Laserfiche WebLink
Related RFI(s) <br /> Related Submittal(s) <br /> Result of Review <br /> CM Final Response KPFF Response forwarded to ICI via email on 7/24/19: <br /> • We have provided electrical circuit connections for six 1 P20A heat trace circuits <br /> (120 volt) are shown in the panel schedule 2A1 on sheet E2.04. The Contractor <br /> shall wire and connect the heat trace to these circuits. <br /> • Heat trace shall be: <br /> 1. Compatible with the 12" ductile iron and 12" welded steel pipe, the grooved <br /> and flexible coupling systems, and the insulation. <br /> 2. Capable of providing automatic freeze protection for the pipe assuming an <br /> ambient temperature of 0 deg F and a sewer flow velocity range of 0-10 FPS. <br /> 3. Rated for outdoor installation and exposure to wet weather. <br /> Response Documents <br /> Reason Code C Cancelled <br /> ✓ Added Work <br /> C Contractor Request <br /> ✓ Deleted Work <br /> C Differing Site Conditions <br /> a Plan Clarification <br /> ( Volvo Fnginoaring <br /> CM Final Response Date 7/24/2019 <br /> E - � <br /> Close <br />