Laserfiche WebLink
0:77. CITY OF EVERETT <br /> Public Works Department <br /> September 12, 2018 <br /> Ariana Adireh <br /> Ariana Designs, LLC <br /> 12400 SE 38th St., STE 50753 <br /> Bellevue, WA 98006 <br /> info@ariid.com <br /> Owner: Damien Properties <br /> Job Address: 4522 Evergreen Way <br /> Plan Check No: B1808-017 <br /> RE: Building Permit Review Letter <br /> Dear Ms.Adireh, <br /> In response to the application for a building permit, the plans have been examined and you are <br /> advised that revisions may be necessary before a permit can be issued. Please review and <br /> respond to the comments below. <br /> NON-STRUCTURAL <br /> 1. The glazing adjacent to the door in the conference room should be shown as safety <br /> glazing. Section 2406.4.2 <br /> 2. A minimum 100 cfm exhaust fan should be shown at the new stove (or provide exhaust <br /> airflow rate calculation). IMC Table 403.3.1.1 <br /> 3. A sign stating Exit in raised characters and braille and complying with ICC A117.1 should <br /> be shown adjacent to the exterior exit doorways. Section 1013.4 <br /> 4. The minimum 60 inch clearance for the water closets should be dimensioned on the plans. <br /> The lavatory should be shown completely outside of this clearance. ANSI Section 604.3.1 <br /> 5. The vertical grab bar adjacent to the water closet as required in ANSI Section 604.5 should <br /> be shown on the plans. <br /> 6. The height of the water closet seats should be shown as 17-19 inches. ANSI Section 604.4 <br /> 7. The centerline of the water closets should be shown 16-18 inches from the near side wall. <br /> ANSI Section 604.2 <br /> ��3 <br /> O 3200 Cedar Street © 425.257.8800 0 everettpw@everettwa.gov <br /> Everett, WA 98201 425.257.8882 fax everettwa.gov <br />