Laserfiche WebLink
� <br />d. The routing of the fire senrice from the city main should be shown relative to the properly line <br />of the building. <br />e. The riser room should be identified on the plans. <br />f. A post indicator valve (PIV) is required if there is not direct access to the riser roum from <br />outside of the building. <br />g. All �lan sheets affected by these revisions. <br />h. All hydreulic calculations affected by these revisions. <br />If you have questions about the backFlow requirements identified on the attached owner notification, please <br />contact Tim Markham at 425-257-8833. If you have questions about the PIV or other fire service equipment, <br />please contact Assistant Fire Marshal ]im Venturo at 425-257-8124. I can answer other questions regarding <br />this corredions letter. <br />Meg Naley,�Architect, NCARB, Plans Examiner <br />Cc: bFM Jifn Venturo, Mike Ward, Paul McKee, Tim Markham, Benyam Stephanos <br />z��j <br />