LOUVER SCHEDULE AIR IN�ET �C OUTLET SCHEDULE
<br /> BASIS OF DESIGN
<br /> NOMINAL SIZE MAX P.D. TAG PURPOSE TYPE NECK SIZE CFM FINISH NC BORDER TYPE REMARKS
<br /> TAG PURPOSE INSTALLATION TYPE ��N� MINIMUM FREE AREA CFM (IN WC) NIANUFACTURER AND MODEL REMARKS (IN.) �FR Mo�E� $"�
<br /> LV-4 HYDRAULIC PUMP AIR EXHAUST WALL 14.5x14.5 55% 680 0.15 RUSKIN ELF6375—DXH 1, 2, 3 SG1 TO SUPPLY GRILLE 96x48 25,00o ALUMINUM BLADES 37 STEEL TITus �32—RS
<br /> LV-5 HYDRAULIC PUMP AIR INTAKE WALL 14.5x14.5 55% 680 0.15 RUSKIN ELF6375—DXH 1, 2, 3 2 �
<br /> LV-6, 7 CONTROL ROOM AIR INTAKE / EXHAUST WALL 14x14 55% 400 0.15 RUSKIN ELF6375—DXH 1, 2, 3 RG1 JOINED W/ ALUMINUM ARRAY 6 GRILLES IN WALL TO EQUAL 132 INCHES WIDE BY 88
<br /> LV-8,9 HYDRAULIC PUMP ROOM MAKEUP AIR WALL 48x66 55� 11,000 — Tgp 1,4
<br /> TO 6 RETURN GRILLE 44x44 7,833 WHITE 28 MULLIONS TITUS 355-ZFL INCHES HIGH
<br /> LV-10,11 HYDRAULIC PUMP ROOM EXHAUST AIR WALL 48x66 55% 11,000 — (Tgp� 1,4
<br /> NOTES: 1 . COLOR TO BE SELECTED BY OWNER. EG1 EXHAUST GRILLE 12x12 500 WHITE 18 WAL� MOUNTED TITUS 350-RL
<br /> 2 PROVIDE WITH FLANGED FRAME AND BIRD SCREEN.
<br /> 3. ALUMINUM LQUVER THROW 73'-0" @ 150 FPM, 90'-0" � 100 FPM, 127'-0" � 50
<br /> 4. ACTUAL SIZE, CFM, MAX P.D., MANUFACTURER AND MODEL WILL BE SELECTED BY BOEING. SD-1 DRUM LOUVER DIFFUSER 70x15 5,000 WHITE 38 ALUMINUM TITUS DL FPM TERMINAL VELOCITY AT 0' DEFLECTION
<br /> SD-2 SUPPLY AIR DIFFUSER 10"� SEE PLAN WHITE 32 ALUMINUM TITUS TDC
<br /> S P�IT C 0 N D E�1 S I N G U N I T S C H E D U L E (VR F) R�-� RETURN AIR GRILLE 22x22 1,270 WHITE 32 ALUMINUM TITUS 50F
<br /> NOMINAL COOLING CAPACITY HEATING CAPACITY ELECTRICAL SHIPPED
<br /> UNIT N0. LOCATION SERVICE EER/IEER BASIS OF DESIGN REMARKS RG-8 REfURN AIR GRILLE 14x14 400 WHfTE 32 ALUMINUM TITUS 50F
<br /> TON (BTU/HR) (BTU/HR) VOLTS PH MCA MOCP WEIGHT (LBS)
<br /> CU-A OUTDOOR CONTROL ROOM 12 12.5 / 21.2 144000 160000 460 3 21 35 706 MITSUBISHI PUHY-P144YLMU 1,2
<br /> NOTES: 1. MOUNT ON 4" CONCRETE PAD MINIMUM 6" WIDER IN EACH DIRECTION THAN CONDENSING UNIT. C O N Q E I V S I N G U N IT S C H E d U LE
<br /> 2. DISCONNECT BY ELEC CONTRACTOR. '
<br /> � PAIRED UNIT SIZE SYSTEM LIQUID SUCTION ELECTRICAL SOUND WEIGHT
<br /> UNIT N0, AREA SERVED UNIT MAKE MQDEL � REMARKS
<br /> (TONS) SCOP (�N.) (IN.) VOLTS PH MCA MOCP d6(A) (LBS. ,
<br /> CU-1 SYSTEMS ROOM FCU-1 LIEBERT PFHZ37AL 3 2.59 1/2 7/8 208 1 22.3 35 57 351 1,2
<br /> SPL T FAf� C01� UNIT SCHEDU�E NOTEs:
<br /> 1. UNIT TO BE MOUNTED OUTSIDE ON CONCRETE SLAB
<br /> UNIT AREA MIN OSA FAN ELECTRICAL SHIPPED OUTDOOR 2. REFRIGERANT R-407C, CHARGED TO 426 OZ
<br /> FILTER BASIS OF DESIGN REMARKS
<br /> N0. SERVED (CFM) CFM ESP VOLTS PH MCA MOCP WEIGHT (LBS) UNIT N0,
<br /> FCU-A1 CONTROL ROOM 200 215Q 0.8 208 1 7.7 15 MERV 13 214 MITSUBISHI PEFY-P72NMHSU CU-A 1, 2, 3
<br /> FCU-A2 CONTROL ROOM 200 2150 0.8 208 1 7.7 15 MERV 13 214 MITSUBISHI PEFY-P72NMHSU CU-A 1, 2, 3 FAN CO I L U N IT SCN ED U LE r •
<br /> NOTES: 1, INCLUDE MANUFACTURER DRAIN PUMP MODEL PAC-KE05DM-F AND CONDENSATE OVERFLOW SWITCH. COOLING CQIL TOTAL FAN CFM ELECTRICAL WJ-.
