Laserfiche WebLink
GENERAL REQUIREMENTS <br />SUMMARY OF WORK <br />Project consists of cast in place concrete detention vault as shown on these Contract Documents used in <br />coordination with the Civil and other discipline's documents. <br />GOVERNING CODE <br />All design and construction shall conform to the 2018 International Building Code, ACI 350-06, and local <br />jurisdiction amendments. <br />Reference tuASTMand other standards shall refer tothe latest edition designated hvIBC Chapter 35. <br />Refer to the specifications for information in addition to that covered by these structural notes and <br />drawings. <br />DOCUMENT <br />Structural Documents shall beused inconjunction with Architectural CwcumentsforaUbiddingand <br />construction. <br />Drawings indicate general and typical details ofconstruction. Typical details and general notes shall apply <br />even ifnot specifically denoted on plans, UN0.Where conditions are not specifically indicated similar <br />details of' construction shall be used, subject to review and approval by the Architect and the SER. <br />These Contract Documents and any materials used inpreparation ofthem, including calculations, are the <br />exclusive property of the SER and can be reproduced only with the permission of the SER. <br />WARRANTY <br />The SER has used that degree of care and skill ordinarily exercised under similar circumstances by <br />members of the profession in this locale and no other warranty, either expressed or implied, is made in <br />connection with rendering professional services. <br />OWNER RESPONSIBILITY <br />The owner shall retain a Special Inspector to perform the special inspection requirements required by the <br />building official and asoutlined inthe Special Inspection section below. <br />..LAASH k wheel loads: <br />Citv of Everett larae Vactor truck wheel loads: <br />re <br />| <br />1 <br />®R <br />I <br />City of Everett standard Vactor truck wheel loads: <br />City of Everett standard Fire truck wheel loads: <br />� <br />' <br />� <br />LIVE LOADS-SMOVU <br />Numbering below isper IBC Section 16O31]: <br />4' 7^ <br />| 4' 8^ | <br />1. Flat -Roof Snow Load: <br />Pf <br />=126psf <br />I Snow Exposure Factor: <br />C° <br />= 1.0 <br />I Snow Importance Factor: <br />Is <br />=11 <br />4. Thermal Factor: <br />[/ <br />= 1.0 <br />Additional Items: <br />Ground Snow Load: <br />90 <br />= 15ps <br />Minimum uniform roof snow load <br />= 25 psf <br />FRONT AXLE: 8,00OLBS <br />REAR AXLE #1:32,0O0L0S <br />FRONT AXLE: 18,R0UB <br />REAR AXLE #1:22,875U8S <br />REAR AXLE #2:22,O75LBI <br />REAR AXLE #]:22,875L0S <br />REAR AXLE #4:22,875L0S <br />FRONT AXLE: 16798LDS <br />REAR AXLE #1:3l,665L8l <br />REAR AXLE #2:2l665LBS <br />FRONT AXLE: 19,000LBI <br />REAR AXLE #1:24,088LB3 <br />REAR AXLE #Z: 24,000LBS <br />LATERAL LOADS ' EARTHQUAKE <br />Numbering below isper IBC Section 16031.5: <br />1.Risk Category: U <br />2. Seismic Importance Factor: |, = 1.0 <br />3.K4apped Spectral Response Acceleration Parameters: S, = 1.394g; S, = 8I29 g <br />4.Site Class: D; FA = 1.0C Fv = 1.5 <br />5.Design Spectral Response Acceleration Parameters: Sns = 0L929g; Sm = 0.528g <br />6. Seismic Design Category: D <br />7.Seismic Response Coefficient: [s=8194 <br />8.Reoponse Modification Coefficient: Fh = l[; Rc = 1.0 <br />9. Analysis Procedure: Seismic Design of Liquid -Containing Concrete Structures, ACI 350.3-06 <br />DESIGN DOCUMENTS <br />Contractor shall verify all dimensions and all conditions at the job site, including building and site conditions <br />before commencing work, and be responsible for same. All discrepancies shall be reported to the Architect <br />before proceeding with work. Any errors, ambiguities and/or omissions in the contract documents shall be <br />reported to the Architect immediately, in writing. No work is to be started before correction is made. <br />Contractor shall verify and/or coordinate all dimensioned openings and slab edges shown on the contract <br />documents. Some dimensions, openings and embedded items are shown on the structural drawings. Others <br />may be required. Refer to architectural