Laserfiche WebLink
'`4 <br /> �i O MECHANlCAL NOTES: -� <br /> � 1. DUCT MATERIAL IS 26 GA. GALV. AND FLEX DUCT. DUCTWORK SHALL BE SUPPORTED PER 2015 IMC <br /> WAC CHAPTER 6. SECTION 603 <br /> 2. MATERIAL iN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25, SMOKE DEVELOPMENT <br /> OF 50 PER 2015 iMC WAC CHAPTER 6. SECTION 602 <br /> 3. LOW PRESSURE DUCT SYSTEMS SHALL HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND <br /> CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND SEALED WITH � <br /> WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC SYSTEMS OR APPROVED TAPES • . <br /> INSTALLED IN ACCORDANCE WITH 2O15 IMC WAC CHAPTER 6 SECTION 603.9. <br /> CD-1 CD-1 <br /> 10" 10" 4. WHEN ISOLATION SLEEVES ARE USED AT LINE C�NNECTIONS TO PLENUMS, THEN THEY SHALL COMPLY . <br /> WITH IMC CHAPTER 6 . <br /> WALL MOUNT <br /> 72� ,o\ ,O RETURN 5. 10" DIFFUSERS WtTH NO MANUAL DAMPERS. USE FLOW CONTROLS AT WYES, TYPICAL AS NOTED ON PLAN <br /> � O � 2 6. MINIMUM OUTSIDE AIR VENTILATION PER 2015 IMC WAC CHAPTER 4, TABLE 4p3.3.1.1. • <br /> ^ 7. OUTSIDE AIR DAMPERS SHALL COMPLY WITH 2O15 WSEC, SECTION C403.2.4.3. <br /> 10 12 HP-� . <br /> 0�1� 8. SINGLE PACKAGE UNITARY FAN COOLWG UNITS HAVING A TOTAL COOLING CAPACITY OF GREATER THAN <br /> 2'1 o T TCURBF 20,000 Btu/h REQUIRE ECONOMIZERS PER WSEC 403.3. EXCEPT AS PERMITTED BY C403.3 EXCEPTION 1 � <br /> O - - - - - - - - - � - - - - - - . • <br /> SUPPLY PLENUM <br /> #Pws�3� MECHANICAL NOTES: (cont.) <br /> OCCUPIED SET POINT MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUILDING SHALL BE IN ACCORDANCE WITN - <br /> TO BE CONTROLLED BY THE REQU�REMENTS OF THE 2015 IMC WAC CHAPTER 6. <br /> nLiGHT OCCUPANCY <br /> SENSORS ROUND FLEX DUCT SHALL BE U.L. LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR DUCTS AND AIR <br /> CONNECTORS. MEASURED IN ACCORDANCE TO ASTM C 518 OR ASTM C 177 AT 75DEG F MEAN � <br /> TEMPERATURE. INSTALLATION SHALL BE W ACCORQANCE WITH MANUFACTURES WSTALLATION INSTRUCT�ONS <br /> CD-1 CD-1 <br /> �� ���� MECHANICA� DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR INSIDE DIMENSION. ' <br /> DUCT INSULATION SHALL COMPLY WITH 2O15 IMC WAC CHAPTER 6, SEC. 604. ; � <br /> � ��� <br /> ELECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. <br /> THERMOSTAT SCHEDULING TO BE PERFORMED ON SITE BY OTHERS. � <br /> ALL MVAC EQUIPMENT LEAVES FACTORY WIRED FOR 240 VOLT OPERATION <br /> OTHE ACCEPTABLE OPERATING RANGE FOR THE 240V & 208V TAPS ARE; <br /> C TAP RANGE <br /> 24-0 253-216 . <br /> M EC HAN I CRL P LAN 208 220_�8� . <br /> 1/4" = 1'-0" SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS CONNECTED FOR , <br /> THE APPLIED SITE VOLTAGE. <br /> MINIMUM VENTILATION RATES PER IMC SECTIC7N 403 AIR FILTERS IN HVAC UNITS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY OTHERS QN SITE. <br /> Rp . <br /> room# name Az (sf} sf/1000 Occ. Dens Pz(calc) Pz(used) (cfm/person) Ra(cfm/sf) Vbz(cfm) REGISTER AIR FLOW TEST AND BALANCE OF HVAC SYSTEM TO BE PROVIDED AND PERFORMED BY OTHERS ON SITE. <br /> 1 Classroom 817 0.817 35 29 29 10 0.12 388 <br /> 388cfm HVAC SITE CONTRACTOR IS RESPONSIBLE FOR BALANCING THE SYSTEM. (2015 IMC WAC 403.3.3.1.5) . <br /> Az=room area(sf) <br /> Occ. Dens=occupant density(from Table 403.3) , <br /> Pz(calc) =zone popufation or occupant quantity(calculatedj <br /> Pz(used) =zone population or occupant quantity(user can override the calculation-increase only) ' � <br /> Rp=people outdoor airFlow rate in breathing zone (cfm/person) - <br /> Ra=area outdoor airflow rate in breathing zone (cfm/sf) <br /> Vbz=Breathin zone outdoor airflow rate er eq.4-1( R *Pz+Ra*Az) <br /> PACKAGE *SPVU* HIGH EFFICIENCY WALL MOUNT HEAT PUMP - SCHEDULE <br /> DOAS/ERV/E�ECTRICAL 1Q DOAS/ERV/ELECTRICAL