DESIGN BUILD NOTES� GENERAL NOTES�
<br /> PROJECT TO BE ELECTRICAL AND MECHANICAL DESIGN-BUILD. NEW LIGHTING SHALL MEET THE 1. SEE ALSO ENGINEERING DRAWINGS (IF PROVIDED) FOR ADDITIONAL INFORMATION.
<br /> FOLLOWING MINIMUM REQUIREMENTS: WHEN THERE ARE DISCREPANCIES BETWEEN ARCHITECTURAL, ELECTRICAL,
<br /> A. IBC 1008.1 - ILLUMINATION REQUIREMENT MECHANICAL OR PLUMBING DRAWINGS OBTAIN CLARIFICATION FROM ARCHITECT IN
<br /> 1. THE MEANS OF EGRESS, INCLUDING THE EXITDISCHARGE, SHALL BE WRITING BEFORE PROCEEDING WITH ANY WORK IN QUESTION OR RELATED WORK. "
<br /> ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY THE IF WORK IS PERFORMED PRIOR TO OBTAINING CLARIFICATION, CONTRACTOR
<br /> G MEANS OF EGRESS IS OCCUPIED. SHALL CORRECT CONFLICTING WORK AT HIS EXPENSE AND AT NO ADDITIONAL
<br /> F E B. IBC 1008.2.1 - ILLUMINATION LEVEL COST TO THE OWNER OR THE ARCHITECT. r � ^ ,
<br /> 1. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 2. BEFORE STARTING ANY WORK, CONTRACTOR SHALL FIELD VERIFY EXISTING ��! �� �� V Y �r
<br /> FOOT-CANDLE (t t LUX) AT THE FLOOR LEVEL. CONDITIONS, IF THERE ARE EXISTING BUILDING OBSTRUCTIONS AND CEILING
<br /> C. IBC 1008.3 - ILLUMINATION EMERGENCY POWER FIXTURES, LEVEL CHANGES, SOFFITS, ETC., CANNOT BE INSTALLED WHERE
<br /> 1. THE POWER SUPPLY FOR MEANS OF EGRESS ILLUMINATION SHALL INDICATED, OR IF THERE ARE ANY CONFLICTS OR DISCREPANCIES, CONTRACTOR
<br /> NORMALLY BE PROVIDED BY THE PREMISE'S ELECTRIC SUPPLY. SHALL NOTIFY AND OBTAIN CLARIFICATION FROM THE ARCHITECT IN WRITING
<br /> 1.1 LOCATIONS INCLUDE: DEDICATED EGRESS ROUTES IN LARGER ROOMS BEFORE PROCEEDING WITH ANY PART OF THE CEILING WORK OR RELATED
<br /> � I � OR SPACES, PUBLIC OR COMMON EGRESS ELEMENTS, ESSENTIAL WORK.
<br /> PORTIONS OF THE INTERIOR EGRESS SYSTEM, INTERIOR EXIST 3. REWORK EXISTING FIRE, LIFE, SAFEfY SYSTEM AS REQUIRED PER NEW WALL
<br /> DISCHARGE ELEMENTS, AND EXTERIOR PORTIONS OF THE EXIT LAYOUT AND CURRENT CODE. ENGINEERING AND INSTALLATION BY BUILDING
<br /> � DISCHARGE, INCLUDING INTERIOR EXIT STAIRWAYS & R,4MPS. RECOMMENDED SUB-CONTRACTOR. a r c h i t@ C t S
<br /> 56'-0" 56'-0" � 2. EACH ROOM SHALL COMPLY WITH THE PROVISIONS OF C4Q5.2.1.1 INTERIOR 4. PROVIDE SMOKE DETECTORS THROUGHOUT TENANT AREAS IN ACCORDANCE WITH
<br /> ' LIGHTING CONTROLS. EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING LOCAL CODES AND MANUFACTURER'S RECOMMENDATIONS.
