Laserfiche WebLink
8. Opening windows on the 3rd floor front elevation should be shown to be a minimum of 24"from <br /> the finished floor to the actual opening of the window. Section R312.2 <br /> 9. The attic access hatches should be shown in an unobstructed, readily accessible location and not <br /> over closet shelves. Section R807.1 <br /> 10. Deck lateral load connections should be detailed on the plans. Section R507.1 <br /> Please provide a response letter, which shows where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan review will <br /> begin. <br /> All required submittals must be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Tony . Lee <br /> Building Official <br />