Q COOLING CAPACITY 3Q HEATING CAPACITY � DOAS UNIT HEAT STRIPS <br /> ENERGY RECOVERY ELECT. INFORM. C . INFORM. <br /> DOAS LQW VENTILATION MODE FULL VENTILATION MODE ELEC. ELEC. OPER. <br /> COMP TOTAL ECON. COOL SENS. COOL SENS. HTG HTG OUTDOOR ' <br /> BARD TYPE CFM BLR. 100% ERV ECM ECM OUTSIDE ENT ENT CAP. CAP. CAP. CAP. OUTSIDE CAP. CAP. SUMMER �B/WB HRS HRL WINTER INDOOR WHR HEAT HEAT WGT. ADDITIONAL <br /> TAG QTY MODEL # TONS SCROLL NOM. TYPE. FREEFLOW OSA V-PH ERV BLOWER V-PH ERV BLOWER DB DB WB EER IPLV BTUH BTUH BTUH BTUH DB COP BTUH BTUH EFFICIENT DEG'S BTUH BTUH EFFICIENT DB MOP V-PH MCA MOP CKT V-PH MCA BTUH CKT KW BTUH LBS. REMARKS <br /> PART/FUl VENTIL. MOTOR .MOTOR PART LOAD PART lOAD FULL LOAD FULI tOAD � PART/LOAD FULL/LOAD � � � � <br /> 750 388 AMPS-1.3 AMPS-.87 AMPS-2.2 AMPS-1.74 � • <br /> HP-1 1 C36HA-A10ZP4XXR 3 2-STAGE ���Q ECM NO 450 230�� WATTS-296 WATTS-95 230�� WATTS-497 WATTS-192 95 80 67 11.0 14.5 23.4K 18.5K 35K 26.3K 47 3.3 22.7K 31K 65� 95/70 6,318 1,711 80� 1,711 23,328 230/1 27 40 A 240/1 52 60 B 10 34;130 678 1, 2, 3, 4, 5, 6, 7, 8 � <br /> ADDITIONA� REMARKS; c3sH� The sequence of operation for the Integrated DOAS s sY tem• <br /> 2 - INCLUDE BARD WALL CURB #TCURBF3642A-4. ERV Wqtts - Low 296 Watts Blower Full Load 192 Watts 1. Upon a call from the occupancy sensor the(DOAS) ERV and the indoor(ECM)motor will <br /> 3 - THERMOSTAT, BARD # 8403-060, 7-DAY PROGRAMMAB�E. ERV Am s - Low 1.3 Am s Blower Full Lood 1.74 Am s start in low vent mode and ventilate the space continuously as oceupied. <br /> 4 - WALL CO2 SENSOR. #8403-067 ERV CFM - Low 300 CFM Blower Part Load 95 Watts Note: 1 on the HVAC Schedule. <br /> 5 - OCCUPANCY SENSOR, (SUPPLIED BY BLAZER) ERV Watts - Med 415 Watts Blower Part Load 0.87 Am s 2, Upon a call from the CO2 sensor the(DOAS)ERV and the indoor(ECM)motor will <br /> 6 - GPS (FIELD INSTALLED CONTROL KIT). ERV Am s - Med 1.$ Am s <br /> � - 2" FILTER. ERV CFM - Med 375 CFM Com ressor Full 2588 Watts change to full vent mode and ventilate the space until the CO2 sensor is satisfied and then • <br /> 8 - ERV (DOAS) ENERGY RECOVERY. ERV Watts - Hi 497 Watts Com ressor Full 11.46 Am s revert back to the low vent mode during the occupied time. � <br /> 9 - UNIT COLOR IS *BUCKEYE GRAY* ERV Am s - Hi 2.2 Am s Com ressor Part 1734 Watts Note: 2 on the HVAC Schedule. <br /> 10 - PRE WSTALLED OUTDOOR THERMOSTAT, SET AT 40DEG'S. ERV CFM - Hi 450 CFM Com ressor Port 7.99 Am s 3. The Heating and Cooling section will only work if there is a Heating or Cooling call from , <br /> *� M.C. TO REFER TO INSTALLATION INSTRUCTIONS FOR START UP AND EQUIPMENT SET. Outdoor Fan 38o Watts the thermostat. This action works entirely independent of the DOAS ventilation portion. <br /> ** M.C. TO CHECK SITE VOLTAGE AND SET CORRECT TAP ON TRANSFORMER. Outdoor Fan 1.67 Am s Note: 3&4 on the HVAC Schedule. . <br /> ** M.C. TO SET AND PROGRAM THERMOSTAT PER CUSTOMERS REQUiREMENTS. 4. This action will keep repeating itself as required by the occupancy sensor, CO2 S@t150f ' <br /> and Room Thermostat. , <br /> 8-18-17 REVISE HEAT PUMP SCHEDULE,ADD SEQUENCE OF OP, RMS COPYRIGHT 2017, BLAZER INDUSTRIES, INC. � MODULAR C/assroom for., Approved for Const: Job No: �J031 <br /> 9-6-17 ADD SUPPLY PLENUM NUMBER (#PWS131) LDG THIS MATERIAL IS THE EXCLUSIVE PROPERIY . <br /> OF BLP,ZER INDUSTRIES, INC.AND SHALL ■� File Copy: <br /> NOT BE REPRODUCED, USED,OR DISCLOSED - 2$ X 32 KC DA - Eve rett S�D■ <br /> �� INQUSTRIES,WC. <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE �� wwv,,.blazerind.com Drawn By: LDG � <br /> DATE REVISION BY WRIITEN PERMISSION OF BLAZER INDUSTRIES. �� P.O.BOX 489 ■ Aumsville,OR 97325-0489 WA. GOLD Pacific Mobile 17 BLMP-04 A9 WA Issue�ate: 9-6-97 <br />