<br /> O PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR THE LIGHTING 5. ALL CEILING MOUNTED DEVICES SHALL BE WHITE. 2505 Third Avenue
<br /> I � I � SERVING THAT AREA. THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE 6. LOCATE ANY CONTROLS THAT NEED ACCESSING OVER ACOUSTICAL CEILING TILE Suite 324
<br /> AREA SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES THE AREAS. DO NOT PLACE ANY ABOVE GYPSUM BOARD CEILINGS, UNLESS Seattle, WA 98121
<br /> LIGHTS SERVED AND INDICATES THEIR STATUS. APPROVED BY ARCHITECT. �
<br /> 7. ALL ACCESS PANELS IN GYPSUM BOARD CEILINGS SHALL BE FRAMELESS;
<br /> � C405.2.1.2 LIGHT REDUCTION CONTROLS. LIGHT REDUCTION CONTROLS NEED NOT LOCATIONS SHALL BE COORDINATED WITH ARCHITECT. GROUP DEVICES TO 206.720.700� phone
<br /> I BE PROVIDED IN THE FOLLOWING AREAS AND SPACES: MINIMIZE THE NUMBER AND SIZE OF ACCESS PANELS. 206.720.2949 fax
<br /> 1. AREAS THAT ARE CONTROLLED BY AN OCCUPANT-SENSING DEVICE. 8. ALL CONDUITS, BOXES, DUCTS, HVAC UNITS, PIPES, ETC., SHALL BE INSTALLED
<br /> � � I EQUIPMENT ROOMS STOREROOMS, RESTROOMS, PUBLIC AS HIGH AS POSSIBLE, NOT LOWER THAN 8" ABOVE LINE OF HIGHEST FINISHED www.craftarchitects
<br /> a I a � I 2 LOBBIES,RELECTRICAL OR MECHANICAL ROOMS. .com
<br /> 3. DAYLIGHT SPACES COMPLYING WITH SECTION C405.22.3.2. CEILING.
<br /> 9. THERE SHALL BE NO COMBUSTIBLE MATERIALS IN THE PLENUM SPACE.
<br /> 10. WHEN MULTIPLE SWITCHES OCCUR IN CLOSE PROXIMITY GANG UNDER SINGLE
<br /> - - ' C405.2.2.1 AUTOMATIC TIME SWITCH CONTROL DEVICES. AUTOMATIC TIME SWITCH SWITCH PLATE. N
<br /> � CONTROLS NEED NOT BE IN SPACES CONTROLLED BY OCCUPANCY SENSORS. 11. FURNISH AND INSTALL NEW THERMOSTATS AS REQUIRED. INSTALL CLOSE TO
<br /> -� 3 DOOR OPENINGS, DO NOT INSTALL IN CENTER OF WALL. ARCHITECT AND CLIENT W
<br /> � C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL BE INSTALLED IN TO APPROVE ALL LOCATIONS. �^
<br /> � ALL CLASSROOMS, CONFERENCE/ MEEfING ROOMS, EMPLOYEE LUNCH AND BREAK 12. ALL LIGHTS TO BE CONTROLLED BY MOTION SENSOR. PROVIDE OVERRIDE �'�
<br /> XIT ' SWITCH AT ALL CONFERENCE ROOMS Q
<br /> 13. ALL LAMPS SHALL BE IDENTICAL FROM ONE MANUFACTURER IN SAME _
<br /> ROOMS, PRIVATE OFFICES, RESTROOMS, WAREHOUSE SPACES, STORAGE ROOMS TEMPERATURE, UON. �
<br /> 9 I AND JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR
<br /> AS 2 LESS ENCLOSED BY FLOOR-TO- CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
<br /> I � CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS CEILING NOTES' � � • �
<br /> � I WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL EITHER �j' Q
<br /> BE MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY T ` 0
<br /> � URN THE LIGHTING �, CENTER CEILING GRID IN ROOM OR AREA IN TWO DIRECTIONS, TYPICAL UON. � L.� > N
<br /> ON TO NOT MORE THAN 50 PERCENT POWER.
