<br /> 2015 Washington State EnUlg Lode Compliance Forms for Commercial,R2 and R3 over u Ali ies and all R1-Page 2 of 7
<br /> Mechanical Permit Plans Checklist MECH-CHK
<br /> 2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2&R3 over 3 stories and all R1 Revised January 2017
<br /> Project Title: Car Toys Everett,WA RTU replacement Date 9/23/2019
<br /> The following inforin4tion is necessary to check a permit application for compliance with the mechanical systems and equipment requirements of the
<br /> Washington State Energy Code,Commercial Provisions.
<br /> Applicable Code Section Code Provision Information Required-Must be in permit documents Location in Building Department
<br /> (yes,no,na) Documents Notes
<br /> NA 0403.2.4.3 Stairway and shaft vent Indicate location of stairway and shaft vent dampers on plans;verify dampers are Class 1
<br /> dampers motorized;refer to HVAC System Controls for additional requirements
<br /> , For systems serving areas>25,000 sf or spanning more than one floor,that include areas that
<br /> NA C4� ?i4r4 Zon, anon dampers are expected to be occupied non-simultaneously;identify isolation zone areas on plans and
<br /> locations of associated isolation dampers in HVAC distribution system;refer to HVAC System
<br /> I. i :I.' Controls for additional requirements
<br /> r !ii For cooling systems with humidification equipment that are also required to have air
<br /> NA dot 2314 Humid Cation economizer,indicate humidifier is adiabatic(direct evaporative or fog atomization),or
<br /> ,1
<br /> .' exception taken
<br /> Additional Efficiercy Package Option,More Efficient HVAC Equipment&Fan Performance-
<br /> Must comply with all 3 provisions to be eligible
<br /> 0406.2.1 To complywith additional efficiency package option,calculate the percentage of heating and
<br /> NA 04031.2.3 HVAC system selection cooling equipment in the project(based on output capacity)that do not have a corresponding
<br /> WSEC listed efficiency;shall be less than 10%to comply
<br /> •
<br /> NA C406..2.2 Minimum equipment To complywith additional efficiency package option,indicate that all listed heating and cooling
<br /> 0403.2.3 efficiency equipment have a rated efficiency that exceeds WSEC listed efficiency by at least 15%
<br /> 0406.2.3 To complywith additional efficiency package option,indicate rated FEG of stand alone fans is
<br /> NA 0403.2.11.3 Minimum fan efficiency z 71;indicate these fans are sized so the fan efficiency at design conditions is within 10%of
<br /> the maximum total or static efficiency
<br /> HVAC System Controls
<br /> Indicate locations of thermostatic and humidity control devices and the zones they serve on
<br /> plans,including perimeter system zones
<br /> Where adjacent(neighboring)zones are controlled by separate thermostats(including
<br /> perimeter systems used to offset heat gain or loss),and are connected by permanent
<br /> Thermostatic controls openings>10%of either zone sf area,indicate controls configured to prevent adjacent zones
<br /> NA 04032.4.1 (thermostats and from operating in conflicting modes(one in heat,other in cool);applies to adjacent perimeter
<br /> humidistats) zones,adjacent nonperimeter zones,and adjacent perimeter and nonperimeter zones
<br /> If applying Exception 2 to nonperimeter zones adjacent to perimeter zones,indicate that
<br /> setpoints and deadband settings in these zones are coordinated so cooling in a nonperimeter
<br /> ' zone does not occur until the temperature in that zone is 5°F higher than the adjacent
<br /> I '! perimeter zone temperature in heating
<br /> Heat pa ll!)supplementary Indicate staged heating operation with compression as the first stage of heating and
<br /> Yes C if 1 all
<br /> i
<br /> 111 heat 11j supplemental heating controlled with outdoor lock-out temperature set to 40°F or less
<br /> I1 I Indicate zone thermostatic controls configured with 5°F minimum deadband for systems that
<br /> NA C4CY .1.2 D�adti�,id control both heating and cooling
<br /> '!1' 1i I I If separate heating and cooling systems with separate thermostatic control devices are used to
<br /> NA Setpoint'overtap restriction serve a zone,indicate locations of both thermostatic control devices and the zone they serve
<br /> C401.2.4.1.3 on plans
<br /> (thermostats)
<br /> NA Indicate a limit switch,mechanical stop or DDC control with programming to prevent
<br /> simultaneous heating and cooling
<br /> 0403y.4.2 Indicate zone thermostatic controls configured with required automatic setback and manual
<br /> NA 0403.2.4.2.1 Automatic setback and override functions,setback temperatures,and control method(automatic time clock or
<br /> C403.2.4.2.2 shutdown programmable controls);note exceptions taken
<br /> NA C403.2.4.2.3 Automatic(optimum)start Indicate system controls that adjust equipment start time required to bring each area served
<br /> up to design temperature just prior to scheduled occupancy
<br /> NA 0403.2.4.3 Outdoorsupply air dampers Indicate automatic controls configured to close OSA damper during unoccupied equipment
<br /> operation;not including economizer cooling,night flush or IMC required OSA/exhaust
<br /> NA C403.2.4.3 Stairway and shaft vent Indicate method of activation of stairway and shaft vent dampers(fire alarm or interruption of
<br /> dampers power)
<br /> For systems serving areas>25,000 sf or spanning more than one floor,that include areas that
<br /> NA C403.2.4.4 Zone isolation controls are expected to be occupied non-simultaneously;indicate controls that allow for independent
<br /> space conditioning of isolation zones;or exception taken
<br /> NA 0403.2.12 Heating outside a building Indicate occupancy sensing or timer switch controls configured to automaticallyshut off
<br /> heating system when area served is unoccupied
<br /> NA 040322.4.5 Snow melt systems Indicate automatic controls configured to shut off system when pavement temperature
<br /> exceeds 50°F and no precipitation is falling,and when outdoor air temperature exceeds 40°F
<br /> NA 0403.2.4.6 Freeze protection system Indicate automatic controls to shut off system when outdoor temperature exceeds 40°F,or
<br /> controls conditions protect fluid from freezing
<br /> Group Ry hotel/motel For hotels and motels with over 50 guest rooms,indicate automatic controls serving guest
<br /> NA 0403.2.4.9 guest rooms rooms that are capable of setback(heating)and set-up(cooling)of temperature setpoint by at
<br /> least 5°F;indicate control method-activated by room entry or occupancy sensor
<br /> 0403 4, 0 Group 2/R3 dwelling For primary space conditioning system,indicate 5-2 programmable thermostats capable of two
<br /> NA' C4 I3 (1 urs,G up R2 sleeping setback periods per day;for all thermostats indicate purpose(heating only,cooling only,or
<br /> 0( '� inks both),required temperature range and at minimum a 10°F deadband;or exception taken
<br /> , 1Iui t III,
<br /> NA l'i iI` �i di &' Indicate method of ventilation air delivery(natural or mechanical)for each zone
<br /> � , ' If mechanically delivered,indicate that systems are configured to provide not more than 150%
<br /> NA C4 2.6 Ventilation of,but at least the minimum required volume of outdoor air to each zone per IMC,ASHRAE
<br /> C403. .11.4 62.1 or other applicable code(WAC,OSHA,etc);or exception taken
<br />
|