3003 W CASINO RD 2015 BLDG 40-58 Plans 2022-11-09
>
Address Records
>
W CASINO RD
>
3003
>
BLDG 40-58
>
Plans
>
3003 W CASINO RD 2015 BLDG 40-58 Plans 2022-11-09
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/9/2022 10:32:44 AM
Creation date
7/24/2019 2:24:46 PM
Metadata
Fields
Template:
Address Document
Street Name
W CASINO RD
Street Number
3003
Tenant Name
BLDG 40-58
Permit
B1512-034
Year
2015
Notes
PAINT BOOTH STRUCTURE
Address Document Type
Plans
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
349
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
P2P PROCESS AIR CONDITIONING UNIT SCHEDULE - SPRAY/PREP BOOTH #1 <br /> CALLOUT SUPPLY FAN FILTER GAS BURNER ELECTRICAL BASIS OF DESIGN <br /> MOTOR [5] [12] <br /> MAX MAX MAX <br /> FAN TYPE DRIVE CFM E.S.P. (IN RPM BHP VEL INPUT OUTPUT LAT BURNER MIN EFF TURNDOWN CONN. SIZE <br /> TYPE MARK LOCATION SERVICE DESIGN CFM [4] TYPE [4] [1] [4] WC) [3] [4] QTY [1] [4] RPM HP [6] TYPE [7] (FPM) MBH MBH (DEG F) TYPE QUANTITY [12] RATIO (IN) [11] VOLTAGE PHASE FREQUENCY MANUFACTURER MODEL NOTES <br /> PACU 1 MECH MEZZANWE SPRAY BOOTH 82Q00 PLENUM DIRECT 20500 3.00 4 2291 1800 40 31.44 MERV 9/MERV 13 500 11860 9880 120 °F INDIRECT 8 $0% 26:1 1 1/2" 460 3 60 SCOTT SPRINGFIELD [9] [10] [13] <br /> PACU 2 MECH MEZZANINE PREP BOOTH 49000 PLENUM DIRECT 8167 2.50 6 2310 1800 15 9.12 MERV 9IMERV 13 500 3175 2650 120 °F INDIRECT 2 80% 20:1 2" 460 3 60 SCOTT SPRINGFIELD [9] [10] [13] ' <br /> SCHEDULE NOTES: <br /> [1] WITH UNIT AT MAXIMUM CONDITIONS ' <br /> [2] OUTSIDE AIR QUANTITY WITH DAMPER AT MlNIMUM POSITION AND UNIT AT MAXIMUM CONDIT(ONS, "OSA A" REFERS TO ASHRAE 62.1 AREA BASED MINIMUM, "OSA A+P" REFERS TO ASHRAE 62.1 AREA AND PEOPLE BASE MINIMUM FOR CO2 CONTROL, SEE SEQUENCE OF OPERATION <br /> [3] STATIC PRESSURE EXTERNAL TO UNIT, DOES NOT INCLUDE DIRTY FILTER ALLOWANCE <br /> [4] VALUE PROVIDED IS BASED ON EACH INDIVIDUAL FAN <br /> [5] VALUE PROVIDED IS BASED ON EACH INDIVIDUAL MOTOR <br /> [6] MAXIMUM ALLOWABLE MOTOR BRAKEHORSEPOWER AT MAX FLOW AND TSP <br /> [7] 2" MERV 9 PRE-FILTER& 12" MERV 13 FINAL FILTER <br /> [8] RADIATED NOISE SHALL BE IN COMPLIANCE WITH LOCAL NOISE ORDINANCES; MAXIMUM RADIATED SOUND POWER LEVELS OF THE UNIT SHALL NOT EXCEED 85 dBA. UNIT SOUND POWER SHALL NOT EXCEED THE LEVEL INDICATED <br /> [9] COORDINATE UNIT LENGTH WITH SUPPLY AND RETURN OPENINGS- SEE DWGS. <br /> [10] PROVIDE WITH OSA/SUPPLY PLENUM <br /> [11] GAS CONNECTION SIZE BASED UPON 5 PSI SUPPLY PRESSURE. � <br /> [12] PROVIDE VFD FOR EACH FAN MOTOR, SEE ELECTRICAL DESIGN FOR VFD SPECIFICATIONS. ELETRICAL TO PROVIDE VFD, VFD TO BE FIELD INSTALLED � <br /> [13] PROVIDE MANUFACTURER INSTALLED TERMINAL JUNCTION BOX ON EXTERIOR OF UNIT CASING INCLUDING ALL WIRING NECESSARY