VARIABLE REFRIGERANT VOLUME - AIR-COOLED CONDENSING UNIT SCHEDULE
<br /> CARN EGI E
<br /> BUILDING
<br /> COOLING CAPACITY HEATING CAPACITY REFRIGERANT CHARGE ELECTRICAL DIMENSIONS EFFICIENCY (NonDucted/Ducted) R E S TO R A TI 0 N
<br /> TAG BASIS OF DESIGN NOMINAL DESCRIPTION ' CONNECTION RATIO �
<br /> (DAIKIN) TONNAGE AMBIENT DESIGN °F AMBIENT DESIG ° NOTES Options and Accessories�
<br /> BTU/h � BTU/h Factory Charge (Ibs) Add'I Refrigerant(Ibs) ��0� VOLTAGE- MIN CIRCUITAMPS MAX OVERCURRENT PROTECTION RUNNING (WxHxD) WEIGHT EER IEER COP 47 COP17 SCHE 3001 OAKES AVE. �
<br /> DB) (°F DB/WB) PHASE {MCA} (MOP) URRENT(A) (inch) (Ibs)
<br /> HP 1 REYQ192TAYDU 16 Air cooled heat recove 2 �92,232 90.0 177,256 15.0/ 13.5 47.6 n/a 97.g 208V 3 h E VE R E TT, WA 9 8 2 01
<br /> ry� � P 21.1 / 152 25.0/20.0 13.6/9.4 48.9 x 66.7 x 30.2/36.7 x 66.7 x 30.2 716.5/526.9 12.5/12.5 22.9/21.1 3.85/3.67 2.41/2.26 26.6/23.1 BHFP26P100U (1)
<br /> Schedule Notes:
<br /> U
<br /> Manu acturer must be certified, listed, and labeled per AHRI 1230.
<br /> a
<br /> � System rating data based on design ambient conditions for cooling and for heating. I �
<br /> Manufacturer must certify and submit system performance at extreme conditions of 120 degrees F ambient in cooling mode and -4 degrees F in heating mode. �
<br /> Submitted performance data must be fully de-rated for alt components and accessories, including but not limited to, line length, vertical separation, connection ratio, design O
<br /> I System must provide continuous heating during defrost and oil return. Systems without this capability must be de-rated to account for heating lost during defrost cycle and unit �„�
<br /> Manufacturer must have published continuous performance rating data at least 120F and -4F to ensure performance during extreme conditions . r►1
<br /> Condensing units must have fully modulating INVERTER compressors.
<br /> `.�
<br /> �
<br /> on -VFD compressors including digital scroll compressors and compressors with hot gas bypass)will not be permitted. �
<br /> Condensing units must have have auto changeover functions �
<br /> Deman imiting relay contact must be provided.
<br /> .�
<br /> � Condensing units must have a minimum of 3 minutes of non -volatile operational memory for use in diagnostics. ; �
<br /> � C�
<br /> � ; All Mode Changeover Devices and FCU refrigerant controls shall be via Electronic Expansion Valves(EEV's)with 2000:1 throttling range. r �
<br /> � EEV actuators must be removable from valve body without disturbing the refrigerant system.
<br /> `.�
<br /> Systems using solenoid control valves must include full port isolation valves before and after refrigerant control box and acoustic treatment to provide no greater than NC20 in the occupied mode.
<br /> � Solenoid control valves and full port isolation valves must be rated for 2.5 times the maximum working pressure in the system and be rated for a minimum L10 life of 500, 000 hours 2813 ROCKEFELLER AVE
<br /> VRF systems using solenoid control valves must provide acoustic treatment to attenuate valve noise below NC20 in all occupied modes. E�RE�, WA 98201
<br /> Condensing units must be furnished with protective coil coating to withstand ASTM 6117 salt spray test for a minimum of 2500 hours.Performance of system must be de- rated for coil coating. PHONE: 425.3�7.8��7
<br /> � Condensing units must have published performance data with 200% indoor connected capacity. �
<br /> FCU thermostats must provide +/-1 degree dead - band set- point and control capability.
<br /> FAX: 425.317.8489
<br /> Air handling units shall be provided with condensate pump.
<br /> i
<br /> System shall be provided with i-Touch Manager controller with WEB based software for displaying up to 8 DI11 - Net systems with 128 indoor units per system.PC by others.
<br /> Manufacturers submittal must include refrigerant piping diagram with pipe diameters, lengths, and refrigerant volume.
<br /> Substitute manufacturer shatl be responsible for additional piping and refrigerant.
<br /> � Contractor to verify piping dimensions.
<br /> Installing contractor must have successfully completed manufacturers certified installation class within past 36 months.
<br /> Contractor to furnish and install insulation on refrigerant piping.
<br /> , Manufacturers Representative must have local stock of parts and factory certified technician on staff.
<br /> iManufacturers Representative shalt provide proof of ongoing installation training at their local facility for at least the past 5 years.
<br /> Manufacturers Representative shall provide proof of continuous sales and support of their products for at least 15 years. -
<br /> Mechanical contractor shall be responsible for all direct costs and operating costs increases for 20 years associated with any deviations resulting from changes in design.
<br /> Condensing unit shaN provide auto charging and indoor unit auto addressing capability.
<br /> � Manufacturer must provide 10 years parts warranty on all FCUs, Condensing Units, Mode Changeover Devices and Zone Controls. Warranty conditions must be clarified during submittal phase.