drawings for size and location of curbs, equipment pads, wall and floor <br />openings, architectural treatment, embeds required for architectural items and dimensions. Refer to mechanical, <br />plumbing, electrical and five protection drawings for size and location of all openings for ducts, piping. conduits' <br />etc. Submit openings to Architect for review. <br />Donot scale drawings. Use only field verified dimensions. When electronic plan files are provided for the <br />Contractor's detailing convenience, it shall be noted that the electronic files are not guaranteed to be <br />dimensionally accurate. The Contractor uses them at their own risk. The published paper documents are the <br />controlling Contract Documents. Electronic files of detail sheets and notes will not be provided. <br />CONTRACTOR- INITIATED CHANGES <br />Contractor- initiated changes shall be submitted in writing to the Architect for review and acceptance prior to <br />fabrication or construction. Changes shown on shop drawings only will not satisfy this requirement. <br />INSPECTIONS <br />The Contractor shall coordinate with the building department for all building department required inspections. <br />TEMPORARY SHORING AND BRACING <br />The Contractor shall provide temporary bracing as required until all permanent connections and stiffening have <br />been installed. The Contractor is responsible for the strength and stability ofall partially completed structures <br />including but not limited to concrete or masonry walls, steel framing and erection aids. The Contractor shall, at <br />their discretion, employ the aid of a licensed Structural Engineer to design all temporary bracing and shoring <br />necessary to complete the work described in these contract documents. The Contractor shall be responsible for <br />all required safety standards, safety precautions and the methods, techniques, sequences or procedures <br />uired in performing their work. For concrete construction refer to ACI 318 Section 2611.2"Removal of <br />Formwork". <br />SAFETY PROCEDURES <br />Contractor shall beresponsible for all safety precautions and the methods, techniques, sequences or <br />procedures required to perform the contractor's work. The Structural Engineer has no overall supervisory <br />authority or actual and/or direct responsibility for the specific working conditions at the site and/or for any <br />hazards resulting from the actions ofany trade contractor. The Structural Engineer has no duty to inspect <br />supervise, note' correct, or report any health orsafety deficiencies to the Owner, Contractors, mrother entities <br />orpersons atthe project site. <br />SHOP DRAWINGS AND SUBMITTALS <br />SHOP DRAWING & SUBMITTAL REVIEW (including Deferred Structural Components) <br />The contractor must review and stamp the shop drawings & submittals for review. SIR will only review <br />submittals for items shown on SEKdocumentx. Submittals for Deferred Structural Components will receive <br />cursory review bvSERfor loads imposed onprimary structure. SEkwill review shop drawings for general <br />conformance with design concept of the project and general compliance with the information given in the <br />Structural Contract Documents. Review of submittals does not constitute approval or acceptance of <br />unauthorized deviation from Contract Documents. <br />Corrections or comments made on shop drawings during this review do not relieve Contractor from <br />compliance with the requirements ofthe plans and specifications. <br />Contractor responsible for: <br />~ Reviewing, approving, stamping and signing submittals prior to submittal to Architect and SER <br />" Timing submittals to allow two weeks of review time for the SER and time for corrections and/or <br />reoubmitta| <br />~ Conformance 0urequirements ofthe Contract Documents <br />~ Dimensions and quantities <br />~ Verifying information to be confirmed or coordinated <br />^ Information solely for fabrication, safety, means, methods, techniques and sequences of construction <br />~ Coordination of all trades <br />` <br />Resubmittals shall be clouded and dated for all changes to the