LEGEND: <br /> 1. SEE LEGEND SHEET 40-58-EO FOR ABBREVIATIONS AND <br /> NOTES. <br /> GENERAL NOTES: <br /> 1. PROVIDE (1) 1-1/2°C BETWEEN GENERATOR AND BUILDING <br /> 40-57 AUTOMATIC TRANSFER SWITCHES FOR CONTROL <br /> 7 7 AND COMMUNICATION. <br /> 2. PROVIDE (2) 1"C BETWEEN EACH AUTOMATIC TRANSFER <br /> SWITCH AND GENERATOR CONTROL PANEL. IN ADDITION <br /> _ TO FEEDER CONDUITS INDICATED, PROVIDE THE <br /> � FOLLOWING CONDUITS: <br /> 450KW (2) SETS: (4)#600 KCMIL, #1/0 G (1} 1"C FROM 120l208V PANEL FOR BATTERY CHARGING. <br /> DIESEL �� <br /> GENERATOR � 800A EA. SET IN 4"C + (1) SPARE 4"C , (1) 1"C FROM 120/208V PANEL FOR JACKET HEATER. <br /> � �2 �'�1 SEE SHEET E5-1B FOR (1} 1-1I2°C FROMA.T.S. FOR CONTROL. <br /> �, i ETHERNET CONNECTION TO OPC SERVER.L FOR <br /> GF � � � CONTINUA710N (1) 1"C SPARE. <br /> SEPARATELY <br /> `� <br /> DERIVED SOURCE 3. SELECTIVE COORDINATION: THE EMERGENCY SYSTEM <br /> GENERATOR#13 3SWBD-G13 BRANCH MUST BE SELECTIVELY COORDINATED. THE <br /> 800A( '�; 480/277V- 3f1�,4W � INDICATED DISTRIBUTION SYSTEM HAS BEEN DESIGNED TO <br /> ; 800/800A MCB PROVIDE FULL SELECTIVE COORpINATION ON THE <br /> � 42,000 AIC FOLLOWING BASIS. ALTERNATES MAY BE PROVIDED FOR <br /> REVIEW WHEN ACCOMPANIED BYA SELECTIVE <br /> COORDINATION STUDY PERFORMED BY A REGISTERED <br /> PROFESSIONAL ENGINEER. <br /> } 1QOA )400A �)400A GENERATOR BREAKER <br /> EM EM EM SIEMENS MD6 <br /> LTPU: 600A <br /> LTD: NA <br /> INST: 5X <br /> TO BLD 40-57 EM SYSTEM 2-1/2"C <br /> REFER TD 40-57-E5 (4)#3/0,#6G M EMERGENCY BRANCH ENC. BREAKER <br /> � SIEMENS HLG 400, ETU 545 <br /> (4)#600 KCMIL, #3G � LTDU.2 5S A <br /> U v INST: 1600A <br /> 4��C Y � <br /> 0 <br /> � 100A FEEDER AND MCB <br /> �* SIEMENS NGB-100 <br /> (4)#600 KCMIL, #3G (4)#600 KCMIL, #3G � INST FIXED AT 900 <br /> TO 3V58-7AG4.0-D TO 3V58-7AG4.0-D <br /> REFER TO 40-58-E4-7A q,��C REFER TO 40-58-E4-7A 4��C BRANCH CIRCUIT BREAKERS <br /> SIEMENS NGB-20 <br /> ATS XE-13-2 ATS XE-13-1 <br /> 400A,4-P 400A, 4-P <br /> 42,000A 42,000A CONSTRUCTI4N NOTES: <br /> WSR WSR <br /> �= CONDUCTOR SIZE ADJUSTED FOR VOLTAGE DROP. <br /> RECALCULATE RND ADJUST AS NECESSARY WHEN <br /> � ACTUAL ROUTE OF FEEDER IS KNOWN. <br /> � �?j PROVIDE SWITCHBOARD WITH VERTICAL SEPARATION PER <br /> � NEC 700.10(B)(5). <br /> � <br /> U <br /> Y � � � GENERATOR SUPPORT PANEL LOCATED W GENERATOR <br /> 0 7 ENCLOSURE. FIELD COORDWATE CONNECTION <br /> `O REQUIREMENTS AND LOCATION. <br /> � <br /> � <br /> � REFERENCE NOTES: <br /> 1. REFERENCE DRAWING 40-58-E508 FOR LIGHTING FIXTURE <br /> SCHEDULE. <br /> XE-3V58-7AF4.25-D <br /> XE-3V58-7AMJ2.0-D <br /> 480(277V-30, 4W 480/277V-3�, 4W <br /> 400A MLO 400A MLO <br /> 42,000 AIC 42,000 AIC <br /> l30A 1125A 1125A 1125A 1125A 1125A 1125A 1125A 1125A 1125A l50A J)30A ) 125A ) 125A ) 125A �) 125A ) 125A ) 125A ) 125A 125A � <br /> / I / � J l l / � / / / �l � � < < � <br /> U <br /> 0 <br /> (3)#6, #10G, <br /> o � 1 C c GENERATOR#13 � � � � � � � � � <br /> 0 <br /> � �,,� C� C� C� C� C� C� 7 <br /> C� (.