: As required to match circuit configuration and control function. <br /> E. Contact Rating: Match branch circuit overcurrent protection, considering derating for <br /> continuous loads. <br /> Swift Green Line—Corridor Stations Special Provisions SP160 <br /> May 2017 <br />