Laserfiche WebLink
r <br /> 8. The flush controls for the water closets should be shown on the wide side of the <br /> compartment. ANSI Section 604.6 <br /> 9. The height of the lavatories in the toilet rooms should be shown as 34 inches maximum. <br /> ANSI Section 606.3 <br /> 10. Exposed pipes and water supply lines under the lavatories should be shown insulated, <br /> guarded or wrapped to protect against contact. ANSI Section 606.6 <br /> 11.The lavatory faucets should be operable with one hand and not require tight grasping, <br /> pinching or twisting of the wrist. ANSI Sections 606.4 and 309 <br /> STRUCTURAL <br /> 1. Sheets A3.0 and A3.1 as well as portions of Sheet A1.0 appear to be structural details and <br /> notes regarding the construction of a new lateral system and parapets. Please provide <br /> structural plans stamped by a registered professional engineer in the State of Washington. <br /> IBC 107.1. <br /> 2. Please provide additional structural calculations stamped and signed by a registered <br /> professional engineer in the state of Washington for the following items: <br /> a. Diaphragm design calculations due to the new lateral system subjected to the <br /> design wind or seismic loading requirements per ASCE 7-10 Chapters 12 & 26, <br /> whichever lateral loads govern the design. <br /> b. Existing roof framing calculations for the potential of added snowdrift and wind <br /> loads resulting from the new parapets added to the roof structure. <br /> 3. On Detail 3 of Sheet A3.1, it appears that the new wood shear wall is being constructed <br /> on the existing slab on grade without a new footing to support the new wall construction. <br /> Please provide calculations indicating that existing slab and soil can withstand the loading <br /> as a result of gravity and lateral loads from the walls. IBC 1604.2 and 1604.4. <br /> 4. Details 1 and 3 on Sheet A3.1 appear to have elements that require Special Inspection <br /> per IBC 1705.2.1 for steel elements and IBC 1705.3 for concrete construction. Please <br /> provide a list of applicable Special Inspection items on the plans. IBC 1704.3. <br /> In order for the processing of your application to continue, it will be necessary to provide the <br /> Building Division with two new sets of revised construction documents reflecting the corrections <br /> requested. Please include a response letter which indicates how the corrections were resolved. <br /> All codes cited refer to the 2015 International Building Code (IBC), 2015 International Existing <br /> Building Code (IEBC), the 2015 International Fire Code (IFC), the 2015 International Mechanical <br /> Code (IMC), and/or the 2015 Washington State Energy Code (WSEC), as amended by the State <br /> of Washington and adopted by the City of Everett. The current IBC referenced standard for <br /> accessible design is the 2009 "Accessible and Usable Buildings and Facilities" (ICC/ANSI <br /> A117.1). Federal ADA regulations and standards may be more restrictive. <br /> O 3Everett200 CedarWA Street 98201 © 425.257.8810425.257.8857 fax O tlee@everettwa.gov <br /> , everettwa.gov <br />