<br /> PHOTOVOLTAIC NOTES , . SCOPE OF WORK App. Date: 5/2/2019
<br /> •
<br /> I.A N INVERTER OR AN AC MODULE IN AN INTERACTIVE PHOTOVOLTAIC SYSTEM SHALL AUTOMATIC ALL ' INSTALLATION OF ROOF MOUNTED SOLAR
<br /> • w Proposed Use: SFR DETACHED
<br /> DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK I asp NEW EQUIPMENT: 21 MODEL#:SLA-M 300-3C
<br /> UPON LOSS OF VOLTAGE IN THAT SYSTEM AND SHALL REMAIN IN THAT STATE UNTIL THE ELECTRICAL .... :.� ,. SILFAB ENERGY MODUL Description: ELECTRICAL TO INSTALL PV SOLAR SYSTEM
<br /> PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED.(NEC 690361) • , • 21 P320 SOLAREDGE OPTI
<br /> 2.ALL EXTERIOR ELECTRICAL METALLIC TUBING(EMT)CONDUIT FITTING SHALL BE RAIN TIGHT , �4,•.- SE6000H-US ON ROOFTOP
<br /> THREAD-LESS COMPRESSION TYPE. '�~ ,. r X ii,Y w - 1
<br /> 3.MODULES AND SUPPORT 5IRUCTURES SHALL BE GROUNDED • { - SOLAREDGE HDINVER'1
<br /> 4.NAMEPLATES SHALL BE PROVIDED FOR ALL CIRCUITS IN THE SERVICE DISTRIBUTION AND POWER " ''' .i.- -,,+ , * ,. i."--. SYSTEM SIZE: 6.300 DC KW POWER RATING
<br /> 6.000 AC KW POWER RATING
<br /> DISTRIBUTION SWITCH BOARDS,PANEL BOARDS.DISCONNECTING SWITCHES,TERMINAL CABINETS, `- Rey' ed By:
<br /> ETC.ALL NAMEPLATES SHALL BE PERMANENTLY ATTACHED AND BE OF SUFFICIENT CAPACITY TO R - RACKING: SPIDER-RAX BLACK WIDOW CON Date:
<br /> WITHSTANDTHE WEATHER. - I SYSTEM •
<br /> Office Set Job Site Set
<br /> 5.JUNCTION BOX/COMBINER BOX HAVE TO USE COMPRESSION TYPE STRAIN RELIEF POSONED FOR ARRAY AREA: 17.58 SQ FT x 21 =
<br /> POSITIONED 369.18 SFire/Planning Set
<br /> APPROPRIATE WATER RUN OFF. -
<br /> 6.CONDUIT RUNS SHALL BE PROVIDED WITH SUFFICIENT WEATHERPROOF PULL BOXES OF JUNCTION . w - 'M
<br /> BOX/COMBINER BOXES PER APPROPRIATE NEC REQUIREMENTS. ;k C ♦ I SITE DETAIL
<br /> 7.SEE PROVIDED CUT SHEETS FOR ADDITIONAL EQUIPMENT SPECIFICATIONS ' ffrf...741= t.,,::+1: - UTILITY: SNOHOMISH PUD
<br /> 8.WIRING MATERIALS SHALL BE SUITABLE FOR THE SUN EXPOSURE AND WET LOCATIONS.FIELD -
<br /> APPLIED PROTECTIVE COATINGS ARE NOT ACCEPTABLE. r ELECTRIC SERVICE: 200A tai y ws A wi`J7 bioassay9.JUNCTION.PULL AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE SO INSTALLED THAT THE ;, ROOF MATERIAL: COMPOSITE SHINGLE
<br /> WIRING CONTAINED IN THEM CAN BE RENDERED ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF ,°''° : ",; ASCE 7 GROUND SNOW LOAD: 25 PSF
<br /> MODULE(S)SECURED BY REMOVABLE FASTENERS AND CONNECTED BY A FLEXIBLE WIRING SYSTEM.
