EVERETT PUBLIC SCHOOLS <br /> Od <br /> SECURITY FENCE AND GATE PROJECT zN <br /> Z�� <br /> _ � <br /> L U <br /> CASCADE HIGH SCHOOL m <br /> 801 E CASINO RD., EVERETT, WA 98203 _ <br /> DESIGN TEAM <br /> OWNER: PROJECT ARCHITECT: TELECOM AND SECURITY ENGINEER: 2727 Oakes Ave. <br /> EVERETT SCHOOL DISTRICT NO. 2 BOTESCH, NASH & HALL ARCHITECTS, P.S. HARGIS ENGINEERS suite 100 <br /> Facilities and Planning Department 2727 Oakes Avenue 1201 3rd Avenue, Suite 600 Everett,WA 9e201 <br /> 3900 Broadway Suite 100 Seattle, WA 98101 REVII <br /> Everett, WA 98201 Everett, WA 98201 (206) 448-3376 Z�, ADDENDUM q2 9-5-24 <br /> (425) 385-4190 (425) 259-0868 <br /> GENERAL NOTES ABBREVIATIONS SYMBOL LEGEND PROJECT DATA DRAWING INDEX <br /> All construction shall comply with the 2015 International Building Code(IBC), A L GENERAL <br /> Washington State regulations for barrier-free design,Washington State Energy A.5. ANCHOR BOLT L LONG;LENGTH DATUM POINT PROJECT NORTH MAJOR APPLICABLE CODES <br /> Code,and all applicable local codes,ordinances and standards. ABv ABOVE LAM LAMINATE GL0 COVER SHEETINTERNATIONAL BUILDING CODE-2018 <br /> A/C AIR CONDITIONING LAV LAVATORY ,�1 <br /> 2. The Contractor is to Verify all existing conditions,dimensions,details,etc. ACT ACOUSTICAL CEILING TILE Ib.a FOUND `r WASHINGTON STATE BUILDING CODE <br /> and notify the Owner and Architect of any and an discrepancies prior to AD AREA DRAM LINEAR FOOT DETAIL NUMBER ARCHITECTURAL <br /> A ADJUSTABLE ELL, LIVE LOAD CHAPTER 5-50 WAC <br /> proceeding with the work. A ABOVE FINISH FLOOR LOC LOCATION INTERNATIONAL PLUMBING CODE-2018 3„ <br /> 3. Do not scale drawi g y ALUM ALUMINUM LT LIGHT 0 NORTH INTERNATIONAL MECHANICAL CODE-2018 ASI.O SITE PLAN <br /> ngs;dimensions govern, The Contractor shall notify the ALT ALTERNATE LP LOW POINT A'0°° AASHING70N STATE ENERGY CODE-2018 41.0 FENCING PLANS REGISTERED <br /> owner and Architect immediately of any and all discrepancies. The drawing APPROX APPROXIMATE AB.O ORNAMENTAL GATE DETAILS ARCHITECT <br /> scales are indicated to proportion ARCH ARCHITECT M ,� <br /> provide visual rtion and should be verified with ASPH ASPHALT SHEET NUMBER DOOR NUMBER AB.I DETAILS <br /> similar drawings and listed dimensions. AUTO AUTOMATIC MAS MASONRY OCCUPANCY(CHAPTER 3Z NO12EW M <br /> A44. AGGREGATE M� MATERIAL E ELECTRICAL STATE OE WASHINGTON <br /> 4. All dimensions are to be center line of stud,or face of concrete wall, unless MDH MECHANICAL DETAIL NUMBER <br /> noted otherwise. B MFD MANUFACTURED WINDOW NUMBER E0.01 SECURITY AND TELECOM LEGEND AND DRAWING INDEX <br /> eDOG BIBOiILDING MFR MANUFACTURER 0 E0.02 SECURITY AND TELECOM GENERAL NOTES <br /> 5. where devices or items or parts thereof are referred to in singular, it is BLK BLOCK MH MANHOLE A_oBO 1 EL00 SECURITY FENCE PLAN-SITE <br /> intended that such shall apply to as many such devices, items or parts as are BLKG BLOCKING MIN MINIMUM <br /> d to to the work. BE. BELOW NEC MISCELLMNEI E6.10 BUILDING I -SECURITY FLOOR PLAN <br /> require properly campe BM BEAM Mo MASONRY OPENING SHEET NUMBER WALL TYPE E6AI BUILDING I - ENLARGED SECURITY PLAN <br /> 6. It shall be the responsibility of the Contractor to locate all existing utilities B.M. BENCH MARK MTL METAL E6.20 BUILDING 3-SECURITY FLOOR PLAN <br /> BRG BEARING 00 <br /> whether shown hereon on not and to protect them from damage. The BSMT BASEMENT N SECTION NUMBER E6.21 BUILDING 3- ENLARGED SECURITY PLAN <br /> Contractor shall bear all expense of repair or replacement of utilities or