Permit#: M22 LO-099 <br /> Site Address: 192C 100TH ST SE BLDG A <br /> SubjectTo Field Inspection Owner. SEA-MAR COMMUNITY HEALTH CENTER <br /> Tenant SEA MAR COMMUNITY HEALTH CENTERS <br /> HVAC ABBREVIATIONS HVAC LEGEND HVAC NOTES App P,,tp te: 10/16/2022 <br /> Proposed Use:COMMERCIAL MECHANICAL(PLAN REVIEW <br /> REQUIRED) <br /> AFF ABOVE FINISHED FLOOR 1. DUCT INSULATION TO NzET THE REQUIREMENTS OF SECT- De—peon: MODIFY EXISTING DUCT SYSTEM,ADD <br /> BOO BACKDRAFT DAMPER 0 INL NE EXHAUST FANS O ION C403.10 OF THE 20',8 WSEC AND SECTION 604 OF EXH1 WSr FAN,DUCTWORK FOR NEW <br /> BTUH BRITISH THERMAL UNIT PER HOUR GR PLA <br /> CD CEILING DIFFUSER THE IECC(INTERNATIONAL ENERGY CONSERVATION CODE). Reviewed By <br /> ��Lt Date: o .s Z�ZL <br /> CFM CUBIC FEET PER MINUTE ROOFTOP EXHAUST FAN 2. SMOKE DETECTOR(S)INSTALLED IN MAIN RETURN AIR Dm_e set ;N1_iob Site Set _Fire/Planningset <br /> CU CONDENSING UNIT 0 DUCTS PER SECTION 606 OF THE 2018 IMC.HVAC SMOKE <br /> DB DECIBEL DUCT DETECTORS SHALL SHUT DOWN POWER TO THE <br /> DH DUCT HEATER UNIT UPON ACTIVATION AND A"SUPERVISORY"ZONE SHALL THIS SET OF <br /> DOAS DEDICATED OUTSIDE AIR SYSTEM SIDEWALL EXHAUST FAN BE INITIATED AT FIRE ALARM PANEL UPON SMOKE DUCT R HAL <br /> ON DOWN BE ON J <br /> EC EVAPORATOR COIL DETECTOR ACTIVATION.2018 IMC SECTION 606.4&604.6.1. <br /> EER ENERGY EFFICIENCY RATIO 3. SUPPLY&RETURN AIR DUCT IS MIN.OUTSIDE <br /> UNCONDITIONED U ^V \y/ M1 <br /> EF EXHAUST FAN VAV FAN BOX SPACES&MIN.R-8 WHEN LOCATED OUTSIDE OF BUILDING u�J 1J �/ nu u <br /> EG EXHAUST GRILLE AS PER THE 2018 WSEC C403.10.1.2. �10�0��W ��EOM <br /> ERV ENERGY RECOVERY VENTILATOR 4. ALL SINGLE PACKAGE HVAC UNITS SHALL BE INSTALLED uuuul uuuu uu JU <br /> ESP EXTERNAL STATIC PRESSURE CEILING EXHAUST FAN WITH ECONOMIZERS PER MANUFACTURER'S INSTALLATION AIR CONDITIONING-HEAT PUMPS-REFRIGERATION- <br /> EXH EXHAUST <br /> FCU FAN COIL UNIT INSTRUCTIONS PER 2018 IMC,SECTION 403 AND SHALL CONTRACTOR'S LICENSE NUMBER: UNIVERI 159RF <br /> OPERATE PER 2018 WSEC,SECTION C403.5.1. AUBURN: (253)939-5501 TACOMA <br /> FD FIRE DAMPER,FLOOR DRAIN O GAS METER (253)922-3141 <br /> SEATTLE: (253)839-212E FAX: (253)735-3432432 <br /> FPM FEET PER MINUTE 5. EQUIPMENT INSTALLATION INSTRUCTIONS TO BE ON-SITE <br /> FSD FIRE AND SMOKE DAMPER ZD12 FOR INSPECTIONS. P.O.BOX ERSAL AFRIGERUB 70NWAS DRAWIN-201 <br /> GA GAUGE VVi DAMPER ©UNNERSAL REFRIGERATION DRAWING-2001 <br /> GF GAS FURNACE 6. ALL HVAC EQMT.TO BE LABELED TO THE SPACE SERVED. <br /> GRD GRILLE,REGISTER,DIFFUSER 7. DUCTS TO BE SUPPORTED AT EACH DIRECTION CHANGE z <br /> HP HORSEPOWER,HEAT PUMP T THERMOSTAT VERTICAL AT 124,MAX.,HORIZONTAL AT 10'-0"MAX. O <br /> ID INSIDE DIMENSION WITH STRAP,OR 8'-0"MAX.TRAPEZE SUPPORT. L <br /> IHP INDOOR(SECTION)HEAT PUMP n- <br /> IRH INFRARED HEATER B. THERMOSTAT TO BE SEVEN-DAYTYPE AND HAVE NIGHT <br /> KW KILOWATT T-BAR SUPPLY DIFFUSER SETBACK WITH 5 DEGREE DEADBAND. U <br /> M <br /> MCD MOTORIZED CONTROL DAMPER THOUSAND BTU PER HOUR FE <br /> 9. THE HVAC INSTALLATION