Laserfiche WebLink
4. Exiting comment 7: Thc ramp to thc stagc cannot excecd 1 inch risc per 12 inchcs of run, per IAC <br />Al 17.1 table 4J5.2 1'or the height of the stage shown on the drawings. Tl�e maximum height of a I:S <br />ramp is 3 inchcs, per that taUle. <br />5. lixiting commcnt 8: The hcight of the stage excecds thc number of risers indicated on the plans at a <br />maximum of 7 inchcs each, and requires either additional riscrs or a lower stage height. <br />Upon submission of hvo inse� i sets of revised drawings rcllecting the corrections requested, your application <br />will be processed. Applicable codes include thc 20UG lntemational Building Codc (IBC), thc 200G Intemational <br />Pirc Codc (1PC), thc 2006 Intemation^! Mechanical Code (IMC), thc 2006 Washington State Gnergy Code <br />(WSEC), the 2006 Washington State Vcntilation and Indoor Air Quality Codc (VIAQ), lhe 2003 Accessible and <br />Usablc Buildings and Facilities A I U.1-2003 (ICC/ANSI) and the City of Everett Municipal Code, including <br />Chapter 1 G.7G, Aulomatic I�ire Detection and Fire Suppression Systems. All codcs refercnced, as adoptcd by thc <br />City of Everett, should include current revisions by the State of Washington. Thcse comments address building <br />issues only. Rcvisions or additions may bc required by other departme�ns (such as Utilitics, Planning or Fire). <br />All required suUmittals must bc oC suCGcient detail and inCormalion to ensure lhat the proposeJ slructure will be <br />constructed in compliancc with all adopted codes. You can rcach me directly to discuss this letter by e-mail at <br />mhalc�ci.cyerett.wa.us or by pl:one at 425-257-8813. <br />Sincercly, <br />N��s <br />Cc: AI�CticrU�, Odyssey Construclion <br />Steve Millec Y.G. <br />