Laserfiche WebLink
, 1 <br /> GGLO! <br /> 5. . Door .131 into the elevator,machinery room should be shown as a minimum 60-minute <br /> assembly. Section 3005.4 <br /> GGLO RESPONSE: <br /> Door rating has been modified to be 60 minute as required. <br /> 6. Per our reading, elevator lobby doors are not required per Section 3006.2, Exception 1. <br /> GGLO RESPONSE: i <br /> Thank you. Elevator smoke doors,have been removed. <br /> 7. 'The.exhaust tans penetrating the fire-resistive ceilings Fifa fire-rateci'flo�r , g assemittly <br /> should be shown with ceiling radiation dampers. Section 717.6,2 <br /> a. Exhaust ducts that are not permitted to have dampers(stove and dryer)should be <br /> shown with an,alternative means of protection (he. a chase below the fire-resistive <br /> ceiling assembly). <br /> GGLO RESPONSE: <br /> On sheet G-f0Z nete ?t.7_6-2 hes:been. _ f itz* . i a ere a deferred'su <br /> However.,on mechanical drawings,the fans in the unitshave been identified as including-backdraft <br /> dampers:' in other locations, soffits are provided below the rated assemblies. ` <br /> 8. The glazing in Stair#2 that is within 5'of the lowest stair tread and less than 5'a,f.f, should <br /> be shown as safety glazing. Section 2406.4.7 <br /> GGLO RESPONSE: <br /> azin aasbeen' .atetystazing uhtuarB legated. Reference A-SO4. <br /> 9. Please verify that the elevator can accommodate a stretcher in the lay-down position..City of <br /> Everett amended Section 3002.4 <br /> GGLO RESPONSE: <br /> Requirement has been added. Reference A-421. <br /> 1, Stair 1 at Level 1 exits to a portion of the building that is covered(but does not have complete <br /> exterior walls).As the covered area is still interior to the building, the exterior wall of the stair <br /> enclosure (001*FB)is an interior wail that requires a symmetrical fire,resistive assembly. <br /> Sections 1023.2, 1028.2&1028.5 <br /> a. The covered area is aortion of the Exit Discharge covered under Section <br /> p rg 1028.1. <br /> The bike racks should not be in the'path of egress as shown on Site Plan A-101. <br /> Section 10.211 <br /> GGLO RESPONSE: <br /> We have created a new walitype that includes a rated exterior sheathing and the bike racks have <br /> been located to not interfere with,the egress pathway. Reference sheet A-114: <br /> Cocoon House <br /> a a Corredtidris 121t312017 <br /> Page 2l <br />