<br /> 2. CENTER LIGHT FIXTURES/SPRINKLER HEAD/CEILING ELEMENT IN 24" PORTION OF '� �
<br /> TAT CGMP B 6 C4052.2.3 DAYLIGHT ZONE CONTROL. DAYLIGHT ZONES SHALL BE DESIGNED SUCH 48" CEILING TILE, TYPICAL UON. � � � �
<br /> � ❑ �2 0 GENERAL AREA LIGHTINGYANDTARONCONTROLL�EDRNLAGCORDANCEDWNTHYS�CTION 3 SORAGHTLINEISHANDIXNUCENTER OFECEILINIGETILES�UON�ICES, ETC., IN � �
<br /> � . O > a
<br /> C405.2.2.3.2. EACH DAYLIGHT CONTROL ZONE SHALL NOT EXCEED 2,500 SQUARE 4. REFER TO ELEVATIONS AND SECTIONS FOR MOUNTING HEIGHTS OF WALL � O Q �
<br /> I' FEET (232 M2). CONTIGUOUS DAYLIGHT ZONES ADJACENT TO VERTICAL SURFACE MOUNTED LIGHT FIXTURES. � �
<br /> o FENESTRATION ARE ALLOWED TO BE CONTROLLED BY A SINGLE CONTROLLING 5. PROVIDE SEISMIC BRACING AT ALL SUSPENDED CEILING SYSTEMS. SUSPENDED --
<br /> ' i DEVICE PROVIDED THAT THEY DO NOT INCLUDE ZONES FACING MORE THAN TWO CEILING AND BRACING SHALL MEET THE MINIMUM REQUIREMENTS OF CISCA AND Q �•• Q
<br /> ; � ADJACENT CARDINAL ORIENTATIONS (I.E.,NORTH, EAST, .SOUTH, WEST). THE PRIMARY ASCE 7-10 SECTION 13.5.6. AS SUMMARIZED ON SHEET A8.1 � W
<br /> DAYLIGHT ZONE SHALL BE CONTROLLED SEPARATELY FROM THE SECONDARY �
<br /> � � � �
<br /> DAYLIGHT ZONE. DAYLIGHT ZONES UNDER SKYLIGHTS MORE THAN 15 FEEf (4572 � � � �
<br /> , 5 MM) FROM THE PERIMETER SHALL BE CONTROLLED SEPARATELY FROM DAYLIGHT Z
<br /> ZONES ADJACENT TO VERTICAL FENESTRATION. LEGEND' W Q (� �
<br /> � � CONTROL SHALL: � �
<br /> 1. CONTROL ONLY LUMINAIRES WITHIN THE DAYLIT AREA. � Z
<br /> I 2. INCORPORATE TIME-DELAY CIRCUITS TO PREVENT CYCLING OF LIGHT LEVEL � INTERNALLY ILLUMINATED EXIT SIGNAGE W BATTERY BA K P W
<br /> i CHANGES OF LESS THAN THREE MINUTES. EXIT EXIT D � C U PER
<br /> � , EXCEPTION: DAYLIGHT ZONES ENCLOSED BY WALLS OR CEILING HEIGHT o I$C SECTION 1013, CONFIRM OPERATION FOR EXISTING. ADD ~
<br /> � PARTITIONS AND CONTAINING TWO OR FEWER LIGHT FIXTURES ARE NOT WHERE NOT EXISTING. ARROW = DIRECTION INDICATOR, IF REQUIRED �
<br /> REQUIRED TO HAVE A SEPARATE SWITCH FOR GENERAL AREA LIGHTING.