FOR VFD OPERATION AND CONTROL PROVIDE ONE JUNCTION BOX PER VFD. <br /> P2P PROCESS EXHAUST FAN SCHEDULE - SPRAYIPREP BOOTH #1 <br /> CALLOUT DESIGN FAN ELECTRICAL BASIS OF DESIGN <br /> FLOW FAN DRIVE FLOW MOTOR[3] <br /> TYPE MARK LOCATION SERVICE (CFM) TYPE TYPE (CFM) E.S.P. (IN.W.G.) [1] QUANTITY RPM RPM HP BHP [2] VOLTAGE PHASE FREQUENCY MANUFACTURER MODEL NOTES <br /> EF 49 APRON LEVEL NORTH OF GRID 4.0 SPRAY BOOTH 90200 PLUG V-BELT 22,550 5.00 4 1130 1800 40 25.4 460 3 60 HUNTAIR CSU-55K [4] <br /> EF 50 APRON LEVEL NORTH OF GRID 4.0 PREP BOOTH 54120 PLUG V-BELT 13,530 5.00 4 1350 1800 20 12.2 460 3 60 HUNTAIR CSU-55K [4] <br /> SCHEDULE NOTES: <br /> [1] STATIC PRESSURE EXTERNAL TO FAN <br /> [2j MAXIMUM ALLOWABLE MOTOR BRAKEHORSEPOWER AT MAX FLOW AND TSP <br /> [3� PROVIDE VFD FOR EACH FAN MOTOR, SEE ELECTRICAL DESIGN FOR VFD SPECIFICATIONS <br /> [4] PROVIDE MANUFACTURER INSTALLED TERMINAL JUNCTION BOX ON EXTERIOR OF UNIT CASING INCLUDING ALL WIRING NECESSARY FOR VFD OPERATION AND CONTROL. PROVIDE ONE JUNCTION BOX PER VFD. <br /> P2P TRENCH FILTER SCHEDULE - SPRAYIPREP BOOTH #1 <br /> DESIGN FACE INDIVIDUAL FILTER DIMENSIONS FILTER ARRAY BASIS OF DESlGN , <br /> TEMPERATURE VELOCITY <br /> MARK EFFICIENCY (°F) (FPM} HEIGHT(IN) WIDTH (IN) DEPTH (IN) HEIGHT WIDTH TOTAL MANUFACTURER MODEL NOTES <br /> F-1 MERV 14 160 120 24" 24" 4" 3 4 12 PUROLATOR SUPERSORB III [4] [5] � <br /> F-2 99% 160 500 24° 24" 11 1/2° 3 4 12 PUROLATOR ULTRA-CELL HEPA [1] [2] <br /> F-3 99.97% 160 500 24° 24" 11 1/2" 3 4 12 PUROLATOR ULTRA-CELL HEPA [1] [3] <br /> SCHEDULE NOTES: <br /> [1] ALL HEPA FILTERS SHALL HAVE METAL CELL SIDES <br /> [2] FOR USE IN FINAL FILTER ASSEMBLY OF PREP BOOTH <br /> [3� FOR USE IN FINAL FILTER ASSEMBLY OF SPRAY BOOTH <br /> [4] FOR SPRAY BOOTH PLENUM, PROVIDE FILTER ARRAY OF 3 ROWS AND 4 COLUMNS <br /> [5] FOR PREP BOOTH PLENUM, PROVIDE FILTER ARRAY OF 2 ROWS AND 4 COLUMNS ' <br /> � , <br /> 900 SW 16th Street Suite 307 FSi consuiting engineers <br /> Renton, Washington 98057 Solutions & Service <br /> � <br /> �. <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE ,vQ' <br /> ACCEPTABILITY NJH 12122115 PROCESS HVAC EQUIPMENT SCHEDULES � <br /> 0 ISSUED FOR CONSTRUCTION FSi 12/22/15 � ��D�'�,p W2548317 Q 12/22/15 � <br /> � THIS DESIGN AND/OR CHECKED N <br /> ' ��,�P'��' '�'� � SPECIFICATION IS APPROVED RED 12/22115 SHEET u� , <br /> - BOE,��� � y � ENGINEER T�r�E BOEING 777X CWC BUILDING � <br /> � APPROVED BY DEPT. DATE BSC 12/22/15 � A�X N_ <br /> \ / � <br /> CHECKED � <br /> �zozso �4 IV' N . <br /> o�,� G�STE E�G��F' - APPROVED B U I LD I N G 40 58 JOB NO. COMP NO. _ <br /> SS�oHAG E`' RE� 40-058-M2x Z <br /> APPROVED DWG NO. <br /> �2�z2i�5 MECHANICAL MASTER EVERETT, WA 40-058-M2x <br />