other STn BOTTOM N NORTH E6.30 BUILDING 5-SECURITY FLOOR PLAN <br /> property damaged by operations in conjunction with the execution of his work. BTWN BETWEEN NA NOT APPLICABLE E6.31 BUILDING 5- ENLARGED SECURITY PLAN <br /> NIC NOT IN CONTRACT q-000 <br /> 7. Tha contractor will Verifyd conform to an re is of all unlit C No NUMBER E6.40 BUILDING 7-SECURITY FLOOR PLAN <br /> an ayiremen Y CAB CABINET NOM NOMINAL E6.41 BUILDING 7- ENLARGED SECURITY PLAN <br /> companies,onlaes noted otherwise in the plans and specifications. c e. CATCH BASIN KITS NOT TO SCALE SHEET NUMBER ROOM NAME <br /> CJ CONTROL JOINT i E801 SECURITY DETAILS <br /> a. Existing elevations and locations to be joined shall be Verified by the CL,C CENTER LINE 0 ROOM E8.02 SECURITY DETAILS <br /> contractor before construction layout. If they differ from those shown on the aG CEILING oM OVERALL WALL SECTION LETTER E0.01 SECURITY ONE-LINE DIAGRAM <br /> crowing s,the Contractor shall notif the Architect, so modifications can be made CUR CLEAR O.C. ON CENTER(S) 001 <br /> g y OCR CLEAR OD OUTSIDE DIAMETER O E9.02 SECURITY ONE-LINE DIAGRAM <br /> before proceeding with the work. cnu CONCRETE MASONRY UNIT OP OPENING E9.03 ELECTRICAL ONE-LINE DIAGRAMS <br /> m CLEAN OUT OFF OPPOSITE q-000 ROOM NUMBER Ed 04 ELECTRICAL ONE-LINE DIAGRAMS <br /> q. All debris shall be removed from the premises and all areas shall be left in COL COLUMN OYC I. OWNER FURNISHED- E10.01 ELECTRICAL PANEL SCHEDULES <br /> CONE CONCRETE CONTRACTOR INSTALLED o <br /> broom clean condition at all times. CENT CONTINUE CONTINUOUS SHEET NUMBER <br /> ! ) o.F.o.l. OWNER FSTALLED- E10.02 ELECTRICAL PANEL SCHEDULES se <br /> CPR COUNTER OWNER INSTALLED E10.03 ELECTRICAL PANEL SCHEDULES U <br /> theThe Contractor shall take all necessary precautions to ensure the safety of CPT CARPET 1 INTERIOR ELEVATION NUMBER �rF/ <br /> the occupants and workers at all times. GPO.I. CONTRACTOR FURNISHED- P <br /> OWNER INSTALLED PER PERIMETER <br /> II. Fire a%tinguishars� Verify the requirements and locations with the fire PL PLATE �SHIEET <br /> marshal.The Contractor is to su I fire extin uishers and cabinets,as ed D P.L. PROPERTY LINEand/or as indicated an the drawi g. g rogpir DBL DOUBLE PLAM PLASTIC LAMINATE <br /> ngs. DF DRINKING FOUNTAIN PLBG PLUMBING <br /> DIM 9 DIAMETER PLF POUNDS PER LINEAR FAT2, NUMBER <br /> 12. Soled insulate all plumbing walls. DIM DIMENSION PITWD PLYWOOD <br /> DISP DISPENSER PIT PAINT(ED) <br /> 13. The plans and specifications are minimums and where details are not pp DOWN FIR PAIR <br /> specifically shown,consistent practices shall be used. Codes and ordinances take DTL DETAIL PREFIN PREFINISHED <br /> precedence Over Ions and fications and whenever incon6istencia6 exist,it will D5 DOWNSPOUT PS POUNDS PER SQUARE FOOT -HR WALL <br /> p pea' PS I POUNDS PER SQUARE INCH <br /> be the Contractor's responsibility to immediately notify the Owner and provide PTN PARTITION <br /> acceptable corrections of m additional charge. E E EAST PVC POLYVINYL CHLORIDE -2-PR WALL <br /> 14. Use 5/8-inch GWB,Type X, in all locations unless noted otherwise. BE EACH <br /> EXPANSION BOLT R s <br /> EJ EXPANSION JOINT RA RETURN AIR <br /> 15. The Contractor shall provide mechanical, plumbing and electrical permits. EL ELEVATION RCP REFLECTED CEILING PLAN 2-HR SMOKE WALL <br /> ELEC ELECTRIC(AL) RD ROOF DRAIN <br /> RDPT RECEPTACLE <br /> I6. Sheet-metal flashing at skylights,roof hatches,rooftop mechanical units, E° DUAL REF REFERENCE/REFRIGERATOR M <br /> EQUIP EQUIPMENT 