Laserfiche WebLink
COMFORT" lart <br /> SYSTEMS <br /> Northwest <br /> Review Comments(via E-mail 1-15-2019) Response(by EA and SAL) <br /> The following should be addressed for the drawings: <br /> 3. A drawing with the structural notes and detail(s) 3. Drawing sheet S2.1 addresses this comment. <br /> for the support of the mechanical units should be <br /> submitted for inclusion in the drawing set. <br /> 4. Detail SSK-2 is partially unreadable(i.e.,left side).A 4. Detail SSK-3 on drawing S2.1 addresses this <br /> clear copy should be used. comment. <br /> 5. A partial plan clarifying the proposed construction 5. Detail SSK-2 on drawing S2.1 addresses this <br /> of the mechanical unit support framing is comment. <br /> recommended. <br /> 6. The following revisions to Detail SSK-2 are 6. Detail SSK-3 on drawing S2.1 has been revised. <br /> recommended <br /> a. The 4x8 blocking appears to be connected to <br /> the sleepers using Simpson HU hangers.The <br /> make and specific model of the hangers should <br /> be stated. <br /> b. The detail specifies connecting the channel <br /> curb to the sleepers with sheet metal screws. <br /> Wood screws should be used. <br /> Feel free to contact me if you have any questions or comments. <br /> Sincerely, <br /> „Afix4X5-0-, <br /> Stephen A. Lehtinen, P.E. <br /> Principal Mechanical Engineer <br /> Comfort Systems USA NW <br /> Email: steve.lehtinen@comfortsystemsusa.com <br /> Direct: (425)602-3247 <br /> Page 2 of 2 <br /> 18702 North Creek Pkwy,Ste 1101 Bothell,Washington 98011 1(425)883-92241 www.comfortsystemsusanorthwest.com Quality People Building SolutionsTM <br />