submittal. Only clouded portions of <br />nsubmitt |viUberevewedandSER'srevewstompapp|kestounlytheseaneas. <br />SUBSTITUTIONS <br />Substitutions shall be submitted in writing prior to submittal of shop drawings. Shop drawings bearing <br />substitutions will berejected. Submit engineering data tosubstantiate the equivalence ofthe proposed <br />items. The SER's basic services contract does not include review of substitutions that require re- <br />engineerinci of the item or adjacent structure. Nor does the SER's contract cover excessive review of <br />proposed substitutions. The fees for making these reviews and/or redesign shall be paid by the <br />Contractor. Reviews and approvals shall not be made until authorization is received. <br />SUBMITTALS <br />Shop drawings and material submittals shaUbesubmittedtotheAohbec and SERprior tnany fabrication <br />or construction for the following structural items. Submittals shall include one reproducible and one copy; <br />reproducible will be marked and returned. If deviations, discrepancies, or conflicts between shop drawings <br />submittals and the contract documents are discovered either prior to or after shop drawing submittals are <br />processed bvthe SER.the Contract Documents control and shall befollowed. <br />, Construction sequence description <br />~ Contractor quality control testing procedures when required in specifications <br />° Concrete mix designs <br />~ Concrete construction joint plans <br />~ Concrete accessories material specification, size and location <br />~ Reinforcing bar shop drawings and placing plans <br />° Reinforcing bar mill certificates shall beavailable upon request <br />~ Deferred Structural Components listed below <br />DEFERRED STRUCTURAL COMPONENTS <br />Components referred to as Deferred Structural Components shall comply with these notes. These <br />elements have not been permitted under the base building application. The Contractor will be required to <br />submit the component system documents to the building official for approval. The documents shall be <br />stamped and signed byanengineer licensed bythe state where the project is|ocated.Thedefened <br />structural components shall not be installed until the design and submittal documents have been <br />approved bythe building official. <br />Prior to building department submittal, the deferred structural components submittals shall receive <br />cursory review by SER for loads imposed on primary structure and general conformance with design <br />concept of the project and general compliance with the information given in the Structural Contract <br />Documents. Review of submittals does not constitute approval or acceptance of unauthorized deviation <br />from Contract Documents. Submittals of contractor -designed components shall include the designing <br />professional engineer's stamp and signature, as noted above. The submittal shall be approved by the <br />component vendor prior to review by the SER. The designing professional isresponsible for code <br />conformance and all necessary connections not specifically called out on architectural or structural <br />contract documents. <br />Submittals shall include details of connections to primary structure that indicate magnitude and direction <br />ofall loads imposed atpoint ofconnection. Design criteria shall beprovided with submittal and <br />calculations shall bemade available upon request. <br />The following list includes the items that are defined as Deferred Structural Components. Refer to other <br />discipline's contract documents for additional deferred components that may require structural design <br />and details. Connections of these elements shall not induce torsion on structural members. Deferred <br />Structural Components shall be manufactured, delivered, handled, stored' and field erected in <br />conformance with instructions prepared bythe component vendor. <br />Deferred structural components: <br />° Helical anchors <br />INSPECTIONS BY BUILDING OFFICIAL <br />The building official, upon notification, shall make structural inspections as required by local ordinance. <br />The inspection by the