]anuary 30, 2014 <br />Mr. Rick Berry <br />AFP Systems, Inc. <br />19435 SW 129`" Ave <br />Turlatin, OR 97062 <br />PUBL/C WORIf(S <br />Project: Install new fire sprinkler system for Walmart <br />]ob Address: 1605 SE Everett Mall Way <br />Pian Review No: K1401-002 <br />RE: Corredions <br />Sent vi� e <br />��ge�� <br />Dear Mr. Berry, <br />In response to the recent application for a new suppression construction permit, the plans have been <br />examined and you are advised that the following issues require resolution prior to further review. As the <br />sprinkler contractor, your firm may not be under contract for some of the following information; however, the <br />documentation of scope of this work (by others) is required on the sprinkler drawings to obtain a sprinkler <br />permit. <br />1. 1605 SE Everett Mall Way currently has an 8" Double Check Valve Assembly (DCVA), with an <br />unapproved 3/a inch bypass. A state approved Double Check Detector Assembly (DCDA) is required for <br />fire services, per Everett Design and Construdion Standards Section 5-3. <br />2. A new doub!c-check detector valve assembly (DCDA) should be shown on the drewings to repiace the <br />DCVA that ou� records indicate on the fire service of this building. <br />a. A Public Works permit will be required. Please contact Benyam Stephanos, Public Works Plan <br />Reviewer, to discuss this requirement, or if you have questions about Public Works plan review <br />for the fire service. Benyam Stephanos can be reached at 425-257-7289. <br />3. All replacements of a single check detector to a double check detector should be installed by a private <br />contractor, since the city only installs new services upon request. <br />4. The fire service for this tenant space should be shown from ttie tenant space to the city main on a site <br />plan, including the new cross connection (DCDA) and model number. <br />5. The revised sprinkler submittal will require three copies of the followin9, so that the submittal can be <br />reviewed: <br />a. A catalo9 cut indicating the DCDA manufacturer's model in the'BarkFlow Prevention Assemblies <br />Approved for Installation in Washington State', publislied by the Washington State Department <br />of Health, current edition. <br />b. A plan and section of the intended location and instailation of the DCDA. The DCDA can be <br />located in an interior or an e�erior location, to comply with City of Everett Standard <br />Construction Drawings 515 or 523, attached. <br />c. The model number of the DCDA should be show on the drawings. <br />//� <br />