<br /> f��l 1X4 SURFACE MOUNTED LED FIXTURE W/ WRAP AROUND U
<br /> C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL BE INSTALLED IN �-�' � ACRYLIC LENS �
<br /> � � ALL CLASSROOMS, CONFERENCE/ MEETING ROOMS, EMPLOYEE LUNCH AND BREAK �
<br /> � CONTROLS DEVICE SHALL BE CAPABLE OF AUTOMATICALLY REDUCING THE NEW 2X4 LAY-IN LED LIGHT, DIRECT/INDIRECT LENS �
<br /> � ! I LIGHTING POWER IN RESPONSE TO AVAILABLE DAYLIGHT BY EITHER ONE OF THE o
<br /> FOLLOWING METHODS:
<br /> - - - - _ _ _ 1. CONTINUOUS DIMMING USING DIMMING BALLASTS AND DAYLIGHT-SENSING HATCH INDICATES "NIGHT LIGHT" FOR EGRESS ILLUMINATION
<br /> I � 4 AUTOMATIC CONTROLS THAT ARE CAPABLE OF REDUCING THE POWER OF NOT LESS THAN 1 FC PER IBC SECTION 1008.2.1. CONSULTANT
<br /> � GENERAL LIGHTING IN THE DAYLIT ZONE CONTINUOUSLY TO LESS THAN 20
<br /> I - PERCENT OF R,4TED POWER AT MAXIMUM LIGHT OUTPUT.
<br /> 2. STEPPED DIMMING USING MULTI-LEVEL SWITCHING AND DAYLIGHT-SENSING � 4'-0" LINEAR LIGHT FIXTURE (6" WIDE)
<br /> I CONTROLS THAT ARE CAPABLE OF REDUCING LIGHTING POWER AUTOMATICALLY.
<br /> THE SYSTEM SHALL PROVIDE A MINIMUM OF TWO CONTROL CHANNELS PER NEW DIRECTIONAL RECESSED LED DOWNLIGHT FIXTURE
<br /> ZONE AND BE INSTALLED IN A MANNER SUCH THAT AT LEAST ONE CONTROL �� �
<br /> STEP IS BETWEEN 50 PERCENT AND 70 PERCENT OF DESIGN LIGHTING POWER
<br /> AND ANOTHER CONTROL STEP IS NO GREATER THAN 35 PERCENT OF DESIGN NEW RECESSED LED DOWNLIGHT FIXTURE
<br /> POWER, AND THE SYSTEM IS CAPABLE OF AUTOMATICALLY TURNING THE O
<br /> SYSTEM OFF. �
<br /> � j NEW SURFACE MOUNTED PENDANT LIGHT
<br /> C408.3.1 FUNCTIONAL TESTING. TESTING SHALL ENSURE THAT CONTROL HARDWARE
<br /> I I AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER
<br /> WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND � NEW WALL MOUNTED LED VANITY LIGHT FIXTURE
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS.
<br /> � � NEW HVAC SOLUTION SHALL MEET THE FOLLOWING MINIMUM REQUIREMENT: 7052
<br /> I REGISTEREO
<br /> A. NEW MECHANICAL ELEMENTS, INCLUDING BUT NOT LIMITED TO PACKAGED UNITS,
<br /> � EXIT CONTROLS, DAMPERS, DUCTING, COMMISSIONING; TO FULLY COMPLY WITH THE � EXHAUST FAN (SONE RATING LESS THAN 1.0 SONE) ARCHITECT
<br /> � PROVISIONS OF WSEC SECTION C403. -- _��
<br /> �o B. VENTILATION REQUIREMENTS FOR RESTROOMS PER WASHINGTON STATE SUSPENDED ACOUSTIC CEILING TILE AND GRID: .
