Laserfiche WebLink
OUTDOOR A R HANDL �1G UNIT WITH GAS HEAT SCHEDU�E �� <br /> SUPPLY FANS ARRAY EXHAUST FANS ARRAY INQIRECT GAS-FIRED HEAT AHU ELECTRICAL* FILTERS ��� <br /> PRE-FiLTERS ( 2") FINAL FILTERS ( 4") MAX DIMENSIONS OPERATING <br /> MARK SERVICE n�E NUMBER OF TOTAL MIN ESP TSP BHP HP NUMBER OF TOTAL ESP TSP BHP HP INPUT OU7PUT TURN DOWN TEMP, SCCR (L x W x H) REMARKS <br /> AIRFLOW OUTSIDE V/PN VFD AIRFLOW V/PH VFD FLA MCA MOP V/PH IPD FPD IPD FPD WEIGHT (LBS.) <br /> (CFM) AIR (CFM) ��N. WG) (IN. WG) (Total) (Total) FANS (CFM) (IN. WG) (IN. WG) (Total) (Total) (MBH) (MBH) RATIO RISE {AMPS) MERV MERV (INCHES) • <br /> (W. WG) (IN. WG) (IN. WG) (IN. WG} <br /> AHU-1 45-012 BUILDING HOR!ZONTAL 6 50,000 5,000 3.5 7.0 82.49 90 480/3 YES 4 47,000 1.0 2.Q 33.61 34 480/3 YES 3,062 2,45Q 30:1 45 160 187 250 480/3 10000 8 Q.50 1.00 13 0.50 1.50 248 x 150 x 127 18,000 1 TO 12 <br /> AHU-2 45-012 BUILDING HORIZONTAL 6 50,000 5,000 3.5 7.0 82.49 90 4-80/3 YES 4 47,000 1.0 2.0 33.61 34 480/3 YES 3,062 2,450 30:1 45 160 187 250 480/3 10000 8 Q.50 1.00 13 0.50 1.50 248 x 150 x 127 18,000 1 TO 13 <br /> 1. AHU MANUFACTURER TO PROVIDE UL LISTED & IABELED BURNER CONTROL PANEL. BURNER IS CONTROLEQ WITH 2-10 VOLTS INPUT BY HONEYWELL (CMCS). - <br /> .,,4. , <br /> 2. PROVIDE AN ARRAY OF SIX SUPPLY FANS AND AN ARRAY OF FOUR EXHAUST FANS. AHU SHALL BE CAPABLE OF PROVIDWG 90� OF NOMINAL AIRFLOW WITH ONE FAN DOWN. , <br /> 3. PROVIDE WITH A SINGLE 480 VOLTS/3 PNASE PONJER CONNECTIQN. <br /> 4. PROVIDE TWO 120 VOLTS /SINGLE PHASE POWER CONNECTIONS FOR LIGNTS/ RECEPTACLE AND EMC5 CONTROL PANEL . <br /> 5. PROVIDE ONE VFD PER FAN (NO VFD BYPASS). PROVIDE VFDS AS PER ELECTRICAL SPECIFICATION 26 29 23 <br /> 6. ALL CONTROLS BY NONEYWELL {EMCS). <br /> 7. UNIT 1S CAPABLE OF SUPP�YING 100� OUTSIDE AIR ( FOR SUMMER COOLING�. <br /> 8. ELECTRICAL CONTRACTOR TO PROVIDE A DISCONNECT SWITCH. <br /> 9. PROVIDE 8" HIGH METAL BASE. <br /> 10. PROVIDE SMOKE DETECTORS IN REfURN AIR DUCT ( BY ELECTRICAL CONTRACTOR). <br /> �_� <br /> 11. PROVIDE 7W0 OUTSIDE AIR DAMPERS: ONE SIZED FOR MINIMUM OUTSIDE AIR (5,000 CFM) AND ONE SIZED FOR ECONOMIZER FLOW (45,000 CFM) ' <br /> 12, UNIT IS EQUIPED WITH PREMIUM EFFIGIENCY MOTORS <br /> 13, ALL DAMPERS PROVIDED BY MANUFACTURER ' <br /> * SEE NOTE �4 FOR 120 VOLTS POWER REQUIREMENTS <br /> FAN SCHEDU�E �` <br /> .,� <br /> MOTOR <br /> UNIT N0. LOCATION AREA SERVED CFM TSP FAN RPM FAN TYPE DRIVE TYPE MANUFACTURER & MODEL OPEft WT. (LBS.} REMARKS <br /> (IN. WC) HP BHP RPM VOLTS PH VFD <br /> EF-1 SUBSTATION TRANSFORMER 6,500 1.10 1198 3.00 2.02 1170 208 3 YES MIX�D FLOW INLINE DIRECT GREENHECK QEID-22-75-B30 370 1, 2, 3, 4, 5 � <br /> - 0 0 I K - -V 4 <br /> SF-1 HYDRAULIC PUMP ROOM HYDRAULIC PUMP ROOM 680 0.50 1550 0.25 Q.24 1750 115 1 NO PROPELLER DIRECT GREENHECK SS1-12-432-A4 35 4, 6, 7 <br /> WALL <br /> NOTES: <br /> � 1. PROVIDE MOTORIZED DAMPER. 6. FAN SHALL RUN CONTINUOUSLY. <br /> 2. CONTROLLED BY EMCS WITH ROOM SENSOR. 7. PROVIDE WALL HOUSING, FLUSH EXTERIOR �NITH OSHA GUARD. � <br /> 3. PROVIDE VFD PER ELECTRICAL SPECIFICATION 262923. <br /> 4. VENTILATION AIR SUPPLY. , <br /> 5. SUPPLY VFD RATED MOTOR WITH GREENHECK SDR T1502268 SHAFT GROUNDING. <br /> -�,;; .. <br /> -::� <br /> ,;1... <br /> ,,;� <br /> :,;� . <br /> �,_. <br /> ;.�.. <br /> i. <br /> � � ,� '„*r,. <br /> V � � � � � <br /> 1601 Fifith Avenue,Sufte 900�Seattle,WA 98101 <br /> e � ph 206.623.0717�fax 206.624.3775 `< <br /> coffman.com r� <br /> LASTING creativity�resWts�relationships � • <br /> r( . <br /> M <br /> . <br /> C <br /> DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL D DATE <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE L S ACCEPTABILITY G.ROUTH 05.26.15 `� <br /> - EDC STATIC TEST FACILITY W3099715 CEI MS 10.02.15 ��� �'��� THIS DESIGN AND/OR CHECKED MEG�IANIC�IL EQUIPMENT SC�IEDULES W4440664 I� 12.22.16 c <br /> �`�' ��' `� SPECIFICATION IS APPROVED M.SOTURA 05.26.15 sHE�r � <br /> A EDC STATIC TEST FACILITY - AS-BUI;TS W3Q99715 CEI MS 09.01.16 � � � �,� APPROVED aY DEPT. DATE COFFMAN Q5.26.15 TITLE EDC STATIC TEST FACILITY - PHASE 2 a <br /> � <br /> B EDC STATIC TEST FACILITY - PHASE 2 W4440664 CEI MS 12.22.16 CHECKED = <br /> �d �E�6 T11��� � APPROVED �� ���I�� 4���� � �oe No. W3099715 COMP NO. � �` <br /> � � <br /> �SSION�� ��� APPROVED MECHANICAL MASTER EVERETT, WA aWc No. 45-012-M2A <br />