building official per IBC Section 110 will be separate from and in addition to the <br />special inspection and structural observation mentioned subsequently. <br />SPECIAL INSPECTIONS <br />ASpeda| Inspector shall be hired by the owner to perform the following special inspections per |B[ <br />Section 1704. See the specifications for additional requirements for special inspection and testing. The <br />architect, structural engineer, and building department shall be furnished with copiesofaUinspecbun <br />reports and test results. <br />Each contractor responsible for the construction of seismic force resisting system, designated seismic <br />system, or component listed in the statement of special inspections shall submit a written statement of <br />responsibility tuthe building official and the owner prior tothe commencement of work on the system or <br />component. The written statement shall beinaccordance with IBC Section 17O4.4. <br />See IBC Chapter 17: "Special Inspections and Tests" for more detailed requirements. <br />d1lifflW" 21 1 .11 JAI Pill <br />Frequency <br />Verification and Inspection <br />Reference <br />Cont. Periodic <br />Verify element materials, sizes, and lengths to comply with the <br />X <br />requirements <br />Determine capacities of test elements and conduct additional load <br />X <br />tests, as required <br />Observe driving operations and maintain complete and accurate <br />X <br />records for each element <br />Verify placement locations and plumpness, confirm type and size of <br />X <br />hammer, record number of blows per foot of penetration, determine <br />required penetrations to achieve design capacity, record tip and butt <br />elevations and document any damage to foundation element <br />For specialty elements: perform additional inspections as determined <br />by the registered design professional in responsible charge <br />Verification and Inspection Reference <br />Cont. Periodic <br />Verify materials below shallow foundations are adequate to achieve X77 <br />the design bearing capacity <br />Verify that excavations are extended to proper depth and have X <br />reached proper material <br />Perform classification and testing of compacted fill materials X <br />Verify use of proper materials, densities and lift thicknesses during X <br />placement and compaction of compacted fill <br />Prior to placement of compacted fill, observe subgracle and verify that <br />site has been prepared properly <br />Frequency <br />Verification and Inspection <br />Reference <br />Cont. <br />Periodic <br />Inspect reinforcement, including prestressing tendons, and verify <br />X <br />IBC 1908.4 <br />Reinforcing bar welding: <br />- Verify weldability of reinforcing bars other than ASTM A706 <br />X <br />AWS D1.4 <br />- Inspect single -pass fillet welds, maximum 5/16" <br />X <br />ACI 318:26.6.4 <br />- Inspect all other welds <br />X <br />Verifying use of required design mix <br />X <br />IBC 1904.1, <br />1904.2,1908.2-3, <br />Prior to concrete placement, fabricate specimens for strength tests, <br />X <br />IBC 1908.10 <br />perform slump and air content tests, and determine the temperature of <br />ACI 318:26.4, <br />the concrete <br />26.12 <br />inspection of concrete and shotcrete placement for proper application <br />X <br />IBC 1908.6-8 <br />Verify maintenance of specified curing temperature and techniques <br />X <br />IBC 1908.9 <br />Inspect formwork for shape, location and dimensions of the concrete <br />X <br />ACI 318: <br />being formed <br />26.11.1.2(b) <br />REPORT & GENERAL CRITERIA <br />Criteria outlined in the report listed below was used for the design of the foundations: <br />Geotezhnico/Engineering Rl <br />prepared byTerraconConsultants, Inc. (yWay15'2O20 <br />Contractor shall be familiar with recommendations in the above -mentioned report prior to start of <br />construction. Allowable soil pressure and lateral earth pressure are assumed and therefore must be <br />verified by Geubechnica| Inspector or the building official. |fsoils are found to beother than <br />assumed' notify the Structural Engineer for possible foundation redesign. For