<br /> (NEC 690.34) -
<br /> ^ ASCE 7-10 WINDSPEEDS: (3 SEC GUST IN MPH)
<br /> 10.IN AN UNDERGROUND PHOTOVOLTAIC SYSTEM.THE POWER SOURCE SHALL BE LABELED WITH THE RISK CATERGORY I: 100 SOLAR
<br /> FOLLOWING WARNING AT EACH JUNCTION BOX.COMBINER BOX,DISCONNECT AND DEVICE WHERE THE s_' ,. Y RISK CATEGORY II: 1 1 O
<br /> UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE:"WARNING-ELECTRIC SHOCK HAZARD. ,.. f�� r'`" RISK CATEGORY III-IV: 115
<br /> IIIIKTHE CURRENT CIRCUIT CONDUCTORS OF THIS PHOTOVOLTAIC POWER SYSTEM ARE UNGROUNDED BUT '3 t "*' „a 4T3 / •
<br /> MAYBE ENERGIZED WITH THE RESPECTTO GROUND DUE TO LEAKAGE PATHS AND/OR GROUND f . ,� _ �, "±~ # N - -/•+f
<br /> FAULTS."(NECE 690.35(F)) ' t , a e , '1,i
<br /> 11.ALL PHOTOVOLTAIC MODULES AND ASSOCIATED EQUIPMENT AND WIRING MATERIAL SHALL BE i» e s,
<br /> PROTECTED FROM ANY PHYSICAL DAMAGE. CODE AUTHORITY 1001 COOPER POINT
<br /> 12.ALL ELECTRICAL DEVICES AND UTILIZATION EQUIPMENT SHALL BE LISTED BY AN APPROVED TESTING 12015 WASHINGTON STATE BUILDING CODE(2015 IBC) RD SW,STE 140.290.
<br /> AGENCY. �, w> "'4. 1b� 'k 2015 WASHINGTON STATE ENERGY CODE(2015 IECC) OLYMPIA,WA 98502
<br /> 13.OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED.
<br /> 14.ALL SPECIFIED WIRING IS BASED ON THE USE OF COPPER 2015 WASHINGTON STATE RESIDENTIAL CODE(2015 INTERNATIONAL PHONE:360-637-4343
<br /> 1 5.CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS AND SHALL COORDINATE ALL INSPECTION, r r•- RESIDENTIAL CODE WASHINGTON AMENDMENTS 2014 WAC51-51-2300
<br /> COMMISSIONING AND ACCEPTANCE WITH THE CLIENT,UTILITY CO.AND CITY INSPECTORS AS NEEDED SECTION M2302) H EI DI PASCHAL
<br /> 16.DRAWINGS ARE DIAGRAMMATIC ONLY,ROUTING OF RACEWAYS SHALL BE ATTH E OPTION OF THE VIEW 2017 WAC 296.468(2017 NEC) PROJECT MANAGER
<br /> CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL BE COORDINATED WITH OTHER TRADES. Zrat
<br /> AERIAL 2017 WASHINGTON CITIES ELECTRICAL CODE(2017 WC EC)
<br /> 17.IF DISTANCES OF CABLE RUNS ARE DIFFERENT THAN SHOWN,THE CONTRACTOR SHALL NOTIFY
<br /> ELECTRICAL ENGINEER TO VALIDATE THE WIRE SIZE.FINAL DRAWINGS WILL BE RED-LINED AND UPDATED 2015 WASHINGTON STATE MECHANICAL CO DE(201 5 UMC)
<br /> AS APPROPRIATE. 2015 WASHINGTON STATE PLUMBING CODE(2015 UPC)
<br /> 18.WHENEVER A DISCREPANCY IN QUANTITY OF EQUIPMENT,ARISES ON THE DRAWINGS OR 2015 WASHINGTON STATE FIRE CODE (2015 IFC) 6.300 DC KW
<br /> SPECIFICATIONS,THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL
<br /> MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN 6.000 KW C EC-AC RATING
