Laserfiche WebLink
' . . li..._:.:_. . . : .. . . . . _._._. ._ . . :: . ..:.:��-., <br /> EXHAUST FA�1S �A� CONTRO � BOXES � <br /> MARK STAT. WHEEL MOTOR ELECT. CHAR. -�pE AIR ELEC. HEATING CONN. SIZE MIN. <br /> AREA SERVED CFM PRESS. TYPE DRIVE RPM REMARKS MARK BYPASS QUANTITY COIL DIA. INLET <br /> N0. � W � DIA. HP V PH CYC N� AREA SERVED OR SHUT S p REMARKS <br /> OFF MAX. MIN. KW MOTOR CHAR. INLET OUTLET I W � * <br /> EF-1 ROOMS �121 1 ,710 0.50 BELT 593 15 3/4 460 3 60 ��PACE" MODEL �CRE-15F W/GRAVITY BACKDRAFT (CFM) (CFM) V PH CYC (IN.) (IN) <br /> 122 & 123 DAMPER AND ROOF CURB, OR APPROVED EQUAL TRANE <br /> ROOMS �113 "PACE" MODEL #CRE-15F W/GRAVITY BACKDRAFT VAV-1 ROOM �220 S.O. 450 225 - - - - 8 15/12 0.30 VCCC-08 ,� <br /> EF-2 114 & 115 1 ,710 0.50 BELT 593 15 3/4 460 3 60 DAMPER AND ROOF CURB, OR APPROVED EQUAL <br /> VAV-2 ROOM �220 S.O. 450 225 - - - - 8 15/12 0.30 TRANE <br /> EF-3 ROOMS �102 1 ,710 0.50 BELT 593 15 3/4 460 3 60 ��PACE" MODEL �CRE-15F W/GRAVITY BACKDRAFT VCCC-08 <br /> 103 8c 104 DAMPER AND ROOF CURB, OR APPROVED EQUAL TRANE <br /> MACHINERY "GREENNECK" MODEL GWB-18-4 W/GRAVITY VAV-3 ROOM �220 S.O. 450 225 - - - - 8 15/12 0.30 VCCC-08 " <br /> EF-4 ROOM �101 1 ,726 0.50 BELT 18 1/4 120 1 60 gqCKDRA�f DAMPER, OR APPROVED EQUAL TRANE <br /> VAV-4 ROOM #210 S.O. 525 262.5 - - - - 8 15/12 0.40 VCCC-08 - <br /> VAV-5 ROOM �210 S.O. 525 262.5 - - - - 8 15/12 0.40 TRANE <br /> PUMP SCHEDU �E �����08 <br /> MARK INLET OUTLET FT. OF MAX. MOTOR CHAR. VAV-6 ROOM �210 S.O. 525 262.5 - - - - 8 15/12 0.40 TRANE <br /> N0. LOCATION SERVICE TYPE ��N � ��N � GPM HEAD RPM HP V PH CYC WEIGHT REMARKS VCCC-08 <br /> MACHWERY CONDENSER PACO #4095-5 OR VAV-7 ROOM #210 S.O. 525 262.5 - - - - 8 15/12 0.40 VCCCE 08 ' <br /> P-1 ROOM � 101 WATER � - - 690 65 1800 15 460 3 60 - APPROVED EQUAL , <br /> EQUIPMENT CHILLED PRIMARY - PACO VAV-8 ROOM �124 S.O. 550 275 - - - - 8 15/12 0.40 TRANE <br /> P-4 MEZZ. �201 WATER L - - 552 40 1800 10 460 3 60 - #4095-5 OR EQUAL VCCC-OS <br /> , .,�: <br /> EQUIPMENT CHILLED S�CONDARY - PACO � <br /> P-� MEZZ. �201 WATER L - - 552 80 1800 20 460 3 60 - #5095-5 OR EQUAL <br /> EQUIPMENT HEATING PACO �2012-1 oR CO �lDE�1SATE PUI� P A�1D RECEI�ER SET . <br /> P-10 L - - 125 140 1800 10 460 3 60 - <br /> MEZZ. �201 HOT WATER APPROVED EQUAL GPM MOTOR CHAR. TANK <br /> MARK DWG. HEAD <br /> EQUIPMENT HEATING PACO �2012-1 OR PER CAP, REMARKS <br /> P-11 MEZZ. �201 HOT WATER � - - 125 140 1800 10 46� 3 60 - APPROVED EQUAL N0. N0. PUMP PS�' HP V