6/26/2019 City of Everett Page i <br /> 2:51:01PM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E1811-029 Site Address 810 90TH ST SW <br /> Applied 11/5/2018 Applicant Lot <br /> Approved 11/5/2018 Owner DIRTU LAURA D&GEORGE Block <br /> Issued 11/5/2018 Contractor BLUE FLAME HTG AIRE&ELECTRIC Tract <br /> Parent Permit No. M1811-018 Description MODIFY CIRCUITS FOR THE INSTALL OF FURANCES/AC Ar <br /> Notes <br /> Scheduled Completed Tune Inspector Result Remarks Inspector's Comments <br /> 1/15/2019 1/15/2019 ELEC 09-FINAL SKB CORRECTION (1/15/2019 2:12 PM SKB) <br /> Provide access to generator connections. <br /> Grounding electrode conductors cannot rely <br /> on the can they have to be in landed on the <br /> grounded bus.What is the depth of the <br /> conduit buried to the generator?Verify the <br /> ground rods.Provide manufactures <br /> instructions for using flexible gas piping to <br /> bond gas. <br /> 1/18/2019 1/18/2019 ELEC 09-FINAL SKB APPROVAL <br /> 1/18/2019 1/18/2019 ELEC 05-SERVICE SKB APPROVAL <br /> 1/18/2019 1/18/2019 ADMIN USE AKH APPROVAL <br /> ONLY** <br /> INSP12 <br /> C/PIAIrsYS TEM <br />