wet weather work, see <br />the Geotechnica|Report. <br />Unless noted otherwise, footings shall becentered below columns orwalls. <br />INSPECTIONS <br />All prepared soil -bearing surfaces shall be inspected by the owners Geotechnical Inspector (or <br />building uffida|) prior to placement ofreinforcing steel and concrete. Inspections shall be made per <br />IBC Table 17056. <br />BEARING VALUES <br />All footings shall bear on undisturbed soil and shall be lowered to firm bearing if suitable soil is not <br />found atelevations shown. Exterior footings shall bear aminimum of18^below the finished ground <br />surface. Footing elevations shown on plans (or in details) are minimum depths and for guidance only; <br />the actual elevations of footings must be established by the Contractor in the field working with the <br />Geotechnica||nxpecor. <br />Allowable vertical bearing soil pressure = 2,000 psf <br />SU0GRADE PREPARATION <br />Prepare subgrade per the Geotechnical Report, summarized as follows: All footings shall be cast on undisturbed <br />firm natural soils that are free of organic materials. Footing excavation shall be free of loose soils, sloughs, debris <br />and free ofwater utaUtimes. If organic silt and/or fill material is encountered at subgrade elevations, overexcavate <br />a minimum of Z-O" below the design foundation subgracle elevation prior to placing footings. Theovmrexcavated <br />areas shall be beckOUed with structural 0| compacted to 95% proctor perASTk4 D-1557 or a lean concrete mix. <br />EXISTING UTILITIES <br />The Contractor shall determine the location of all adjacent underground utilities prior to any excavation, shoring. <br />pile driving, orpier drilling. Any utility information shown on the plans and details are approximate and not <br />verified by the SER. Contractor is to provide protection of any utilities or underground structures during <br />construction. <br />DRAINAGE <br />Drainage systems, including foundation, roof and surface drains, shall be installed as directed by the Geotechnical <br />Report. Vapor retarder placed below slab -on -grade shall conform to ASTM E 1643 and ASTM E 745. <br />RETAINING WALLS/BASEMENT WALLS <br />Grade nneither side ofconcrete walls shall not vary bymore than 12^'UNO. Slope ofbackfi||shall not exceed 2H <br />to 1\( UNO. 8ackfi|| behind all retaining walls with free draining' granular fill installed per the Gootechnica| Report. <br />Design pressures used for the design ofretaining walls are based on fully submerged conditions. <br />Active earth pressure = 80PCF <br />A1'restearth pressure = 90P[F <br />Passive earth pressure = 280P[F <br />Coefficient offriction (factor ofsafety of1.S included) =0.45 <br />Provide temporary shoring for tops of walls if backfill is placed prior to the supporting structure being constructed. <br />Supporting structure is the floor framing and sheathing completely installed and attached to perpendicular walls. <br />PILES AND PIERS GENERAL CRITERIA <br />Pile orpier lengths indicated ondrawings are estimated; actual length shall be determined infield byGeotechnica| <br />Inspector. For bidding purposes, the contractor shall provide an add/deduct value per foot of pile/pier length. <br />This value shall be applied to variations in actual lengths as compared to estimated lengths. <br />The contractor shall determine the location ofall adiacentundorgroundutilities prior todrilling ordriving <br />operations. Hole drilling shall beperformed vvithou�loss ofground and without endangering previously installed <br />piles. Refer to the Geotechnica| Report for recommended drilling or driving procedure. Alternate piles shall be <br />placed and completed so that at least 24 hours are allowed for the concrete to set prior to drilling adjacent piers. <br />Pile or pier types other than those indicated on the drawings may be submitted as a Substitution. Optional piles <br />must be supported on the same soil strata as the piles shown on the drawings. If the configuration of the piles is <br />different from the contract documents, the modification to the pile caps must also be designed by the contractor <br />and