<br /> UNIT N0. AREA SERVED MAKE MODEL TYPE (gTU/H} (RANGE) VOLTS PHASE (LBS) REMARKS
<br /> 2. INCLUDE MANUFACTURER FILTER BOX WITH 4" MERV 13 FILTER MODEL FBH4-4. '
<br /> 3. PROVIDE 24" LONG FULL SIZE PLENUM ON SUPPLY SIDE OF FAN COIL. FCU-1 SYSTEMS ROOM LIEBERT MMD36E SPLIT SYSTEM 33,800 1250 208 1 225 1,2,3
<br /> 4. PROVIDE BACNEf INTERFACE FOR SITE HONEYWELL DDC SYSTEM. NOTES:
<br /> 1. ELECTRICAL DISCONNECT BY ELECTRICAL CONTRACTOR.
<br /> ENERGY RECOVERY VENTILATOR SCHEDULE 2. PROVIDE WITH WALL MOUNTED THERMOSTAT.
<br /> 3. ECONOMIZER EXCEPTION: COOLING UNITS AND SPLIT SYSTEMS WITH A TOTAL COOLING CAPACITY RATED IN ACCORDANCE WITH SECTION C403.2.3 OF LESS THAN 33,000 BTU/H
<br /> SUPPLY FAN EXHAUST FAN SUMMER SUPPLY WWTER SUPPLY COOLING/HEATING ENERGY ELECTRICAL
<br /> UNIT N0. LOCATION MAKE & MODEL FILTER OPER WT. (LBS.) REMARKS �`�'
<br /> CFM ESP HP BHP CFM ESP HP BHP * DB * DB EFFICIENCY VOLTS PH HZ FLA ° ,
<br /> ERV-1 CONTROL ROOM ALDES E1100-FI 400 0.5 (2� 0.4 0.77 400 0.5 (2� 0,5 0.77 77.4 F 64.7 F 59.3% / 58.5% 120 1 60 10.5 MERV 8 230 1
<br /> ELECTRIC UNIT HEATER SCHEDULE .
<br /> * WORST CASE DESIGN SUMMER AMBIENT TEMPERATURE 85F / 69F (DB/WB) AND WINTER 23F. MARK LOCATION MAKE MODEL ARRANGEMENT KW /VOLT/ PH FAN WGT. REMARKS
<br /> NOTES:
<br /> CFM VOLTSfPH
<br /> 1. UNIT SHALL BE PROVIDED WITH A BASIC PROGRAMMABLE CONTROLLER MOUNTED ON SPACE WALL. U - T SF Z - H L .5 4 5 80 3 1
<br /> UH-2 HYDRAULIC PUMP ROOM REZNOR EGEB-7 HORIZONTAL 7,5 / 480 / 3 625 480/3 37 1, 2, 3
<br /> N(}TES:
<br /> B 1, PROVIDE FAN GUARD, WALL BRACKETS � �.X
<br /> 2. HEATER CONTROLLED BY EMCS
<br /> 3. BOTTOM OF UNIT SHALL BE AT LEAST 8 FOOT ABOVE FINISH FLOOR
<br /> B ,
<br /> ..=�,t
<br /> .:�t.
<br /> .;.�.
<br /> :_�
<br /> ISSUE FOR CONSTRUCTION
<br /> COFFMAN .
<br /> N G I N E E R S
<br /> 1 1� ■ ^/1 ■n 0 /� f'� 1601 Fifth Avenue,Suite 900�Seattle,WA 98101 ` ¢�
<br /> £. .
<br /> L L L �,, ph 206.623.0717�fax 206.624.3775 <
<br /> coffman.com ,
<br /> r
<br /> LASTING creativity�results(relationships �
<br /> �
<br /> K
<br /> C
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPRQVED DATE L S ACCEPTABILITY G ROUTH �05 26.15 SUBTITLE CURRENT REVISION SYMBOL DATE •
<br /> _ ��� S°�' TH,S oES,�N ANo oR �HE�KEo — MECHANICAL EQUIPMENT SCHEDULES W4440664 B � 2.�2.� 6 �
<br /> E D C S T A T I C T E S T F A C I L I T Y W 3 0 9 9 7 1 5 C E I M S 1 Q.0 2.1 5 ti � I�� � M.S O T U R A 0 5.2 6.1 5 �
<br /> � SPECIFICATION IS APPROVED SHEET
<br /> A EDC STATIC TEST FACILITY — AS—BUILTS W3099715 CEI MS 09.01.16 ���,H�� '� , o �" INEER TITLE EDC STATIC TEST FACILITY — PHASE 2 '�
<br /> � �2, APPROVED BY DEPT. DATE COFFMAN 05.26.15 «
<br /> B EDC STATIC TEST FACILITY — PHASE 2 W4440664 CEI MS 12.22.16 cHECKE� �
<br /> � BUILDING 45 012 �
<br /> ro 36611 APPROVED � JOB N0. COMP NO.
<br /> ��CIST�,�9 �,� W3099715 Q
<br /> �'sSjoNA� ��� APPROVED MECHANICAL MASTER EVERETT, Wq °wc No. 45-012—M2B
<br /> <��
<br />
|