4-HR WALL <br /> sonny head sills,soffits, parapet walls,reglets,a%pansian joints,etc.,shall EN EACH WAY REINF REINFORCE(MENT) <br /> be installed as recommended by SMACNA(Sheet Metal and Air Conditioning EXIST EXISTING RD'D REWIRE(D) t� <br /> Contractors National Association)manual. ENT EXTERIOR RM REV�19E(D);REVISION;REVERSE CD 0 00 <br /> R.O. ROUGH OPENING <br /> 17. Penetrations through rated construction shall bs protected by U.L.Listed T R.o.W. RIGHT OF WAY <br /> stop materials and methods per IBC 2015. roll FFou°pMDIN T ONRru. ROOF roF uwT KEYNOTE NUMBER C� <br /> FE FIRE EXTINGUISHER RE RESILIENT BASE Q <br /> I8. Sealing caulking and weather-stripping shall be installed to provide a FEC FIRE EXTINGUISHER CABINET (n <br /> complete building envelope FIN FINISH SA <br /> S S SOUTH 0 UQ <br /> FIN FLR FINISH FLOOR SAN SANITARY <br /> Iq. Prior approval is reayired on an changes on alterations to the approved plans. sB SPLASH BLOCK DEMO KEYNOTE NUMBER v, <br /> FLR,FL. FLOOR <br /> 20. Contractor to preserve existing trees and use coution around major roots. r�°R FLUORES ENN4)/FIRE RATED 5C `STUD CARE M^T�I L^C LLD <br /> SLH SCHEDULE IH I'-I IVL <br /> I'T (,) F00'f SD STORM DRAIN 100 Cz Of <br /> FTG FOOTING SEAL SEALANT LLJ <br /> ED/FURRING SF SOUARE FOOT <br /> FUR FURR t_t_ <br /> SAT SHEET W U00 LW <br /> G SIM SIMILAR PICTURE NUMBER <br /> 4A GAGE,GAUGE SPED SPECIFICATION <br /> GALV, GALVANIZED DSO SQUARE <br /> GS GRAB BAR SERV SERVICE O <br /> VICINITY MAP 4C 4ENERAL CONTRACTOR `ES SANITARY SEWER REVISION CLOUD os rvo. <br /> GL GLA%,GLAZING EST SOUND 55 STEEL 22-1018 <br /> 4W8 GYPSUM WALLBOARD-ttPE X ETC, SOUND TRANSMISSION CLASS <br /> STD STANDARD <br /> t1 5TC STEEL REVISION NUMBER DRAWN Br - <br /> m hsore STS STORM SEWER <br /> �.%ry meixei v rvs a ear Geneve sle nic.., CARE STRUCT STRUCTURAL;STRUCTURE <br /> HDR HEADER 0 <br /> ri aAp�sys {.° Y I p HOW HARDWARE SEEP SUSPEND(ED) Permit#: PW2411-016 crvec%eD er AM <br /> I 5 4 i HDWD HARDWOOD <br /> f -f t i '� HM HOLLOW METAL 51 STAIN 6 VARNISH Site Address: 801 E Casino Rd <br /> ` ENS STORM WATER SEWER <br /> uorslz HORRONTAL Owner: EVERETT SCHOOL DIST 2 <br /> 0 n094 HIP ��TPOWER T App.Date: 11/14/2024 <br /> T.O.C. TOP OF CURB PERMIT SET <br /> a }} WT4 HEATING TELE TELEPHONE Description: Cascade High School Security Fencing And Gates <br /> v q 9 HTR HEATER - - SECTION LETTER <br /> xzwoQ HT <br /> HEATING,VENTILATING TEMP TEMPORARY <br /> er."mu s.IswQ °n°T11L h.. // AND AIR CONDITIONING TV TELEVISION RAVE XX XX ��i�di2o2d <br /> _.: V NW HOT WATER T.O.B. TOP OF BEARING <br /> �,¢ t x Commune TO TOP OF PARAPET <br /> T.O.S. TOP OF STEEL <br /> mvee� r tee" ,e Tfe seen r�erveoQ�/ T.O.W. TOP OF WALL <br /> 'y ' a ID IN5IDE DIAMETER TYP TYPICAL <br /> ID EVERETT City of Everett Permit Services <br /> e"b[ <br /> e�m"e1 "4 / Tx REVIEWED FOR CODE COMPLIANCE COVER SHEET <br /> iN E(^) INCLUDE U,V,W & Y By Review Discipline:Public Works INSUL INSULATION <br /> T INT INTERIOR V VOLT A <br /> I-SITE ..A- VE TION T. VINYL COMPOSI TILE <br /> RT VERTICAL COLUMN GRID REFERENCE <br /> ,e.oe.esm�e0 J v 9 Y <br /> Reviewer:Ably Tse a e <br /> L ____J h,. JET olsT W WEST Date:11115@024 <br /> Pv 0 sI IN WITHER Review Status:Approved for Permit <br /> •� rvmevaa e�Q ¢ {� \. ,y a g^Cog KW K KILOWATT HIDWOODR CLOSET <br /> WH WATER HEATER <br /> GAF Op,uh tey - HT WITHOUT <br /> v0'� £ ,a oe em sou w.v n,� /i` WEIGHT Gi-O <br /> W W F- WELDED WIRE FABRIC <br /> W W M. WELDED WIRE MESH <br /> rQ e 4 .9 <br /> oe. YD YARD <br />