submitted with the Substitution. A2-weekminimum time allowance must bemade for the engineer toreview <br />all optional pile and pile -cap design. <br />Inspections shall be made by the Geotechnica| Inspector per IBC Table 17057or 1705.8. <br />HELICAL PILES <br />Helical Piles shall conform to geotechnical report recommendations for minimum required loads shown on plans. <br />Helical Piles shall meet the following criteria: <br />Minimum Depth 10ft below base of foundation <br />Installation Criteria 5'000ft'|b minimum torque <br />Testing Criteria (2)anchors to20096ofdesign load <br />Special Inspections Per IBC 1705.9 <br />CONCRETE <br />CAST -UN -PLACE CONCRETE <br />Concrete materials shall conform to the following: <br />Portland cement: <br />Type 1'ASTM[1S0 <br />Fly ash (if used): <br />A5TK4 [618dass For[ <br />Slag cement (if used): <br />ASTK4[989 <br />Lightweight aggregates: <br />lightweight aggregates shall not beused without <br />prior approval ofSEKand building department <br />Normal weight aggregates: <br />A5TW[33 <br />Sand equivalent: <br />ASTM[33 <br />Water: <br />Potable per ASTM C94 <br />Air entraining admixtures: <br />ASTK4 [260 <br />Chemical admixtures: <br />A6TWC4O4 <br />Floweb|oconcrete admixtures: <br />ASTK4[lO17 <br />Durability requirements ofconcrete mixes shall conform tobuilding code. These requirements include <br />water'cemenddou» material ratios' minimum compressive strengths, air entrainment type of cement, and <br />maximum chloride ion content. <br />Strength MaxMaxTotal Air and Classes <br />Location Vc <br />| |Agg Size | VVyC! Content(PEI) Ratio <br />| | � T <br />F S <br />LEAN MIX SOIL REPLACEMENT 1.5 SACK <br />UNDER FOUNDATIONS 1,500 SAND CEMENT F2 SO WO C1 <br />CONCRETE MIXTURES <br />Mixes shall be proportioned to meet compliance requirements of ACI 350 Section 5.2. Slump, Vy/[ratio, <br />admixtures and aggregate size will bedetermined bythe contractor. Submit documentation ofconcrete <br />mixture characteristics for review by the SER before the mixture is used and before making changes to <br />mixtures already in use. Documentation shall comply with AC| 350Sedion 5.3.3. <br />All concrete, including slab on grade, shall contain an acceptable water -reducing admixture conforming to <br />ASTM C494 and be used in strict accordance with the manufacturer's recommendations. <br />All concrete which is exposed to freezing and thawing in a moist condition or exposed to deicing <br />chemicals shall contain anair entraining agent, conforming toASTK4[26O. Total air content shall be <br />adjusted per A[|]5Ufor mix designs with smaller nominal aggregate size. The amount ofentrained air <br />shall bemeasured atthe discharge end ofthe placing nozzle. Entrained air shall beasnoted ±1.0Y6by <br />volume. Air -entrainment shall not be used at slabs that will receive a smooth, dense, hard -troweled finish. <br />Trucks hauling plant -mixed concrete shall arrive on -site with a field ticket indicating the maximum gallons <br />of water that can be added at the site not to exceed the total water content in the approved mix design. <br />Concrete shall be deposited as nearly as practicable in its final position to avoid segregation due to <br />rehandling orflowing. Concrete shall be thoroughly consolidated by suitable means during placement <br />and shall be thoroughly worked around reinforcement, embedded items, and into corners of forms. <br />��` <br />Pmmit� P�2�7�� ��� <br />Site Address: 2200LYMP|C8;VO <br />| <br />Owner: CAT A[YSTCAPOFAL <br />Tenant: VAOUTPATIENT CLINIC <br />App.Date: 7/22-/I020 <br />Proposed Use: DEMO <br />Description: BTORK0VVATERuKU[TFOR NEVVVA <br />OUTPATIENT CUW|C-REVISION ARI0ISSUANCE <br />Reviewed <br />7,�Qffice set Job Site Set Fire/Planning Set <br />190NvW^zEEaTPEETSUITE oo| osNVsRooLORxou8nuo2 <br />11 - - , 1� I F�" N Di" <br />ffl, I g <br />Ali NOW <br />Sv F, H`11,1 <br />M_ <br />}2OlFirst Avenue South, Suite 310 <br />Seattle, Washington 98134 <br />ISSUANCE: DATE: <br />PERMIT SET 05/26/2021 <br />APPROVED <br />PUBLIC WORKS DEPARTMENT <br />By <br />DATE <br />CITY OF EVERETT REVIEWED FOR PERMIT <br />SHEET NUMBER: <br />