<br /> THE SPECIFICATIONS TO ENDURE COMPLETE COMPLIANCE AND LONGEVITY OF THE OPERABLE SYSTEM SHEET INDEX
<br /> REQUIRED BY THE ARCHITECT/ENGINEER. A-1 GENERAL NOTES,SHEET INDEX,BUILDING&PROJECT DATA CENTRAL INVERTER SYSTEM
<br /> 19.ALL BROCHURES,OPERATION MANUALS.CATALOGS.SHOP DRAWINGS,ETC.SHALL BE HANDED A-2 SITE PLANo
<br /> OVER TO THE OWNER'S REPRESENTATIVE AT THE COMPLETION OR WORK. 23° 2.70
<br /> 20.ALL WIRING CONCEALED IN WALL AND CEILING SPACES SHALL BE IN METAL CONDUIT. A-3 WIRING&MOUNTING PLAN TILT AZIMUTH
<br /> 21.THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE P E-1 ELECTRICAL SINGLE LINE DIAGRAM
<br /> WITH THE"SMACNA"-GUIDLINES FOR SEISMIC RESTRAINS OF MECHANICAL SYSTEMS AND PLUMING 0 E-2 ELECTRICAL CALCULATIONS
<br /> PIPING SYSTEMS. ';', S
<br /> 22.ALL OF THE LISTED SYSTEMS REQUIRED THAT THE SEISMIC LATERAL FORCE F INCLUDING Harborvlew Park Q ;Y E-3 LABELING REQUIREMENTS
<br /> CONSIDERATION OFA^P AND W.F.BE DETERMINED AT EACH LEVEL OF THE BUILDING SO THAT BRACE s' E-4 EQUIPMENT:PV MODULE SPECIFICATION SHEET 4706 GLENWOOD AVE
<br /> SPACING CAN BE CALCULATED.THE DISTRICT STRUCTURAL ENGINEER CAN APPROVE THE SEISMIC E-5 EQUIPMENT:INVERTER SPECIFICATION SHEET
<br /> LATERAL FORCE DETERMINATION. E-6 EQUIPMENT:DC/DC OPTIMIZER SPECIFICATION SHEET EVERETT,
<br /> 23.A COPY OF THE CHOSEN BRACING SYS I EM(S)INSTALLATION GUIDE/MANUAL SHALL BE ON THE JOB 4...0
<br /> YS-1 EQUIPMENT:RACKING SYSTEM �-� WA 98203
<br /> SITE PRIOR TO STARTING THE INSTALLING OF HANGERS AND/OR BRACES. 'ttw,��,
<br /> 24.WHEN INSTALLING DRILLED-IN ANCHORS AND/OR POWDER DRIVEN PINS IN EXISTING , S-2 EQUIPMENT:RACKING SYSTEM c ,,,
<br /> NON-PRESTRESSED REINFORCED CONCRETE.USE CARE AND CAUTION TO AVOID CUTTING OR $-3 EQUIPMENT:RACKING SYSTEM ATTACH ,.1i1 !_�- j
<br /> DAMAGING THE REINFORCED BARS.WHEN INSTALLING THEM INTO EXISTING PRE-STRESSED CONCRETE - Viii.'.. CHRISTOPHER CONNAIR
<br /> TENDONS BY USING A NON-DESTRUCTIVE METHOD PRIOR TO INSTALLATION.EXERCISE EXTREME CARE (937)305-5812
<br /> AND CAUTION TO AVOID CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION.MAINTAIN A - = `.`�/ 20191
<br /> MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT AND THE DRILLED-IN ANCHOR. > MHT IJ �_�
<br /> 25.THE WORKING CLEARANCES AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW
<br /> ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN ACCORDANCE WITH NEC 110.26. APN:00505700003905
<br /> 26.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT.(NEC 300.6 01.
