Laserfiche WebLink
4 <br /> b. An additional smoke alarm should be shown in the (new) hallway outside of the sleeping <br /> rooms on the first level. Section R314.3 <br /> 8. The 2'6"x2'6"slider in the master bathroom of unit#1 should be shown as safety glazing. Section <br /> R308.4.5 <br /> 9. The glazing at the stair landing in Unit 4 should be shown to be a minimum of 36"a.f.f or safety <br /> glazing. Section R308.4.7 <br /> 10. Opening windows on the 3rd floor front elevation should be shown to be a minimum of 24"from <br /> the finished floor to the actual opening of the window. Section R312.2 <br /> 11. The attic access hatches in units 1 &4 should be shown in an unobstructed, readily accessible <br /> location and not over closet shelves. Section R807.1 <br /> 12. Deck lateral load connections should be detailed on the plans. Section R507.1 <br /> Please provide a response letter, which shows where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan review will <br /> begin. <br /> All required submittals must be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Tony R. Lee <br /> Building Official <br /> _1 <br />