PH CYC GAL. <br /> CRP-1 - 12 60 2 460 3 60 15 ��WEIL" MODEL 2C-539 <br /> OR APPROVED EQUAL <br /> P-1 _ CHILLED IN- 1 1/2 1 1/2 32 28 1770 3/4 460 3 60 110 B�LL & GOSSETT � <br /> WATER LINE SERIES 60 SIZE 1 1/2A <br /> - - HOT WATER �N 1 1 7 10 2200 1 25 115 1 60 10 BELL & GOSSEI-f E/� PA� J � � I V TA I V r\� <br /> P 2 LINE � SLC-25 • <br /> MARK CAPACITY SYSTEM � <br /> N0. GALS. PRESSURE SERVICE REMARKS <br /> PSIG <br /> WAT E R C H I ��E R S ET-, 100 50 CHILLED WATER "TACO" MODEL PS 100 <br /> COMPRESSOR CHILLER CONDENSER ET-2 400 50 HEATING HOT WATER "TACO" MODEL PS 400 <br /> MARK LOCATION CAP. MOTOR WATER N� P p WATER N� P p REMARKS <br /> . ,{� <br /> KW ENT. LVG. OF �. GPM ENT. LVG. OF �- (1) MAX WATER VELOCITY <br /> N0. TONS INPUT V PH CYC GPM(1) �F °F PASS °F °F PASS P �U �IBI �lG SCHEDU �E �OR FOOD P �AZA EQUIP �IE�1T <br /> SHALL NOT EXCEED 8 FPS <br /> CH-1 MACHINERY 230 144 460 3 60 552 54 44 2 23 690 80 9Q 2 27 , " <br /> ROOM #101 NOM ITEM DESCRIPTION WORK REQUIRED REMARKS <br /> ROUGH-IN CONNECT 1/2" CW WITH STOP PROVIDE 1/2" ANGLE STOP WITH <br /> 6 COFFEE URN AND PIPE INDIRECT WASTE (FULL SIZE) FLEXIBLE RISER - CHROME FINISH. <br /> D O O R H EAT E R S � FROM DRAIN OUTLET TO FLOOR SINK <br /> COIL DATA FAN DATA N XT T UNIT. <br /> CAP. ROUGH-IN CONNECT 1 2" CW, TWO 1 2" HW, PROVIDE TWO SINK FITTINGS WITH CHROME FINISH, . <br /> MARK ENT. LVG. ENT. LVG. � THREE COMPARTMENT „ � � » SWING SPOUT AND BUILT - IN SHUT-OFF STOPS; : $` � <br /> AREA SERVED BTU/HR HEAD MTG. REMARKS O SINK THREE 2 W EACH WITH TRAPS AND 1/2 V. „ r <br /> N0. (1000) WATER WATER GPM �N �- CFM AIR AIR HP HT CHICAGO FAUCET N0. 445R, AND THREE 2 P-TRAPS, <br /> �F �F �F �F ROUGH-IN 8c CONNECT 1/2" CW, 1/2" HW, PROVIDE FAUCET WITH VACUUM BREAKER � <br /> DH OVERHEAD 3 .4 0 1 15 5 74 5 .5 24'* W�LOUVER-CONE DIFFUSER O WASH BASIN 1 1/2" W, 1 1/2" V COMPLETE WITN TRAP AND HOSE SIMILAR TO SS-1 FIXTURE <br /> • � • & STOPS - <br /> DH OVERHEAD 305.4 160 130 22 0.5 12,160 65 95 2 24'* ARMSTRONG AQ362NL-T23 WITH HIGH VELOCITY NOZZLE AND LIQUID CORE. <br /> 14 DOORS *MIN. ELEV. A.F.F., ELEC SERVICE 480V/3�, WEIGHT=600 LBS Q SERVICE SINK ROUGH-IN & CONNECT 3/4 CW, 3/4 HW, PROVIDE FAUCET WITH VACUUM BREAKER <br /> DH OVERHEAD , ARMSTRONG AQ362NL-T23 WITH HIGH VELOCITY NOZZLE AND LIQUID CORE. (FLOOR MOUNTED) 3 W & 2 V COMPLETE WITH 3 TRAP. AND HOSE SIMILAR TO SS-1 FIXTURE <br /> 15 DOORS 305.4 160 130 22 0.5 12,160 65 95 2 24 * *MIN. ELEV. A.F.F., ELEC SERVICE 480V/3�, WEIGHT=600 LBS <br /> PIPE INDIRECT