SHALL BE COMPLETE WHEN ALL LU <br /> 0 <br /> NC NOISE CRITERIA CD SECTIONS OF 2018 WSEC C408 HAVE BEEN SATISFIED.THIS <br /> NIC NOT IN CONTRACT ❑ T-BAR RETURN GRILLE SHALL INCLUDE AS-BUILT DRAWINGS,SUBMITTALS,0&M O D <br /> MANUALS,SYSTEM BALANCE REPORT,AND A COMMIS-NOT TO SCALE cn <br /> OBD OPPOSED BLADE DAMPER SIONING REPORT. �j <br /> OC ON CENTER Z HARDLID SUPPLY DIFFUSER 10.DUCT SEALING SHALL MEET REQUIREMENTS OF 2018 WSEC LLI <br /> OD OUTSIDE DIMENSION OR DIAMETER <br /> C403.10.2. DUCT WORK WHICH IS DESIGNATED TO w <br /> OHP OUTDOOR HEAT PUMP OPERATE AT PRESSURES ABOVE 1/2"WATER COLUMN a <br /> OSA OUTSIDE AIR HARDLID RETURN GRILLE <br /> STATIC PRESSURE SHALL BE SEALED AS FOLLOWS: <br /> OSCI OWNER SUPPLIED CONTR.INSTALLED LU FD �— FIRE DAMPER � I <br /> POC POINT OF CONNECTION 1. STATIC PRESSURE 1/2INCH TO 2INCHES:SEAL ALL <br /> RA RETURN AIR TRANSVERSE JOINTS AND LONGITUDINAL SEAMS. p p <br /> RAG RETURN AIR GRILLE SPIRAL LOCK SEAMS IN ROUND AND FLAT OVAL DUCT <br /> RPM REVOLUTIONS PER MINUTE FSD FIRE SMOKE DAMPER WORK DO NOT REQUIRE SEALING;HOWEVER,OTHER ; <br /> RTU ROOFTOP UNIT SEAMS SHALL BE SEALED. DJ <br /> SA SUPPLY AIR VOLUME DAMPER 11.2018 WSEC FORMS,DUCT PLANS,BALANCING FEATURES, cc <br /> SG SUPPLY GRILLE AS WELL AS VENTILATION REQUIREMENTS(AS PER TABLE <br /> SP STATIC PRESSURE 403.3.1.1,2018 IMC MINIMUM VENTILATION RATES)AND <br /> SSG SIDEWALL SUPPLY GRILLE SD SMOKE DETECTOR OCCUPANCY,ALONG WITH A MECHANICAL PERMIT AT THE <br /> TBD TO BE DETERMINED TIME OF THE TENANT IMPROVEMENT PERMIT. CID <br /> TG TRANSFER GRILLE FLEXIBLE DUCT SA RA <br /> TYP TYPICAL O <br /> UH UNIT HEATER ® IN <br /> VFD VARIABLE FREQUENCY DRIVE ROUND DUCT UP SCOPE OF WORK VTR VENT TO ROOF <br /> VVT VARIABLE VOLUME AND TEMPERATURE JOB# 22X)OC LU <br /> O ROUND DUCT DOWN 1. INSTALL(1)EXHAUST FAN W./ASSOC.VENTING. r Q <br /> 10x10 CD 2. MODIFY EXISTING DUCT DISTRIBUTION SYSTEM TO BEST L� <br /> 1 CFM-CD DIFFUSER TAG ACCOMMODATE NEW TENANT IMPROVEMENT FLOORPLAN. <br /> 3. INSTALL DUCTWORK,GRILLES&REGISTERS. L u <br /> _J �� LL <br /> APPROVED �..1 W OI6d CommuNp•,Planning 6 Eeonomfc Dewbpngnt � <br /> PLANNING DEPARTMENT 1 <br /> NNI DATE:I o z (�j W <br /> l o a: w <br /> a < <br /> �'- � <br /> E'er T_ <br /> Additional Permits Are Required C;� O <br /> For This Project To Include: `` r <br /> aAfrr a /5 4✓�EPE�DC✓f UeQr SuoP6�r ❑ Plumbing ❑Sprinkler L� <br /> �LAf /tYL4Cry 4 PE/L QScF /6 tr L/r Mechanical Fire Alarm �il <br /> Electrical r n � <br /> EXCE6ps ZD LBS. ") <br /> T <br /> PRINT/PLOT D>TE: <br /> FAN SCHEDULE <br /> DRAFTER: <br /> �'ID BRAND NAME MODEL NUMBER CFM SP HP/AMP FLOW WPH SOUND DUCT LOCATION ARW <br /> RATING <br /> DESIGNER: <br /> EF-1 NUTONE QTXEN150 150 .10 .5 A CV 120/1 1.4 SON ES 6"0 I.T.ROOM SS <br /> PROJECT MANAGER: <br /> SS <br /> JOB NUMBER: <br /> :'iTY CJF EyERETT 22xxx <br /> REVIEWED FOR PERMIT SHEET NUMBER: <br /> M-C <br /> PENDING CITY APPROV/ L_ <br /> NOTE:These plans are diagrammatical only. <br /> Please verify all dimensions at job site. <br />