<br /> �
<br /> ���`
<br /> ; �
<br /> VARIABLE REFRIGERANT VOLUME - INDOOR UNIT SCHEDULE � �
<br /> �
<br /> CONNECTED TO: SUPPLY FAN COOLING CAPACITY HEATING CAPACITY ELECTRICAL DIMENS�ONS WEIGHT "-� " '��� _.r
<br /> BASIS OF NOMINAL ENTERING POWER Max Overcurrent ' �`+�
<br /> ZONE Min Circuit Amps WxHxD Net
<br /> TAG DESIGN TYPE CONDENSING IR FLOW RAT SENSIBLE AIR TOTAL NTERING AIR SUPPLY Protection NOTES Options and Accessories 3t�8l1 � -
<br /> (DAIKIN) TONNAGE UNIT CHANGEOVER cfm TOTAL BTU/h gTU/h BTU/h °Fdb
<br /> DEVICE °F DB °F WB Voltage - Phase MCA MOP inch Ibs �� ��
<br /> FCU 1 FXMQ48PBVJU 4.0 Ceiling Mounted Ducted (Medium Static) HP 1 Yes 1,377 48,011 34,961 80.0 67.0 53,978 70.0 230V 1ph 3.4 15.0 55.1 x 11.8 x 27.6 101.4 BRC1E73 (1), DACA-FXMQ48131K(1) �.
<br /> �`";�<F.!
<br /> FCU 2 FXMQ54PBVJU 4.5 Ceiling Mounted Ducted (Medium Static) HP 1 Yes 1,624 53,983 39,326 80.0 67.0 59,983 70,0 230V 1 ph 3.4 15.0 55.1 x 11.8 x 27.6 103.6 BRC1 E73 (1), DACA-FXMQ48131 K(1) i � ° �
<br /> FCU 3 FXMQ09PBVJU 0.8 Ceiling Mounted Ducted (Medium Static) HP 1 Yes 317 9,486 7,613 80.0 67.0 10,509 7p.p 230V 1ph 0.6 15.0 21.7 x 11.8 x 27.6 55.1 BRC1E73 (1), DACA-FXMQ12131K (1)
<br /> FCU 4 FXMQ18PBVJU 1.5 Ceiling Mounted Ducted (Medium Static) HP 1 Yes 635 17,983 15,176 80.0 67.0 �9,994 70.0 230V 1ph 1.6 15.0 39.4 x 11.8 x 27.6 79.4 BRC1E73 (1), DACA-FXMQ30131K (1)
<br /> FCU 5 FXMQ15PBVJU 1.3 Ceiling Mounted Ducted (Medium Static) HP 1 Yes 560 15,014 11,704 80.0 67.0 16,514 70,0 230V 1 ph 1.5 15.0 39.4 x 11.8 x 27.6 79.4 BRC1 E73 (1), DACA-FXMQ30131 K(1)
<br /> FCU 6 FXMQ07PBVJU 0.6 Ceiling Mounted Ducted (Medium Static) HP 1 Yes 317 7,507 6,244 80.0 67.0 8,496 70,0 230V 1ph 0.6 15.0 21.7 x 11.8 x 27.6 55.1 BRC1E73 (1), DACA-FXMQ12131K (1)
<br /> FCU 7 RD2XJRT Renewaire ERV/w DX Coil HP 1 Yes 1,130 36,000 28,079 80.0 67.0 39,g89 70.0 208-3 55.1 x 11.8 x 27.6 101.4 BRC1E73 (1), EKEXV100-US, EKEQMCBAV3-US
<br /> I
<br /> erlo REqS1ERED �
<br /> Schedule Notes: ARCHITECT
<br /> Ease of installation with auto adjusting airflow at commissioning based on external static pressure •
<br /> Easy maintenance with service access from below �p� a �R
<br /> aTAIE OF�119NiQl�di
<br /> Built-in condensate pump (FXDQ_M, FXF�P, FXFQ_T, FXMC�M, FXM�P, FXUQ_P, FXZ�M)
<br /> Optional MERV 8 and 13 filters (FXMQ M, FXM�P)
<br /> Optional Economizer Kit
<br /> Standard Limited Warranty: 10-year warranty on compressor and all parts
<br /> SCALE: AS NOTED
<br /> ISSUE DATE: 07/24/2017
<br /> DRAWN: AC �
<br /> VARIABLE REFRIGERANT VOLUME - ZONE HEAT RECOVERY DEVICE SCHEDULE ; CHECKED: RE
<br /> MAX � .
<br /> BASIS OF CONDENSING UNIT VOLTAGE- MIN C(RCUIT OVERCURRENT MAX CAPACITY DIMENSIONS � THIS PLAN AND DESIGN IS AND REMAINS
<br /> TAG DESIGN SERVED PHASE AMPS (MCA) PROTECTION (per Port WEIGHT (Ibs) ZONE SERVED Options and Accessories THE PR�ERTY OF THE ARCHITECTS AND
<br /> (DAIKIN) ) (WxHxD inch) MAY NOT 8E USED WITHOUT PRIOR
<br /> (MOP) � CONSENT FROM THE ARCHITECT
<br /> BS 1 BS8Q54TVJ HP 1 208V 1ph 0.8 15.0 54,000 22.8 x 11.7 x 18.9 72.8 KHFP26A100C (1)
<br /> Schedule Notes: REVIEW
<br /> Individual control and changeover with extended range of product offerings-4, 6, 8, 10 and 12 port options.
<br /> Unlimited number of unused ports per box or system. REV. DATE DESCRIPTION
<br /> No drain piping needed.
<br /> Standard Limited Warranty: 10-year warranty on all parts. Or'J 2F) SCHEMATIC DESIGN
<br /> 08 15 PROGRESS DRAWINGS �
<br /> 09 08 PERMIT SET
<br /> MECHANICAL SCHEDULES .