<br /> 310.8 DI ``,,,,, /4706Glenwood Avenue CITY OF EVERET�
<br /> 27.GROUNDING BUSHINGS ARE REQUIRED AROUND PRE-PUNCHED CONCENTRIC KNOCKOUTS ON THE
<br /> DC SIDE OF THE SYSTEM.(NEC 250.97) Permit Services
<br /> 28.THE GROUNDING ELECTRODE CONDUCTOR MUST BE PROTE(.I ED FROM PHYSICAL DAMAGE IF
<br /> SMALLER THAN#6 COPPER WIRE.(NEC 250.64 B) DATE DESCRIPTION
<br /> 29.GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS,EXCEPT FOR SPLICES OR JOINTS AT
<br /> BUSBARS WITHIN LISTED EQUIPMENT.(NEC 250.64 C)
<br /> 30.RACEWAY FOR GROUNDING ELECTRODE CONDUCTOR SHALL BE BONDED AT EACH END.(CEC
<br /> 250.64(E) ''ro:.na a--a
<br /> 31.WHERE ALL TERMINALS OF THE DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN POSITION,
<br /> A SIGN WILL BE PROVIDED WARNING OF THE HAZARD PER NEC 690.17.34.EACH UNGROUNDED
<br /> CONDUCTOR OF THE MULT-IWIRE BRANCH CIRCUIT WILL BE IDENTIFIED PER PHASE AND SYSTEM PER
<br /> Joy's!,t`ard.A,Caterdiy
<br /> NEC210.5. ,i�! k
<br /> 32.CIRCUITS OVER 250V TO GROUND SHALL COMPLY WITH NEC250.97&250.92(B)&LAMC 93.250.97. - ""� ,-.}ry b DATE 4/23/19
<br /> 33.DC CONDUCTORS EITHER DO NOT ENTER THE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR '' �'' DRAWN:
<br /> ENCLOSURES TO THE FIRST ACCESSIBLE DC DISCONNECTING MEANS PER NEC 690.31(E).LAMC /_\ f' -,) 't
<br /> 93.690.31(E) 1; VICINITY MAP € DRAWN BY: PD
<br /> 34.ALL METALLIC FRAME RAILS AND OTHER CURRENT CARRYING METALLIC COMPONENTS(CONDUIT, 11 W."
<br /> JUNCTION&PULL BOXES,RACEWAY,ETC)SHALL BE SOLIDLY GROUNDED PER THE MANUFACTURER'S ii
<br /> INSTALLATION INSTRUCTIONS LAMC 93.690.1 10.3&93.1 10.3(B). ! �
<br /> 35.SCREWS,NUTS,BOLTS&WASHERS THAT ATTACH EQUIPMENT GROUNDING LUGS SHALL BE La-4
<br /> STAINLESS STEEL LAMC 93.110.3(B). 4 GENERAL
<br /> 36.NO PIPING.DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE CITY OF Etj[.EVERETT
<br /> LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT. V ERE 1
<br /> 37.ALL FIELD INSTALLED JUNCTION,PULL AND OUTLET BOXED LOCATED BEHIND MODULES OR PANELS Permit Services NOTES
<br /> SHALL BE ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A MODULE(S)OR PANEL(S)SECURED BY
<br /> REMOVABLE FASTENERS. PROJECT DATA/l T/�
<br /> 38.REMOVAL OF A DWP-INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE PROJECT /-'� �1
<br /> BONDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC
<br /> SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR.
<br /> 39.THE ROOF MOUNTED PHOTOVOLTAIC MODULES,PANELS,OR SOLAR VOLTAIC ROLL ROOFING
<br /> MATERIAL SHALL HAVE THE SAME OR BETTER LISTED FIRE-RESISTANCE RATING THAN THE BUILDING
<br /> ROOF-COVERING MATERIAL.
<br /> 40.ALL ROOF MOUNTED CONDUIT WILL BE A MINIMUM 1/2"OFF THE ROOF SURFACE. 1