� C.� *k U o U _ o U o U o U o U o U o U o U <br /> � � � �k �k �k �k �k �k *k L, 30KVA O � N N 1 � N N 1 `` N N 1 ` N �y � N N I� N N 1 ` N N I1 j N N 1 <br /> � o U �� � O U � O U �- O U � O U �\ O U � O U � O U O U � � � � � � �k � �� �k <br /> " c� I/ N �v � I 'i�' �i r �= ,- � .... � �. 480:208Y/120V .-. .-. .-. .-. .-, ,-. .-. .-. <br /> � � �� N� CV _ � CV � N ,-�"J � N � N � (V � N � � � �t' d' d' d' d' d' d' <br /> SPD _ � � ..� .� � `. ...., ,.. �. <br /> � r-. .-� �-. .-� .-. �-. .-. .� � � - <br /> � � � � 0 � 5 � � 10 � 5 � � (4)#1, #6G, SPo <br /> 5 1-1/2"C � <br /> � I 200/3 200/3 � 200/3 100/3 ^ <br /> NF NF NF 100 J <br /> C M M C M M �I � M 1O <br /> SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD SPD <br /> 3 � 125A MLO 125A MLO 125A MLO 125A MLO 125A MLO 125A MLO 125A MLO 125A MLO <br /> 125A MLO 125A MLO 125A MLO 125A MLO 125A MLO 100A MLO 125A MLO 125A MLO 125A MLO 100A MGB � <br /> 125A BUS 125A BUS 125A BUS 125A BUS 125A BUS 100A BUS 125A BUS 125A BUS 125A BUS 208YI120V <br /> 3Q�, 4W 3Q1, 4W 3Q�, 4W 3Q1, 4W 3Q�, 4W 3(�, 4W 30, 4W 3�, 4W 3�, 4W 3�, 4VV 3Q1, 4W 3�, 4W 3�D, 4W 3Q�, 4W 3Q�, 4W 3f�, 4W 3Q1, 4W 3�, 4W <br /> XE-3V58-lATN2H3.15 XE-3V58-7A64.0 XE-3V58-1AG4.0 XE-3V58-7ATN2C3.15 XE-3V58-7AJ4.0-1 XE-3V58-7AJ4.0-2 XE-3V58-1AJ2.0 XE-3V58-lATN1K2.30 XE-3V58-1AG2.0 GENERATOR#13 XE-3V58-7AMG2.0 XE-3V58-7AUG2.0 XE-3V58-7AUJ2.0 XE-3V58-7AVG2.0 XE-3V58-7AVJ2.0 XE-3V58-7ACG2.0 XE-3V58-7ACH2.0 XE-3V58-7ACK2A <br /> (METERED PANEL) (METERED PANEL} <br /> 8 V V <br /> 5 7 g <br /> 6 <br /> 6 � REV 33 CHANGES ONLY <br /> 7 "`� <br /> ��. cAMA� <br /> �,v o� �As�� �� � <br /> � c������' �'�q'�� � <br /> 0 67: F�rr712 5'�' MT} <br /> :4 ,. <br /> _ q, . <br /> � � � 52�6�� �� �� <br /> 900 SW 16th Stre�et��Suite �3�7 ��°�F��'�isTER�° c,���� <br /> sS1ONAL � <br /> Renton, Washin�ton 98057 �..■�n � <br /> � <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE W A s �� ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE � <br /> � �� °F H(Nc CHECKED �v22"5 EMERGENCY ONE-LINE DIAGRAM W2548317 10 _ 12/22/15 N <br /> REVISION-RELEASE 29 JTD DFC 10I20I15 5 REVISION-RELEASE 18 JTD JLM 05/19/15 Q, T THIS DESIGN AND/OR JTD 12l22115 SHEET �n <br /> 5 � SPECIFICATION IS APPROVED .- <br /> BRPH ARCHITECTS ENGINEER TITLE N <br /> 1 REVISION-RELEASE 5 JTD FAK 01126/15 6 REVISION-RELEASE 19 JTD DFC 06IO2/15 ��� � BOEING 777X CWC BUILpING <br /> n ENeiNEERsiNc. APPROVED BY DEPT. DATE DFC ,z�22„5 E51 A � <br /> 2 REVISION-RELEASE 11 JTD FAK 03/03/15 7 REVISION-RELEASE 20 JTD DFC 06116115 N0.3137 CHECKED � N <br /> 3 REVISION-RELEASE 15(AUTOCLAVE 90P) JTD FAK 04/07/15 8 REVISION-RELEASE 26 JTD DFC 09108/15 ��',F �o APPROVED B U I LD I N G �O'�V JOB NO. COMP NO. <br /> %qr ��tiP � 40-58-E5-1A � <br /> 4 REVISION-RELEASE 16 JLM FAK 04l21/15 9 REVISION-RELEASE 27 RER DFC 09122/15 F oF AujN° � APPROVED ELECTRICAL MASTER EVERETT,WA °wc r,o. 40-58-E5-1A <br />