<br /> MECHANICAL CODE (WAC 51-52) ACOUSTICAL CEILING SYSTEM, ARMSTRONG CORTEGA, SECOND ' KA�FfR , CRAFT
<br /> "' LOOK II, 2767, 2X4 SCORED TO 2X2, WHITE, ANGLED TEGU� StATE OF HINGTON
<br /> C. ALL OCCUPIED SPACES SHALL BE VENTILATED BY MECHANICAL MEANS IN
<br /> EXIT ACCORDANCE WITH SECTION 403 IN THE 2015 INTERNATIONAL MECHANICAL CODE THE EDGE WITH 15/16" PRELUDE GRID, WHITE OR EQUIVALENT
<br /> I n VENTILATION SYSTEM SERVING THE SPACE SHALL BE DESIGNED TO PROVIDE
<br /> � i I I VENTILATION OVER AND ABOVE THAT REQUIRED BY TABLE 403.3 IN ACCORDANCE WITH GWB
<br /> EXIT I ACCEPTED ENGINEERING PR,4CTICE. GYPSUM BOARD CEILING Submittals�Revisions:
<br /> I I NEW EXIT SIGNAGE SHALL MEET THE FOLLOWING MINIMUM REQUIREKAENTS:
<br /> - A. ALL REQUIRED EXIT SIGNS SHALL HAVE LETTERS SIX INCHES HIGH MiNiMUM a,►v� FOR PERMIT 08 08 2018
<br /> TAT RECEIVING - SHALL CONFORM WITH ALL APPLICABLE CODES. � �
<br /> 133 _ THE BUILDING IS FULLY SPRINKLERED. THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE OPEN TO STRUCTURE
<br /> � FIRE PROTECTION DRAWINGS AS REQUIRED BY THE GOVERNING AUTHORITY. THE FIRE FOR BID 08/16/2018
<br /> PROTECTION CONTRACTOR SHALL SUBMIT DRAWINGS TO THE ARCHITECT FOR REVIEW PRIOR TO
<br /> I � ' COMMENCING WITH THE WORK.
<br /> � � � PERMIT CORRECTION 10/22/2Q18
<br /> I DAYLIGHT ZONE
<br /> � (PRIMARY DEPTH = TO WINDOW HEAD HEIGHT, 24" BEYOND FOR CONSTRUCTION 12/18/2018
<br /> �
<br /> 0 j WIDTH OF WINDOW) '
<br /> iI (SECONDARY DEPTH = 2 TIMES WINDOW HEAD HEIGHT) � PERMIT REVISION 01 11
<br /> , /2019
<br /> NOTE: �
<br /> - - FOR POSSIBLE FUTURE EQUIPMENT AND STORAGE NEEDS ON THE TOP OF TAT AREAS THE
<br /> �- - - 5 STRUCTURE OF TAT IS DESIGNED FOR 125 PSF LIVE LOAD. SEE STRUCTURAL DRAWINGS AND +X'-X' INDICATES CEILING HEIGHT ABOVE FINISHED FLOOR
<br /> � CALCULATIONS.
<br /> �
<br /> - - - KEY NOTES� O
<br /> WASTE ACCUMULATION �. cE���N� �R�� sTART Po�NT. Sheet Title: REFLECTED CEILING PLAN
<br /> SHIPPING & RECEIVING
<br /> � 130 ;� 2. NOT USED
<br /> � 3. NOT USED
<br /> PARTIAL 1 ST FLOOR
<br /> Z � 4. NOT USED
<br /> � N
<br /> a
<br /> �
<br /> 5. FUTURE WORK UNDER SEPARATE PERMIT. Date: 08�08�2018
<br /> Z 6. WORK UNDER SEPARATE PERMIT.
<br /> W a
<br /> U -
<br /> O I
<br /> � Design:
<br /> W
<br /> J
<br /> �
<br /> Drawn:
<br /> � -� - - - - - 6
<br /> �
<br /> Project No: 18-076.05
<br /> o �
<br /> �
<br /> r
<br /> 0
<br /> �
<br /> Approved: KCR
<br /> �
<br /> �
<br /> Building No:
<br /> � REFLECTED CEILING PLAN - PARTIAL 1ST FLOO
<br /> �
<br /> � Z � 1/8" _ � '-o" Sheet No:
<br /> .
<br /> COPYRIGHT CRAFT ARCHITECTS 2018
<br />
|