WASTE (FULL SIZE) <br /> � � BEVERAGE AIR STAND FROM DRAIN OUTLET TO FLOOR , <br /> B SINK UNDER UNIT. <br /> ROUGH-IN CONNECT 1/2" HW WITH STOP r' <br /> H OT WAT E R C I R C U �ATO R S �9 B & B HOT CASE AND PIPE INDIRECT WASTE (FULLSIZE) PROVIDE 1/2" ANGLE STOP WITH FLEXIBLE <br /> MARK FT. OF MAX. MOTOR CHAR. FROM UNfT S DRAIN OUTLET TO OUTLET CHROME FINISH. <br /> N0. LOCATION SERVICE GPM HEAD HP RPM V PH CYC �PE REMARKS FLOOR SINK UNDER UNIT. <br /> HWC-1 INSIDE AHU-1 HOT WATER 38 10 1/4 1800 120 1 60 IN- BELL & GOSSETT LD3 20 B & B COLD CASE F OM 1UN T'DSIRDRAIN OUTLETULL SIZE) R E I E R E I V � E I MAG E <br /> 2,5,6 2,5,6 R E C I R C. L I N E O R A P P R O V E D E Q U A L � <br /> HWC INSIDE HOT WATER IN- BELL & GOSSETT LD3 FLOOR SINK UNDER ITEM 2 1 <br /> 3 & 4 AHU-3 & 4 RECIRC. 46 12 1/4 1800 120 1 �� LINE OR APPROVED EQUAL � I:\TIFF\MECH\40-BLDGS\40-005\140-005-4001 -M 111 .TIF � = Y <br /> ROUGH-IN CONNECT 1/2" HW <br /> 21 B & B HOT CASE WITH STOP AND PIPE INDIRECT WASTE PROVIDE 1/2" ANGLE STOP WITH FLEXIBLE � I:\TIFF\MECH\40-BLDGS\40-005\140-005-4005-M1 .TIF <br /> TO FLOORESINKOUNDER UNDRAW OUTLET OUTLET CHROME FINISH. � .\ \ \ <br /> 3 I TIFF MECH\40-BLDGS\40-005 140-005-4001 -M201 .TIF <br /> COO �If� G TOWERS <br /> PIPE INDIRECT WASTE (FULLSIZE) <br /> ENT LVG. AMB. N0. TOTAL MOTOR CHAR. 22 COLD CASE FROM UNIT'S DRAIN OUTLET TO <br /> MARK LOCATION NOM. GPM WATER WATER DEStGN OF FAN REMARKS FLOOR SINK UNDER ITEM 2� <br /> N0. TONS �F °F TEMP. °F FANS HP V PH CYC <br /> CT-1 NORTH SIDE OF 230 690 90 80 79 1 5 460 3 60 W� 4 KW <br /> MACH. RM. �101 PAN HEATER . <br /> OFFMAN �� <br /> N G I N E E R S <br /> 1601 Fifth Avenue,Suite 900�Seattle,WA 98101 I S S U E F 0 R P E R M I T : <br /> ph 206.623.0717�fax 206,624.3775 <br /> coffman.com <br /> LASTING creativiry�resuib�relationships <br /> SYM itEVIS10N BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTIT�E CURRENT REVISION SYMBOL DATE � <br /> ��L Sp� ACCEPTABILITY <br /> - -��T �MA�E �� s�rr � TNIS DESIGN AND/OR cH-cKEa SCHEDULES W5240458 03.05.18 � r <br /> A ACAD CONVERSION PERI . �ti � SPECIFICATION IS APPROVED sHEET � <br /> B 777X PALLETIZED RACEWAY TOOLS W5240458 CEI MS 03.05.18 BOE,�� � � � � N iN ER TiT�E 777X PALLETIZED RACEWAY TOOLS � <br /> � �, APPROVED BY DEPT. DATE n n � C � : <br /> CHECKED �y� � <br /> �o � 36611 9 � APPROVED B U 1 L D I N G 4 0�0� JOB N0. COMP N0. C <br /> � �'GISTEBE � t- <br /> �sSroNAL ��� aPPRovEo MECHANICAL MASTER EVERE-iT, Wq owc No. 40-005-M1c <br /> 3/5118 <br />